B-46
D30 Line Distance Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
9AA1
Teleprotection Channel 1 Number of Lost Packets
0 to 65535
---
1
F001
0
9AA2
Teleprotection Channel 2 Status
0 to 2
---
1
F134
2 (n/a)
9AA3
Teleprotection Channel 2 Number of Lost Packets
0 to 65535
---
1
F001
0
9AA4
Teleprotection Network Status
0 to 2
---
1
F134
2 (n/a)
9AAF
Teleprotection Channel 1 Input States
0 to 1
---
1
F500
0
9AB0
Teleprotection Channel 2 Input States
0 to 1
---
1
F500
0
9AC0
Teleprotection Input 1 States, 1 per register (16 items)
0 to 1
---
1
F108
0 (Off)
9AD0
Teleprotection Input 2 States, 1 per register (16 items)
0 to 1
---
1
F108
0 (Off)
VT Fuse Failure (Read/Write Setting) (2 modules)
A09A
VT Fuse Failure 1 Function
0 to 1
---
1
F102
0 (Disabled)
A09B
VT Fuse Failure Neutral Wire Open 1 Function
0 to 1
---
1
F102
0 (Disabled)
A09C
VT Fuse Failure Neutral Wire Open 1 3rd Harmonic Pickup
0 to 3
pu
0.001
F001
100
A09D
...Repeated for module number 2
VT Fuse Failure Actuals (Read Only) (2 modules)
A0AC
VT Fuse Failure 1 V0 3rd Harmonic
0 to 999999.999
V
0.001
F060
0
A0AE
...Repeated for module number 2
A0C0
Summator 1 Function
0 to 1
---
1
F102
0 (Disabled)
Selector Switch Actual Values (Read Only)
A210
Selector Switch 1 Position
1 to 7
---
1
F001
0
A211
Selector Switch 2 Position
1 to 7
---
1
F001
1
Selector Switch Settings (Read/Write) (2 modules)
A280
Selector 1 Function
0 to 1
---
1
F102
0 (Disabled)
A281
Selector 1 Range
1 to 7
---
1
F001
7
A282
Selector 1 Timeout
3 to 60
s
0.1
F001
50
A283
Selector 1 Step Up
0 to 4294967295
---
1
F300
0
A285
Selector 1 Step Mode
0 to 1
---
1
F083
0 (Time-out)
A286
Selector 1 Acknowledge
0 to 4294967295
---
1
F300
0
A288
Selector 1 Bit0
0 to 4294967295
---
1
F300
0
A28A
Selector 1 Bit1
0 to 4294967295
---
1
F300
0
A28C
Selector 1 Bit2
0 to 4294967295
---
1
F300
0
A28E
Selector 1 Bit Mode
0 to 1
---
1
F083
0 (Time-out)
A28F
Selector 1 Bit Acknowledge
0 to 4294967295
---
1
F300
0
A291
Selector 1 Power Up Mode
0 to 2
---
1
F084
0 (Restore)
A292
Selector 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A293
Selector 1 Events
0 to 1
---
1
F102
0 (Disabled)
A294
Reserved (10 items)
---
---
1
F001
0
A29E
...Repeated for Selector 2
Digital Counter (Read/Write Setting) (8 modules)
A300
Digital Counter 1 Function
0 to 1
---
1
F102
0 (Disabled)
A301
Digital Counter 1 Name
---
---
---
F205
“Counter 1"
A307
Digital Counter 1 Units
---
---
---
F206
(none)
A30A
Digital Counter 1 Block
0 to 4294967295
---
1
F300
0
A30C
Digital Counter 1 Up
0 to 4294967295
---
1
F300
0
A30E
Digital Counter 1 Down
0 to 4294967295
---
1
F300
0
A311
Digital Counter 1 Preset
–2147483647 to
2147483647
---
1
F004
0
A313
Digital Counter 1 Compare
–2147483647 to
2147483647
---
1
F004
0
A315
Digital Counter 1 Reset
0 to 4294967295
---
1
F300
0
A317
Digital Counter 1 Freeze/Reset
0 to 4294967295
---
1
F300
0
A319
Digital Counter 1 Freeze/Count
0 to 4294967295
---
1
F300
0
A31B
Digital Counter 1 Set To Preset
0 to 4294967295
---
1
F300
0
A31D
Reserved (11 items)
---
---
---
F001
0
A328
...Repeated for Digital Counter 2
A350
...Repeated for Digital Counter 3
Table B–10: MODBUS MEMORY MAP (Sheet 38 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...