B-66
D30 Line Distance Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
EC01
Synchrocheck 1 V1 Source
0 to 5
---
1
F167
0 (SRC 1)
EC02
Synchrocheck 1 V2 Source
0 to 5
---
1
F167
1 (SRC 2)
EC03
Synchrocheck 1 Maximum Voltage Difference
0 to 400000
V
1
F060
10000
EC05
Synchrocheck 1 Maximum Angle Difference
0 to 100
degrees
1
F001
30
EC06
Synchrocheck 1 Maximum Frequency Difference
0 to 2
Hz
0.01
F001
100
EC07
Synchrocheck 1 Dead Source Select
0 to 5
---
1
F176
1 (LV1 and DV2)
EC08
Synchrocheck 1 Dead V1 Maximum Voltage
0 to 1.25
pu
0.01
F001
30
EC09
Synchrocheck 1 Dead V2 Maximum Voltage
0 to 1.25
pu
0.01
F001
30
EC0A
Synchrocheck 1 Live V1 Minimum Voltage
0 to 1.25
pu
0.01
F001
70
EC0B
Synchrocheck 1 Live V2 Minimum Voltage
0 to 1.25
pu
0.01
F001
70
EC0C
Synchrocheck 1 Target
0 to 2
---
1
F109
0 (Self-reset)
EC0D
Synchrocheck 1 Events
0 to 1
---
1
F102
0 (Disabled)
EC0E
Synchrocheck 1 Block
0 to 4294967295
---
1
F300
0
EC10
Synchrocheck 1 Frequency Hysteresis
0 to 0.1
Hz
0.01
F001
6
EC11
...Repeated for Synchrocheck 2
EC22
...Repeated for Synchrocheck 3
EC33
...Repeated for Synchrocheck 4
Settings File Template (Read/Write Setting)
ED00
FlexLogic Displays Active
0 to 1
---
1
F102
1 (Enabled)
ED01
Reserved
---
---
---
F205
(none)
Setting File Template (Read Only Non-Volatile)
ED07
Last Settings Change Date
0 to 4294967295
---
1
F050
0
Settings File Template (Read/Write Setting)
ED09
Template Bitmask (750 items)
0 to 65535
---
1
F001
0
Table B–10: MODBUS MEMORY MAP (Sheet 58 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...