B-68
D30 Line Distance Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
F102
ENUMERATION: DISABLED/ENABLED
0 = Disabled, 1 = Enabled
F103
ENUMERATION: CURVE SHAPES
F104
ENUMERATION: RESET TYPE
0 = Instantaneous, 1 = Timed
F106
ENUMERATION: PHASE ROTATION
0 = ABC, 1 = ACB
F108
ENUMERATION: OFF/ON
0 = Off, 1 = On
F109
ENUMERATION: CONTACT OUTPUT OPERATION
0 = Self-reset, 1 = Latched, 2 = Disabled
F111
ENUMERATION: UNDERVOLTAGE CURVE SHAPES
0 = Definite Time, 1 = Inverse Time
F112
ENUMERATION: RS485 BAUD RATES
F113
ENUMERATION: PARITY
0 = None, 1 = Odd, 2 = Even
F114
ENUMERATION: IRIG-B SIGNAL TYPE
0 = None, 1 = DC Shift, 2 = Amplitude Modulated
F116
ENUMERATION: NEUTRAL OVERVOLTAGE CURVES
0 = Definite Time, 1 = FlexCurve A, 2 = FlexCurve B,
3 = FlexCurve C
F118
ENUMERATION: OSCILLOGRAPHY MODE
0 = Automatic Overwrite, 1 = Protected
F119
ENUMERATION: FLEXCURVE PICKUP RATIOS
Bitmask
Curve shape
Bitmask
Curve shape
0
IEEE Mod Inv
9
IAC Inverse
1
IEEE Very Inv
10
IAC Short Inv
2
IEEE Ext Inv
11
I2t
3
IEC Curve A
12
Definite Time
4
IEC Curve B
13
FlexCurve A
5
IEC Curve C
14
FlexCurve B
6
IEC Short Inv
15
FlexCurve C
7
IAC Ext Inv
16
FlexCurve D
8
IAC Very Inv
Bitmask
Value
Bitmask
Value
Bitmask
Value
0
300
4
9600
8
115200
1
1200
5
19200
9
14400
2
2400
6
38400
10
28800
3
4800
7
57600
11
33600
Mask
Value
Mask
Value
Mask
Value
Mask
Value
0
0.00
30
0.88
60
2.90
90
5.90
1
0.05
31
0.90
61
3.00
91
6.00
2
0.10
32
0.91
62
3.10
92
6.50
3
0.15
33
0.92
63
3.20
93
7.00
4
0.20
34
0.93
64
3.30
94
7.50
5
0.25
35
0.94
65
3.40
95
8.00
6
0.30
36
0.95
66
3.50
96
8.50
7
0.35
37
0.96
67
3.60
97
9.00
8
0.40
38
0.97
68
3.70
98
9.50
9
0.45
39
0.98
69
3.80
99
10.00
10
0.48
40
1.03
70
3.90
100
10.50
11
0.50
41
1.05
71
4.00
101
11.00
12
0.52
42
1.10
72
4.10
102
11.50
13
0.54
43
1.20
73
4.20
103
12.00
14
0.56
44
1.30
74
4.30
104
12.50
15
0.58
45
1.40
75
4.40
105
13.00
16
0.60
46
1.50
76
4.50
106
13.50
17
0.62
47
1.60
77
4.60
107
14.00
18
0.64
48
1.70
78
4.70
108
14.50
19
0.66
49
1.80
79
4.80
109
15.00
20
0.68
50
1.90
80
4.90
110
15.50
21
0.70
51
2.00
81
5.00
111
16.00
22
0.72
52
2.10
82
5.10
112
16.50
23
0.74
53
2.20
83
5.20
113
17.00
24
0.76
54
2.30
84
5.30
114
17.50
25
0.78
55
2.40
85
5.40
115
18.00
26
0.80
56
2.50
86
5.50
116
18.50
27
0.82
57
2.60
87
5.60
117
19.00
28
0.84
58
2.70
88
5.70
118
19.50
29
0.86
59
2.80
89
5.80
119
20.00
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...