GE Multilin
D30 Line Distance Protection System
5-121
5 SETTINGS
5.5 FLEXLOGIC
5
5.5.8 NON-VOLATILE LATCHES
PATH: SETTINGS
FLEXLOGIC
NON-VOLATILE LATCHES
LATCH 1(16)
The non-volatile latches provide a permanent logical flag that is stored safely and will not reset upon reboot after the relay
is powered down. Typical applications include sustaining operator commands or permanently block relay functions, such as
Autorecloser, until a deliberate interface action resets the latch. The settings element operation is described below:
•
LATCH 1 TYPE
: This setting characterizes Latch 1 to be Set- or Reset-dominant.
•
LATCH 1 SET
: If asserted, the specified FlexLogic operands 'sets' Latch 1.
•
LATCH 1 RESET
: If asserted, the specified FlexLogic operand 'resets' Latch 1.
Figure 5–48: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC
LATCH 1
LATCH 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
LATCH 1 TYPE:
Reset Dominant
Range: Reset Dominant, Set Dominant
MESSAGE
LATCH 1 SET:
Off
Range: FlexLogic operand
MESSAGE
LATCH 1 RESET:
Off
Range: FlexLogic operand
MESSAGE
LATCH 1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
LATCH 1
EVENTS: Disabled
Range: Disabled, Enabled
842005A3.CDR
LATCH 1 FUNCTION:
LATCH 1 TYPE:
LATCH 1 SET:
LATCH 1 RESET:
RUN
SET
RESET
SETTING
SETTING
SETTING
SETTING
FLEXLOGIC OPERANDS
Off=0
Off=0
Enabled=1
LATCH 1 ON
LATCH 1 OFF
LATCH N
TYPE
LATCH N
SET
LATCH N
RESET
LATCH N
ON
LATCH N
OFF
Reset
Dominant
ON
OFF
ON
OFF
OFF
OFF
Previous
State
Previous
State
ON
ON
OFF
ON
OFF
ON
OFF
ON
Set
Dominant
ON
OFF
ON
OFF
ON
ON
ON
OFF
OFF
OFF
Previous
State
Previous
State
OFF
ON
OFF
ON
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...