GE Multilin
D30 Line Distance Protection System
5-123
5 SETTINGS
5.6 GROUPED ELEMENTS
5
5.6.3 LINE PICKUP
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
LINE PICKUP
The line pickup feature uses a combination of undercurrent and undervoltage to identify a line that has been de-energized
(line end open). Alternately, the user may assign a FlexLogic operand to the
TERMINAL OPEN
setting that specifies the termi-
nal status. Three instantaneous overcurrent elements are used to identify a previously de-energized line that has been
closed onto a fault. Faults other than close-in faults can be identified satisfactorily with the distance elements.
Co-ordination features are included to ensure satisfactory operation when high speed automatic reclosure (AR) is
employed. The
AR CO-ORD DELAY
setting allows the overcurrent setting to be below the expected load current seen after
reclose. Co-ordination is achieved by all of the
LINE PICKP UV
elements resetting and blocking the trip path before the
AR
CO-ORD DELAY
times out. The
AR CO-ORD BYPASS
setting is normally enabled. It is disabled if high speed autoreclosure is
implemented.
The line pickup protection incorporates zone 1 extension capability. When the line is being re-energized from the local ter-
minal, pickup of an overreaching zone 2 or excessive phase current within eight power cycles after the autorecloser issues
a close command results in the
LINE PICKUP RCL TRIP
FlexLogic operand. For security, the overcurrent trip is supervised by
LINE PICKUP
LINE PICKUP
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
LINE PICKUP SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2
MESSAGE
PHASE IOC LINE
PICKUP: 1.000 pu
Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
LINE PICKUP UV PKP:
0.700 pu
Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
LINE END OPEN PICKUP
DELAY: 0.150
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
LINE END OPEN RESET
DELAY: 0.090
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
LINE PICKUP OV PKP
DELAY: 0.040
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
AR CO-ORD BYPASS:
Enabled
Range: Disabled, Enabled
MESSAGE
AR CO-ORD PICKUP
DELAY: 0.045
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
AR CO-ORD RESET
DELAY: 0.005
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
TERMINAL OPEN:
Off
Range: FlexLogic operand
MESSAGE
AR ACCELERATE:
Off
Range: FlexLogic operand
MESSAGE
LINE PICKUP DISTANCE
TRIP: Enabled
Range: Disabled, Enabled
MESSAGE
LINE PICKUP BLOCK:
Off
Range: FlexLogic operand
MESSAGE
LINE PICKUP
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
LINE PICKUP
EVENTS: Disabled
Range: Disabled, Enabled
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...