5 SETTINGS
5.6 GROUPED ELEMENTS
5
c) GROUND DISTANCE
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
DISTANCE
GROUND DISTANCE Z1(Z5)
GROUND DISTANCE Z1
GND DIST Z1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
GND DIST Z1 DIR:
Forward
Range: Forward, Reverse, Non-directional
MESSAGE
GND DIST Z1
SHAPE: Mho
Range: Mho, Quad
MESSAGE
GND DIST Z1
Z0/Z1 MAG: 2.70
Range: 0.00 to 10.00 in steps of 0.01
MESSAGE
GND DIST Z1
Z0/Z1 ANG: 0°
Range: –90 to 90° in steps of 1
MESSAGE
GND DIST Z1
ZOM/Z1 MAG: 0.00
Range: 0.00 to 7.00 in steps of 0.01
MESSAGE
GND DIST Z1
ZOM/Z1 ANG: 0°
Range: –90 to 90° in steps of 1
MESSAGE
GND DIST Z1
REACH: 2.00
Ω
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
GND DIST Z1
RCA: 85°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1 REV
REACH: 2.00
Ω
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
GND DIST Z1 REV
REACH RCA: 85°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1 POL
CURRENT: Zero-seq
Range: Zero-seq, Neg-seq
MESSAGE
GND DIST Z1 NON-
HOMOGEN ANG: 0.0°
Range: –40.0 to 40.0° in steps of 0.1
MESSAGE
GND DIST Z1
COMP LIMIT: 90°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1
DIR RCA: 85°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1
DIR COMP LIMIT: 90°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1 QUAD
RGT BLD: 10.00
Ω
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
GND DIST Z1 QUAD
RGT BLD RCA: 85°
Range: 60 to 90° in steps of 1
MESSAGE
GND DIST Z1 QUAD
LFT BLD: 10.00
Ω
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
GND DIST Z1 QUAD
LFT BLD RCA: 85°
Range: 60 to 90° in steps of 1
MESSAGE
GND DIST Z1
SUPV: 0.200 pu
Range: 0.050 to 30.000 pu in steps of 0.001
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...