background image

GE Multilin

D30 Line Distance Protection System

5-185

5 SETTINGS

5.6 GROUPED ELEMENTS

5

g) AUXILIARY OVERVOLTAGE

(ANSI 59X, IEC PTOV)

PATH: SETTINGS 



 GROUPED ELEMENTS 

 SETTING GROUP 1(6) 



 VOLTAGE ELEMENTS 



 AUXILIARY OV1

The D30 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage
conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under 

SYSTEM

SETUP 

 AC INPUTS 



 VOLTAGE BANK X5 



 AUXILIARY VT X5 SECONDARY

 is the per-unit (pu) base used when setting the

pickup level.

A typical application for this element is monitoring the zero-sequence voltage (3V_0) supplied from an open-corner-delta
VT connection.

Figure 5–97: AUXILIARY OVERVOLTAGE SCHEME LOGIC

 AUXILIARY OV1

 

AUX OV1

FUNCTION: Disabled

Range: Disabled, Enabled

MESSAGE

AUX OV1 SIGNAL

SOURCE: SRC 1

Range: SRC 1, SRC 2

MESSAGE

AUX OV1 PICKUP:

0.300 pu

Range: 0.000 to 3.000 pu in steps of 0.001

MESSAGE

AUX OV1 PICKUP

DELAY: 1.00 s

Range: 0.00 to 600.00 s in steps of 0.01

MESSAGE

AUX OV1 RESET

DELAY: 1.00 s

Range: 0.00 to 600.00 s in steps of 0.01

MESSAGE

AUX OV1 BLOCK:

Off

Range: FlexLogic operand

MESSAGE

AUX OV1 TARGET:

Self-reset

Range: Self-reset, Latched, Disabled

MESSAGE

AUX OV1 EVENTS:

Disabled

Range: Disabled, Enabled

827836A2.CDR

FLEXLOGIC OPERANDS

AUX OV1
FUNCTION:

AUX OV1 BLOCK:

AUX OV1 SIGNAL
SOURCE:

AUX OV1 PICKUP:

AUX OV1 DPO

AUX OV1 OP

AUX OV1 PKP

RUN

AND

SETTING

SETTING

AUX OV1 RESET
DELAY :

AUX OV1 PICKUP
DELAY :

SETTING

Enabled=1

Disabled=0

t

PKP

t

RST

SETTING

SETTING

Off=0

AUXILIARY VOLT (Vx)

Vx    Pickup

<

Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A

Page 1: ...0 Markland Street Markham Ontario Canada L6C 0M1 Tel 1 905 927 7070 Fax 1 905 927 5098 Internet http www GEDigitalEnergy com IISO 9001 G N E I L M I U T L TE S I R G E E D R GE Multilin s Quality Mana...

Page 2: ...r Digital Energy Multilin and GE Multilin are trademarks or registered trademarks of GE Multilin Inc The contents of this manual are the property of GE Multilin Inc This documentation is furnished on...

Page 3: ...ARCHY 1 18 1 5 4 RELAY ACTIVATION 1 18 1 5 5 RELAY PASSWORDS 1 19 1 5 6 FLEXLOGIC CUSTOMIZATION 1 19 1 5 7 COMMISSIONING 1 20 2 PRODUCT DESCRIPTION 2 1 INTRODUCTION 2 1 1 OVERVIEW 2 1 2 1 2 ORDERING 2...

Page 4: ...SETTINGS FILE TRACEABILITY 4 11 4 3 FACEPLATE INTERFACE 4 3 1 FACEPLATE 4 14 4 3 2 LED INDICATORS 4 15 4 3 3 CUSTOM LABELING OF LEDS 4 18 4 3 4 DISPLAY 4 23 4 3 5 KEYPAD 4 23 4 3 6 BREAKER CONTROL 4...

Page 5: ...S 5 178 5 7 CONTROL ELEMENTS 5 7 1 OVERVIEW 5 186 5 7 2 TRIP BUS 5 186 5 7 3 SETTING GROUPS 5 188 5 7 4 SELECTOR SWITCH 5 190 5 7 5 SYNCHROCHECK 5 196 5 7 6 AUTORECLOSE 5 200 5 7 7 DIGITAL ELEMENTS 5...

Page 6: ...SOURCES 6 14 6 3 3 SYNCHROCHECK 6 17 6 3 4 TRACKING FREQUENCY 6 18 6 3 5 FLEXELEMENTS 6 19 6 3 6 IEC 61580 GOOSE ANALOG VALUES 6 19 6 3 7 TRANSDUCER INPUTS OUTPUTS 6 20 6 4 RECORDS 6 4 1 FAULT REPORTS...

Page 7: ...TION 10 1 10 1 3 HIGH SET OVERCURRENT ELEMENTS 10 1 10 2 DISTANCE ELEMENTS STEPPED DISTANCE SCHEME 10 2 1 PHASE DISTANCE 10 2 10 2 2 GROUND DISTANCE 10 3 10 3 SERIES COMPENSATED LINES 10 3 1 INTRODUCT...

Page 8: ...UES FROM RECEIVED GOOSE DATA C 3 C 2 5 GGIO4 GENERIC ANALOG MEASURED VALUES C 3 C 2 6 MMXU ANALOG MEASURED VALUES C 4 C 2 7 PROTECTION AND OTHER LOGICAL NODES C 4 C 3 SERVER FEATURES AND CONFIGURATION...

Page 9: ...COMMUNICATIONS E 1 DEVICE PROFILE DOCUMENT E 1 1 DNP V3 00 DEVICE PROFILE E 1 E 1 2 IMPLEMENTATION TABLE E 4 E 2 DNP POINT LISTS E 2 1 BINARY INPUT POINTS E 8 E 2 2 BINARY AND CONTROL RELAY OUTPUT E...

Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...

Page 11: ...f the specified limits Only qualified personnel are to operate the device Such personnel must be thoroughly familiar with all safety cau tions and warnings in this manual and with applicable country r...

Page 12: ...tents listed are missing please contact GE Digital Energy immediately GE DIGITAL ENERGY CONTACT INFORMATION AND CALL CENTER FOR PRODUCT SUPPORT GE Digital Energy 650 Markland Street Markham Ontario Ca...

Page 13: ...rm func tions at both the station and supervisory levels The use of these systems is growing rapidly High speed communication is required to meet the data transfer rates required by modern automatic c...

Page 14: ...power lines The UR series relays support 1 A and 5 A CTs The remote inputs and outputs provide a means of sharing digital point state information between remote UR series devices The remote outputs i...

Page 15: ...he system Employing OOD OOP in the software architecture of the D30 achieves the same features as the hardware architecture modularity scalability and flexibility The application software for any UR s...

Page 16: ...to the UR Internet access or a DVD drive The following qualified modems have been tested to be compliant with the D30 and the EnerVista UR Setup software US Robotics external 56K FaxModem 5686 US Robo...

Page 17: ...tallation program automatically creates icons and adds EnerVista UR Setup to the Windows start menu 8 Click Finish to complete the installation The UR series device is added to the list of installed I...

Page 18: ...stalled 2 Connect the computer to the F485 and the F485 to the RS485 terminal on the back of the UR device or connect directly the computer to the RS232 port on the front of the relay 3 Select the UR...

Page 19: ...e The computer and UR device must be on the same subnet 1 Verify that the latest version of the EnerVista UR Setup software is installed available from the GE EnerVista CD or online from http www gedi...

Page 20: ...n of the EnerVista UR Setup software is installed available from the GE EnerVista CD or online from http www gedigitalenergy com multilin See the Software Installation section if not already installed...

Page 21: ...sign the computer an IP address compatible with the relay s IP address 1 From the Windows desktop right click the My Network Places icon and select Properties to open the network con nections window 2...

Page 22: ...ng Start Run from the Windows Start menu and typing cmd 2 Type the following command substituting the IP address of 1 1 1 1 with yours C WINNT ping 1 1 1 1 3 If the connection is successful the system...

Page 23: ...ata verify the physical connection between the D30 and the computer and double check the programmed IP address in the PRODUCT SETUP COMMUNICATIONS NETWORK IP ADDRESS setting then repeat step 2 7 If th...

Page 24: ...Quick Connect dialog box 4 Select the Ethernet interface and enter the IP address assigned to the D30 then click the Connect button The EnerVista UR Setup software creates a site named Quick Connect w...

Page 25: ...matically discover and communicate to all UR series IEDs located on an Ether net network Using the Quick Connect feature a single click of the mouse triggers the software to automatically detect any U...

Page 26: ...ed printed or changed See chapter 4 in this manual or the EnerVista UR Setup Help File for information about the using the EnerVista UR Setup software interface QUICK ACTION HOT LINKS The EnerVista UR...

Page 27: ...computer using a straight through serial cable A shielded twisted pair 20 22 or 24 AWG connects the F485 converter to the D30 rear communications port The converter terminals GND are connected to the...

Page 28: ...d actual value messages are arranged hierarchically The header display pages are indicated by double scroll bar characters while sub header pages are indicated by single scroll bar characters The head...

Page 29: ...MAND access level restricts the user from making any settings changes but allows the user to perform the fol lowing operations Operate breakers via faceplate keypad Change state of virtual inputs Clea...

Page 30: ...ponding system 2 Visual verification of active alarms relay display messages and LED indications 3 LED test 4 Visual inspection for any damage corrosion dust or loose wires 5 Event recorder file downl...

Page 31: ...stic features include an event recorder capable of storing 1024 time tagged events oscillography capable of storing up to 64 records with programmable trigger content and sampling rate and data logger...

Page 32: ...g Blocking 51G Ground Time Overcurrent 78 Out of Step Tripping 51N Neutral Time Overcurrent 79 Automatic Recloser Table 2 2 OTHER DEVICE FUNCTIONS FUNCTION FUNCTION FUNCTION Breaker arcing current I2...

Page 33: ...s The order code structure is dependent on the mounting option horizontal or vertical and the type of CT VT modules enhanced diagnostic CT VT modules or HardFiberTM process bus modules The order code...

Page 34: ...l inputs 6F 6F 6F 6F 6F 8 Fast Form C outputs 6G 6G 6G 6G 6G 4 Form A voltage with optional current outputs 8 digital inputs 6H 6H 6H 6H 6H 6 Form A voltage with optional current outputs 4 digital inp...

Page 35: ...urrent with optional voltage and 2 Form C outputs 8 digital inputs 6M 6M 6M 2 Form A current with optional voltage and 4 Form C outputs 4 digital inputs 6N 6N 6N 4 Form A current with optional voltage...

Page 36: ...A no monitoring outputs 4 digital inputs 6V 6V 2 Form A outputs 1 Form C output 2 Form A no monitoring latching outputs 8 digital inputs INTER RELAY COMMUNICATIONS select a maximum of 1 per unit 2A C3...

Page 37: ...no monitoring latching outputs 8 digital inputs INTER RELAY COMMUNICATIONS select a maximum of 1 per unit For the last module slot P is used for digital input output modules slot R is used for inter...

Page 38: ...puts 6B 2 Form A voltage with optional current and 4 Form C outputs 4 contact inputs 6C 8 Form C outputs 6D 16 contact inputs 6E 4 Form C outputs 8 contact inputs 6F 8 Fast Form C outputs 6G 4 Form A...

Page 39: ...puts 6N 4 Form A current with optional voltage outputs 8 contact inputs 6P 6 Form A current with optional voltage outputs 4 contact inputs 6R 2 Form A no monitoring and 2 Form C outputs 8 contact inpu...

Page 40: ...teps of 1 Comparator limit angle 30 to 90 in steps of 1 Directional supervision Characteristic angle 30 to 90 in steps of 1 Limit angle 30 to 90 in steps of 1 Right blinder Quad only Reach 0 02 to 500...

Page 41: ...tion 5 to 25 cycles in steps of 1 Voltage supervision pickup series compensation applications 0 to 5 000 pu in steps of 0 001 GROUND DISTANCE OPERATING TIME CURVES The operating times are response tim...

Page 42: ...elay 0 00 to 600 00 s in steps of 0 01 Operate time 20 ms at 3 pickup at 60 Hz Timer accuracy 3 of operate time or 1 4 cycle whichever is greater PHASE DIRECTIONAL OVERCURRENT Relay connection 90 quad...

Page 43: ...accuracy 3 of operate time or 1 4 cycle whichever is greater Operate time 30 ms at 1 10 pickup at 60 Hz NEGATIVE SEQUENCE OVERVOLTAGE Pickup level 0 000 to 1 250 pu in steps of 0 001 Dropout level 97...

Page 44: ...nts 80 1 through 20 of pickup Time delay 0 to 65535 ms in steps of 1 FLEX STATES Number up to 256 logical variables grouped under 16 Modbus addresses Programmability any logical variable contact or vi...

Page 45: ...ontact input change of state contact output change of state self test events Data storage in non volatile memory FAULT LOCATOR Method single ended Voltage source wye connected VTs delta connected VTs...

Page 46: ...ontinuous current draw 4 mA when energized Auto burnish impulse current 50 to 70 mA Duration of auto burnish impulse 25 to 50 ms DCMA INPUTS Current input mA DC 0 to 1 0 to 1 1 to 1 0 to 5 0 to 10 0 t...

Page 47: ...ANSI C37 90 Carry continuous 6 A as per IEEE C37 90 Break DC resistive as per IEC61810 1 Operate time 4 ms Contact material silver alloy Control separate operate and reset inputs Control mode operate...

Page 48: ...90 pu in steps of 0 001 2 2 8 COMMUNICATION PROTOCOLS RS232 Front port 19 2 kbps Modbus RTU RS485 1 rear port Up to 115 kbps Modbus RTU DNP 3 Typical distance 1200 m Isolation 2 kV isolated together...

Page 49: ...category II Ingress protection IP20 front IP10 back Noise 0 dB INTERFACE TYPE TYPICAL DISTANCE RS422 1200 m G 703 100 m EMITTER FIBER TYPE TRANSMIT POWER RECEIVED SENSITIVITY POWER BUDGET 820 nm LED M...

Page 50: ...pple DC IEC 60255 11 12 ripple 200 ms interrupts Radiated and conducted emissions CISPR11 CISPR22 IEC 60255 25 Class A Sinusoidal vibration IEC 60255 21 1 Class 1 Shock and bump IEC 60255 21 2 Class 1...

Page 51: ...has accumulated on the faceplate display a dry cloth can be used To avoid deterioration of electrolytic capacitors power up units that are stored in a de energized state once per year for one hour con...

Page 52: ...2 22 D30 Line Distance Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...

Page 53: ...o the removable modules and is itself removable to allow mounting on doors with limited rear depth The case dimensions are shown below along with panel cutout details for panel mounting When planning...

Page 54: ...ounting When planning the location of your panel cutout ensure that provision is made for the faceplate to swing open without interference to or from adjacent equipment The relay must be mounted such...

Page 55: ...58 243 4 mm 7 00 177 7 mm 4 00 101 6 mm 7 10 180 2 mm 13 66 347 0 mm 14 03 356 2 mm 0 20 5 1 mm 1 55 39 3 mm 4 Places 0 213 5 41 mm Front of Panel Mounting Bracket Vertical Enhanced Front View Vertica...

Page 56: ...UR Device Instruction Sheet GEK 113182 Connecting a Remote UR V Enhanced Front Panel to a Vertically Mounted Horizontal UR Device Instruction Sheet For side mounting D30 devices with the standard fro...

Page 57: ...GE Multilin D30 Line Distance Protection System 3 5 3 HARDWARE 3 1 DESCRIPTION 3 Figure 3 6 D30 VERTICAL SIDE MOUNTING INSTALLATION STANDARD PANEL...

Page 58: ...NG REAR DIMENSIONS STANDARD PANEL C U T O U T 1 33 33 9 2 83 71 9 6 66 169 2 12 20 309 9 0 159 DIA 6 PLACES 4 0 0 213 DIA 5 4 4 PLACES SEE HOLES MARKED X INCHES MILLIMETERS 5 33 135 4 PANEL SHOWN FOR...

Page 59: ...arrow marker on the terminal block See the following figure for an example of rear terminal assignments Figure 3 9 EXAMPLE OF MODULES IN F AND H SLOTS X W V U T S P N M L K J H D G F B R 8 4 7 3 6 2 5...

Page 60: ...ontact input H7a Contact input H7c Contact input H8a Contact input H8c Common H7b Surge H5 H6c H6a H6b H6 I V I V I V I V Fibre optic Ground at remote device Shielded twisted pairs Co axial cable COM...

Page 61: ...ies power for dry contact input connections The power supply module provides 48 V DC power for dry contact input connections and a critical failure relay see the Typical wiring diagram earlier The cri...

Page 62: ...ground current input that is the same as the phase current input Each AC current input has an isolating transformer and an automatic shorting mechanism that shorts the input when the module is withdra...

Page 63: ...functions FlexLogic metering and communications The IEC 61850 process bus system offers the following benefits Reduces labor associated with design installation and testing of protection and control...

Page 64: ...open and the DC current through the output contact when it is closed Each of the monitors contains a level detector whose out put is set to logic On 1 when the current in the circuit is above the thr...

Page 65: ...form A contact or the resistor can be used to monitor the state of the output Wherever a tilde symbol appears substitute with the slot position of the module wherever a number sign appears substitute...

Page 66: ...rm C 6a 6c 2 Inputs 7a 7c 2 Inputs 7a 7c 2 Inputs 7a 7c 2 Inputs 7a 7c 2 Inputs 8a 8c 2 Inputs 8a 8c 2 Inputs 8a 8c 2 Inputs 8a 8c 2 Inputs 6U MODULE 6V MODULE 67 MODULE 4A MODULE TERMINAL ASSIGNMENT...

Page 67: ...GE Multilin D30 Line Distance Protection System 3 15 3 HARDWARE 3 2 WIRING 3 Figure 3 15 CONTACT INPUT AND OUTPUT MODULE WIRING 1 of 2 842762A3 CDR...

Page 68: ...IN 8c COMMON 7b SURGE 8c 7c 8b I V I V I V I V DIGITAL I O 6N 1b 2b 3b 4b 6c 1a 2a 3a 4a 5a 6a 1c 2c 3c 4c 5c 5b 1 2 3 4 8a 7b 7a CONTACT IN 7a CONTACT IN 5a CONTACT IN 7c CONTACT IN 5c CONTACT IN 8a...

Page 69: ...each contact group The maximum external source voltage for this arrangement is 300 V DC The voltage threshold at which each group of four contact inputs detects a closed contact input is programmable...

Page 70: ...uto burnishing allow currents up to 50 to 70 mA at the first instance when the change of state was sensed Then within 25 to 50 ms this current is slowly reduced to 3 mA as indicated above The 50 to 70...

Page 71: ...ne Distance Protection System 3 19 3 HARDWARE 3 2 WIRING 3 The auto burnish circuitry has an internal fuse for safety purposes During regular maintenance check the auto burnish functionality using an...

Page 72: ...arranged as three ter minals per row with a total of eight rows A given row can be used for either inputs or outputs with terminals in column a having positive polarity and terminals in column c havin...

Page 73: ...1 RTD CONNECTIONS Three wire shielded cable RTD terminals Maximum total lead resistance 25 ohms for Platinum RTDs Route cable in separate conduit from current carrying conductors RTD 859736A1 CDR RTD...

Page 74: ...running the EnerVista UR Setup software provided with the relay Cabling for the RS232 port is shown in the following figure for both 9 pin and 25 pin connectors The baud rate for this port is fixed at...

Page 75: ...but insulated from the shield To avoid loop currents ground the shield at only one point If other system considerations require the shield to be grounded at more than one point install resistors typi...

Page 76: ...24 RS485 SERIAL CONNECTION c 100BASE FX FIBER OPTIC PORTS Ensure that the dust covers are installed when the fiber is not in use Dirty or scratched connectors can lead to high losses on a fiber link...

Page 77: ...ble for generating the IRIG B signal this equipment can use a GPS satellite system to obtain the time reference so that devices at different geographic locations can be syn chronized Figure 3 25 OPTIO...

Page 78: ...terconnection for dual channel type 7 communications modules is shown as follows Two channel modules allow for a redundant ring configuration That is two rings can be created to provide an additional...

Page 79: ...H IEEE C37 94 820 nm 128 kbps multi mode LED 2 channels 72 1550 nm single mode laser 1 channel 73 1550 nm single mode laser 2 channels 74 Channel 1 RS422 channel 2 1550 nm single mode laser 75 Channel...

Page 80: ...ws the configuration for the 72 73 7D and 7K fiber laser module Figure 3 30 LASER FIBER MODULES 7Q Channel 1 G 703 channel 2 1300 nm single mode laser 7R G 703 1 channel 7S G 703 2 channels 7T RS422 1...

Page 81: ...DWARE 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 Observing any fiber transmitter output can injure the eye When using a laser Interface attenuators can be necessary to ensure that you do not exceed the...

Page 82: ...INTERFACES Pin nomenclature can differ from one manufacturer to another Therefore it is not uncommon to see pinouts num bered TxA TxB RxA and RxB In such cases it can be assumed that A is equivalent...

Page 83: ...module internal timing mode and loop timing mode default Internal Timing Mode The system clock is generated internally Therefore the G 703 timing selection should be in the internal timing mode for ba...

Page 84: ...al loopback mode the multiplexers are active and the functions of the circuit are divided into two with each receiver transmitter pair linked together to deconstruct and then reconstruct their respect...

Page 85: ...clock input for the two RS422 channels The system functions correctly when the following connections are observed and your data module has a terminal timing feature Terminal timing is a common fea tu...

Page 86: ...Tx clock in the center of the Tx data bit Figure 3 39 CLOCK AND DATA TRANSITIONS d RECEIVE TIMING The RS422 interface utilizes NRZI MARK modulation code and therefore does not rely on an Rx clock to...

Page 87: ...imum optical input power to the receiver Figure 3 40 RS422 AND FIBER INTERFACE CONNECTION Connections shown above are for multiplexers configured as DCE data communications equipment units 3 3 7 G 703...

Page 88: ...0 40 nm Connection as per all fiber optic connections a Tx to Rx connection is required The UR series C37 94 communication module can be connected directly to any compliant digital multiplexer that su...

Page 89: ...the original location of the module to help ensure that the same or replacement module is inserted into the correct slot 2 Simultaneously pull the ejector inserter clips located at the top and at the...

Page 90: ...3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 Figure 3 42 IEEE C37 94 TIMING SELECTION SWITCH SETTING Cover screw Top cover Bottom cover Ejector inserter clip Ejector inserter clip Timing selectio...

Page 91: ...witch to internal timing mode while not receiving a valid data packet The link activity LED status is as follows Flashing green FPGA is receiving a valid data packet Solid yellow FPGA is receiving a y...

Page 92: ...patible with HP HFBR 1315T transmitter and HP HFBR 2316T receiver Fiber optic cable length up to 11 4 km Fiber optic connector type ST Wavelength 1300 40 nm Connection as per all fiber optic connectio...

Page 93: ...he original location of the module to help ensure that the same or replacement module is inserted into the correct slot 2 Simultaneously pull the ejector inserter clips located at the top and at the b...

Page 94: ...as follows Flashing green loop timing mode while receiving a valid data packet Cover screw Top cover Bottom cover Ejector inserter clip Ejector inserter clip Timing selection switches Channel 1 Channe...

Page 95: ...id data packet Solid red switch to internal timing mode while not receiving a valid data packet The link activity LED status is as follows Flashing green FPGA is receiving a valid data packet Solid ye...

Page 96: ...3 44 D30 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...

Page 97: ...uired See the EnerVista UR Setup Help File or refer to the Connecting EnerVista UR Setup with the D30 section in Chapter 1 for details 4 1 3 ENERVISTA UR SETUP OVERVIEW a ENGAGING A DEVICE The EnerVis...

Page 98: ...al display of power system and relay operation data captured during specific triggered events f FILE SUPPORT Execution Any EnerVista UR Setup file that is opened launches the application or provides f...

Page 99: ...new features are added or existing features are enhanced or modified The EEPROM DATA ERROR message displayed after upgrading downgrading the firmware is a resettable self test message intended to inf...

Page 100: ...4 4 D30 Line Distance Protection System GE Multilin 4 1 ENERVISTA UR SETUP SOFTWARE INTERFACE 4 HUMAN INTERFACES 4 Figure 4 1 ENERVISTA UR SETUP SOFTWARE MAIN WINDOW 1 2 3 4 5 6 7 8 9 842786A2 CDR 10...

Page 101: ...re describes how to enable the settings tem plate for UR series settings files 1 Select a settings file from the offline window of the EnerVista UR Setup main screen 2 Right click the selected device...

Page 102: ...ble by clicking them The setting available to view is displayed against a yellow background as shown below Figure 4 3 SETTINGS TEMPLATE VIEW TWO SETTINGS SPECIFIED AS EDITABLE 6 Click on Save to save...

Page 103: ...ly those settings available for editing Display all settings with settings not available for editing greyed out Use the following procedure to only display settings available for editing 1 Select an i...

Page 104: ...ecified by the template but all settings are shown The effect of applying the template to the phase time overcurrent settings is shown below Figure 4 6 APPLYING TEMPLATES VIA THE VIEW ALL SETTINGS COM...

Page 105: ...ENTRIES The following procedure describes how to lock individual entries of a FlexLogic equation 1 Right click the settings file or online device and select the Template Mode Create Template item to...

Page 106: ...elow and on the front panel display Figure 4 9 SECURED FLEXLOGIC IN GRAPHICAL VIEW b LOCKING FLEXLOGIC EQUATIONS TO A SERIAL NUMBER A settings file and associated FlexLogic equations can also be locke...

Page 107: ...is infor mation can be compared with the D30 actual values at any later date to determine if security has been compromised The traceability information is only included in the settings file if a compl...

Page 108: ...ay configuration since the settings file was saved a SETTINGS FILE TRACEABILITY INFORMATION The serial number and file transfer date are saved in the settings files when they are sent to a D30 device...

Page 109: ...EL INFORMATION SERIAL NUMBER ACTUAL VALUES PRODUCT INFO MODEL INFORMATION LAST SETTING CHANGE c ADDITIONAL TRACEABILITY RULES The following additional rules apply for the traceability feature If the u...

Page 110: ...the EnerVista UR Setup software The front panel interface consists of LED panels an RS232 port keypad LCD display control pushbuttons and optional user programmable pushbuttons The faceplate is hinged...

Page 111: ...reset via the SETTINGS INPUT OUTPUTS RESETTING menu The RS232 port is intended for connection to a portable PC The USER keys are used by the breaker control feature Figure 4 18 TYPICAL LED INDICATOR...

Page 112: ...cludes phase instantaneous overcurrent phase undervoltage etc This means that the phase A B and C operate oper ands for individual protection elements are ORed to turn on or off the phase A B or C LED...

Page 113: ...on when the operate operand associated with the element is asserted and remain on until the RESET button on the front panel is pressed after the operand is reset All elements that are able to discrimi...

Page 114: ...eight user setting groups revisions 3 0x and higher support six setting groups For convenience of users using earlier firmware revisions the relay panel shows eight setting groups Please note that th...

Page 115: ...ter and press the Print button in the front panel report window 5 When printing is complete fold the sheet along the perforated lines and punch out the labels 6 Remove the D30 label insert tool from t...

Page 116: ...upwards as shown below 2 Bend the tab at the center of the tool tail as shown below The following procedure describes how to remove the LED labels from the D30 enhanced front panel and insert the cus...

Page 117: ...own below This attaches the label tool to the LED label 3 Remove the tool and attached LED label as shown below 4 Slide the new LED label inside the pocket until the text is properly aligned with the...

Page 118: ...l of the label tool underneath as shown below Make sure the bent tab is pointing away from the relay 2 Slide the label tool under the user programmable pushbutton label until the tabs snap out as show...

Page 119: ...g mode These keys also scroll through alphanumeric values in the text edit mode Alternatively val ues can be entered with the numeric keypad The decimal key initiates and advances to the next characte...

Page 120: ...o breakers 4 3 7 MENUS a NAVIGATION Press the MENU key to select a header display page top level menu The header title appears momentarily followed by a header display page menu item Each press of the...

Page 121: ...t Actual Values page appears This page contains system and relay status information Repeatedly press the MESSAGE keys to display the other actual value headers SETTINGS PRODUCT SETUP Press the MENU ke...

Page 122: ...e the VALUE DOWN key displays the previous selection c ENTERING ALPHANUMERIC TEXT Text settings have data values which are fixed in length but user defined in character They can be upper case letters...

Page 123: ...RODUCT SETUP message appears on the display 2 Press the MESSAGE RIGHT key until the SECURITY message appears on the display 3 Press the MESSAGE DOWN key until the INSTALLATION message appears on the d...

Page 124: ...s you to ENTER NEW PASSWORD 7 Type in a numerical password up to 10 characters and press the ENTER key 8 When the VERIFY NEW PASSWORD is displayed re type in the same password and press ENTER 9 When t...

Page 125: ...es within three minutes the REMOTE ACCESS DENIED FlexLogic operand is set to On and the D30 does not allow settings or command access via the any external communications interface for five minutes The...

Page 126: ...4 30 D30 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...

Page 127: ...See page 5 47 FAULT REPORTS See page 5 52 OSCILLOGRAPHY See page 5 54 USER PROGRAMMABLE LEDS See page 5 56 USER PROGRAMMABLE SELF TESTS See page 5 59 CONTROL PUSHBUTTONS See page 5 60 USER PROGRAMMABL...

Page 128: ...5 121 SETTINGS GROUPED ELEMENTS SETTING GROUP 1 See page 5 122 SETTING GROUP 2 SETTING GROUP 6 SETTINGS CONTROL ELEMENTS TRIP BUS See page 5 186 SETTING GROUPS See page 5 188 SELECTOR SWITCH See page...

Page 129: ...page 5 230 RESETTING See page 5 230 DIRECT INPUTS See page 5 231 DIRECT OUTPUTS See page 5 231 TELEPROTECTION See page 5 234 IEC 61850 GOOSE ANALOGS See page 5 236 IEC 61850 GOOSE UINTEGERS See page...

Page 130: ...the primary cur rent base to convert to from a primary current value Where the current source is the sum of two or more CTs with different nominal primary current the primary base quantity is the lar...

Page 131: ...Element OP operate The DPO event is created when the measure and decide comparator output transits from the pickup state logic 1 to the dropout state logic 0 This could happen when the element is in...

Page 132: ...For example in the scheme shown in the above diagram the user configures one source to be the sum of CT1 and CT2 and can name this source as Wdg1 I Once the sources have been configured the user has...

Page 133: ...uired by the user to know how to connect the relay to external circuits Bank identification consists of the letter designation of the slot in which the CT VT module is mounted as the first character f...

Page 134: ...learing the data logger Clearing the user programmable pushbutton states The following operations are under setting password supervision Changing any setting Test mode operation The command and settin...

Page 135: ...all the remote and local security operands shown above Changing the password or any other setting does not take the relay out of service The relay is taken out of service when a settings file is writt...

Page 136: ...P SECURITY ACCESS SUPERVISION The following access supervision settings are available INVALID ATTEMPTS BEFORE LOCKOUT This setting specifies the number of times an incorrect password can be entered wi...

Page 137: ...ns as normal that is a local setting password is required If this setting is any contact input on FlexLogic operand then the operand must be asserted set as on prior to providing the local setting pas...

Page 138: ...ccess is permitted and the timer programmed with the Access Authorized Timeout setting value is started When this timer expires remote setting access is immediately denied If access is permitted and a...

Page 139: ...to set up a simple RADIUS server where the third party tool used is an example a Download and install FreeRADIUS from www freeradius net as the RADIUS server This is a Windows 32 bit instal lation tha...

Page 140: ...elay automatically provides the authentication from the device 4 In the EnerVista software choose server authentication and log in using the user name and password configured on the RADIUS server for...

Page 141: ...changes after the fact Only Supervisor can set the Settings and Firmware Lock in the Security Settings This role also has the ability to forcefully logoff any other role and clear the security event...

Page 142: ...ting specifies the period of time in minutes of a lockout period the default is three and the maximum is 9999 A value of 0 means that there is no lockout period e RESTORE DEFAULTS PATH SETTINGS PRODUC...

Page 143: ...Based Access Control RBAC Lock Relay This setting uses a Boolean value Enable Disable to indicate if the device accepts setting changes and whether the device can receive a firmware upgrade This setti...

Page 144: ...TS PATH SETTINGS PRODUCT SETUP SECURITY SUPERVISORY SELF TESTS Failed Authentications If this setting is Enabled then the number of failed authentications is compared with the Session lockout threshol...

Page 145: ...1 Authentication Failed 2 User Lockout 3 FW Upgrade 4 FW Lock 5 Settings Lock 6 Settings Change Because this can fill the entire event log it is supported by the already existing Settings_Change log...

Page 146: ...prefer these low voltages to be displayed as zero while others prefer the voltage to be displayed even when the value reflects noise rather than the actual sig nal The D30 applies a cut off value to...

Page 147: ...uired For example to assign user programmable pushbutton 1 to clear demand records the following settings should be applied 1 Assign the clear demand function to pushbutton 1 by making the following c...

Page 148: ...r some time after each transmission c ETHERNET NETWORK TOPOLOGY The three independent UR ports do not have routing capability and work only on local subnets for the switched network topology End nodes...

Page 149: ...2 255 0 0 0 where LAN3 is 12 x x x 255 0 0 0 Example 3 Incorrect IP1 Mask1 10 1 1 2 255 0 0 0 IP2 Mask2 10 2 1 2 255 0 0 0 IP3 Mask3 10 3 1 2 255 0 0 0 This example is incorrect because the mask of 2...

Page 150: ...3 uses the IP and MAC address of P2 Figure 5 4 MULTIPLE LANS WITH REDUNDANCY Multiple LANS No Redundancy The following topology provides local configuration monitoring through EnerVista software on LA...

Page 151: ...ed only in advanced network configura tions and should normally be left at their default values but may be changed if required for example to allow access to multiple UR series relays behind a router...

Page 152: ...on This allows the EnerVista UR Setup software to be used on the port The UR operates as a Modbus slave device only When using Modbus protocol on the RS232 port the D30 responds regardless of the MODB...

Page 153: ...100000 MESSAGE DNP VOLTAGE SCALE FACTOR 1 Range 0 001 0 01 0 1 1 10 100 1000 10000 100000 MESSAGE DNP POWER SCALE FACTOR 1 Range 0 001 0 01 0 1 1 10 100 1000 10000 100000 MESSAGE DNP ENERGY SCALE FACT...

Page 154: ...ver UDP IP on channel 1 only Refer to Appendix E for additional information on the DNP protocol Changes to the DNP CHANNEL 1 PORT and DNP CHANNEL 2 PORT settings take effect only after power has been...

Page 155: ...LT DEADBAND settings determine when to trigger unsolicited responses containing analog input data These settings group the D30 analog input data into the following types current voltage power energy p...

Page 156: ...ion of dead network TCP connections If there is no data traffic on a DNP TCP connection for greater than the time specified by this setting the connection will be aborted by the D30 This frees up the...

Page 157: ...not take effect until the D30 is restarted i IEC 61850 PROTOCOL PATH SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL The D30 Line Distance Protection System is provided with optional IEC 6185...

Page 158: ...TIONS IEC 61850 PROTOCOL GSSE GOOSE CONFIGURATION TRANSMISSION The general transmission settings are shown below PATH SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE GOOSE CONFIGURATION...

Page 159: ...C address to be set This address must be a multicast address the least significant bit of the first byte must be set In D30 releases previous to 5 0x the destination Ethernet MAC address was determine...

Page 160: ...sets 1 through 8 the integrity GOOSE message will still continue to be sent at the pre configured rate even if no changes in the data items are detected The GOOSE functionality was enhanced to prevent...

Page 161: ...n required to transfer IEC 61850 data items between two devices The general steps required for transmission configuration are 1 Configure the transmission dataset 2 Configure the GOOSE service setting...

Page 162: ...d must match the configuration on the receiver the default value is 0 Set the CONFIG GSE 1 CONFREV value This value changes automatically as described in IEC 61850 part 7 2 For this example it can be...

Page 163: ...ned by the GGIO1 ST Ind1 stVal value in the sending device The above settings will be automatically populated by the EnerVista UR Setup software when a com plete SCD file is created by third party sub...

Page 164: ...se two data items The Boolean status values from these data items can be utilized as remote input FlexLogic operands First the REMOTE DEVICE 1 16 DATASET setting must be set to contain dataset GOOSEIn...

Page 165: ...s restarted Do not set more than one protocol to the same TCP UDP port number as this results in unreliable operation of those protocols The SERVER SCANNING feature should be set to Disabled when IEC...

Page 166: ...and values used to determine when the update the MMXU mag and cVal values from the associated instmag and instcVal values The mag and cVal values are used for the IEC 61850 buffered and unbuffered rep...

Page 167: ...to control the D30 virtual inputs The GGIO4 analog configuration points are shown below PATH SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GGIO4 ANALOG CONFIGURATION The NUMBER OF ANALOG P...

Page 168: ...not all values can be stored Some values may be rounded to the closest possible floating point number The GGIO5 integer configuration points are shown below PATH SETTINGS PRODUCT SETUP COMMUNICATIONS...

Page 169: ...effect until the UR is restarted PATH SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL XCBR CONFIGURATION The CLEAR XCBR1 OpCnt setting represents the breaker operating counter As breakers op...

Page 170: ...ins an embedded web server and is capable of transferring web pages to a web browser such as Internet Explorer or Firefox The web pages are organized as a series of menus that can be accessed starting...

Page 171: ...r station Since the D30 maintains two sets of IEC 60870 5 104 data change buffers no more than two masters should actively communicate with the D30 at one time TFTP PROTOCOL TFTP MAIN UDP PORT NUMBER...

Page 172: ...this results in unreliable operation of those protocols The D30 relay does not support energy metering As such the IEC ENERGY DEFAULT THRESHOLD setting is not appli cable The IEC 60870 5 104 and DNP...

Page 173: ...the avail able external time sources synchronizes the RTC and the synchrophasor clock A setting of None causes the RTC and the synchrophasor clock to free run A setting of PP IRIGB PTP SNTP IRIGB PP P...

Page 174: ...ol automation and data communication applications and thereby facilitates interoperabil ity between different vendor s clocks and switches PP specifies a worst case delivered time error of less than 1...

Page 175: ...PP the default VLAN priority is 4 but it is recommended that in accordance with PTP it be set to 7 Depending on the characteristics of the device to which the relay is directly linked VLAN Priority ma...

Page 176: ...eive time values from an SNTP NTP server usually a ded icated product using a GPS receiver to provide an accurate time UR series relays support unicast broadcast multicast and anycast SNTP functionali...

Page 177: ...C is synchronized with a communications protocol providing only UTC such as PTP or SNTP the time offset setting is used to determine local time from the UTC provided PTP ALTERNATE_TIME_OFFSET_INDICATO...

Page 178: ...seconds waiting for the fault report trigger If trigger does not occur within this time the values are cleared to prepare for the next disturbance Fault current and voltage phasors one cycle after the...

Page 179: ...RT 1 SOURCE setting selects the source for input currents and voltages and disturbance detection The FAULT 1 REPORT TRIG setting assigns the FlexLogic operand representing the protection element eleme...

Page 180: ...etc A trigger position of 25 consists of 25 pre and 75 post trigger data The TRIGGER SOURCE is always captured in oscillography and may be any FlexLogic parameter element state contact input virtual o...

Page 181: ...used to expedite the selection of the parameter on the relay display It can be quite time consuming to scan through the list of parameters via the relay keypad and display entering this number via th...

Page 182: ...s are turned on One LED at a time turns off for 1 second then back on The test routine starts at the top left panel moving from top to bottom of each column of the LEDs This test checks for hardware f...

Page 183: ...start stage 2 At this point forward test may be aborted by pressing the pushbutton APPLICATION EXAMPLE 2 Assume one needs to check if any LEDs are burned as well as exercise one LED at a time to chec...

Page 184: ...ogrammable LED settings select the FlexLogic operands that control the LEDs If the LED 1 TYPE setting is Self Reset the default setting the LED illumination will track the state of the selected LED op...

Page 185: ...arms continue to function along with other major and minor alarms Refer to the Relay self tests section in chapter 7 for additional information on major and minor self test alarms USER PROGRAMMABLE SE...

Page 186: ...ons and are not protected by the control password However by supervising their output operands the user can dynamically enable or disable control pushbuttons for security reasons Each control pushbutt...

Page 187: ...ol breaker control typically uses the larger optional user programmable pushbuttons making the control pushbuttons available for other user applications Figure 5 9 CONTROL PUSHBUTTON LOGIC 842010A2 CD...

Page 188: ...The user programmable pushbuttons are under the control level of password protection The user configurable pushbuttons for the enhanced faceplate are shown below USER PUSHBUTTON 1 PUSHBUTTON 1 FUNCTIO...

Page 189: ...tton The pushbutton maintains the set state until deactivated by the reset command or after a user specified time delay The state of each pushbutton is stored in non volatile memory and maintained thr...

Page 190: ...state of the corresponding FlexLogic operand between On and Off on each button press or by virtually activating the pushbutton assigning set and reset operands When in the Latched mode the states of t...

Page 191: ...undisturbed as long as PUSHBUTTON 1 ON operand is asserted The high priority option is not applicable to the PUSHBTN 1 OFF TEXT setting This message can be temporary removed if any front panel keypad...

Page 192: ...Lock SETTING Off 0 Local Lock SETTING Off 0 Set SETTING Off 0 Reset SETTING Enabled Disabled Autoreset Function FLEXLOGIC OPERAND PUSHBUTTON 1 ON FLEXLOGIC OPERAND PUSHBUTTON 1 OFF TIMER 200 ms 0 AND...

Page 193: ...NG any FlexLogic operand PUSHBTN 1 LED CTL AND SETTING Flash Message Time TRST 0 PUSHBUTTON ON LATCHED LATCHED SELF RESET AND From user programmable pushbuttons logic sheet 1 842021A3 FLEXLOGIC OPERAN...

Page 194: ...and ACTUAL VALUES top level menus The sub menus facili tate text entry and Modbus register data pointer options for defining the user display content Once programmed the user definable displays can b...

Page 195: ...e character is used to mark the start of a data field the length of the data field needs to be accounted for Up to five separate data fields can be entered in a user display the nth tilde refers to th...

Page 196: ...and bottom line items are different USER DISPLAY 1 DISP 1 TOP LINE Current X A Shows user defined text with first tilde marker MESSAGE DISP 1 BOTTOM LINE Current Y A Shows user defined text with secon...

Page 197: ...d and signaled by the following FlexLogic operands 1 DIRECT RING BREAK direct input output ring break This FlexLogic operand indicates that direct output messages sent from a UR series relay are not b...

Page 198: ...nication channels The following application examples illustrate the basic concepts for direct input and output configuration Please refer to the Inputs and outputs section in this chapter for informat...

Page 199: ...D 1 DIRECT I O CH1 RING CONFIGURATION Yes DIRECT I O DATA RATE 128 kbps For UR series IED 2 DIRECT OUTPUT DEVICE ID 2 DIRECT I O CH1 RING CONFIGURATION Yes DIRECT I O DATA RATE 128 kbps The message de...

Page 200: ...oth rings are healthy IED 1 to IED 2 0 2 of power system cycle IED 1 to IED 3 0 4 of power system cycle IED 1 to IED 4 0 2 of power system cycle IED 2 to IED 3 0 2 of power system cycle IED 2 to IED 4...

Page 201: ...UTPUT DEVICE ID 2 DIRECT I O CH1 RING CONFIGURATION Yes DIRECT I O CH2 RING CONFIGURATION Yes For UR series IED 3 DIRECT OUTPUT DEVICE ID 3 DIRECT I O CH1 RING CONFIGURATION Yes DIRECT I O CH2 RING CO...

Page 202: ...M CH1 2 PATH SETTINGS PRODUCT SETUP DIRECT I O CRC ALARM CH1 2 The D30 checks integrity of the incoming direct input and output messages using a 32 bit CRC The CRC alarm function is available for moni...

Page 203: ...ssuming the best case of only 1 bit error in a failed packet having 1 failed packet for every 63 received is about equal to a BER of 10 4 c UNRETURNED MESSAGES ALARM CH1 2 PATH SETTINGS PRODUCT SETUP...

Page 204: ...OF TERMINALS is 3 three terminal system set the NUMBER OF CHANNELS to 2 For a two terminal system the NUMBER OF CHANNELS can set to 1 or 2 redundant channels LOCAL RELAY ID NUMBER TERMINAL 1 RELAY ID...

Page 205: ...elay until RELAY SETTINGS is set to Programmed This setting is defaulted to Not Programmed when at the factory The UNIT NOT PROGRAMMED self test error message is displayed until the relay is put into...

Page 206: ...d consists of the following steps Configure the field units This establishes the point to point connection between a specific port on the relay process bus module and a specific digital core on a spec...

Page 207: ...vel ground fault currents the sensitive ground input may be used In this case the sensitive ground CT primary rating must be entered Refer to chapter 3 for more details on CT connections Enter the rat...

Page 208: ...NOMINAL FREQUENCY value is used as a default to set the digital sampling rate if the system frequency cannot be measured from available signals This may happen if the signals are not present or are he...

Page 209: ...L SOURCES PATH SETTINGS SYSTEM SETUP SIGNAL SOURCES SOURCE 1 2 Identical menus are available for each source The SRC 1 text can be replaced by with a user defined name appropriate for the associated s...

Page 210: ...port It can also be used to supervise current based elements to prevent maloperation as a result of the wrong settings or external CT wiring problem A disturbance detector is provided for each source...

Page 211: ...t of sources used to provide the functions required in this application and the CT VT inputs that are used to provide the data Figure 5 22 EXAMPLE USE OF SOURCES Y LV D HV AUX SRC 1 SRC 2 SRC 3 Phase...

Page 212: ...LOSE Off Range FlexLogic operand MESSAGE BREAKER 1 A 3P CLSD Off Range FlexLogic operand MESSAGE BREAKER 1 A 3P OPND Off Range FlexLogic operand MESSAGE BREAKER 1 B CLOSED Off Range FlexLogic operand...

Page 213: ...er and used to track the breaker open or closed position If the mode is selected as 1 Pole the input mentioned above is used to track phase A and the BREAKER 1 B and BREAKER 1 C settings select operan...

Page 214: ...sabled BREAKER 1 FUNCTION SETTING Off 0 BREAKER 1 BLOCK OPEN FLEXLOGIC OPERANDS TRIP PHASE A TRIP PHASE B TRIP PHASE C TRIP 3 POLE SETTING Off 0 BREAKER 1 OPEN SETTING Enabled BREAKER 1 PUSHBUTTON CON...

Page 215: ...REAKER 1 FA OPEN BREAKER 1 INTERM FA FLEXLOGIC OPERANDS BREAKER 1 ANY P OPEN BREAKER 1 1P OPEN BREAKER 1 OOS SETTING 3 Pole 1 Pole BREAKER 1 MODE SETTING Off BREAKER 1 EXT ALARM SETTING Off BREAKER 1...

Page 216: ...ed to disconnect switch 1 SWITCH 1 MODE This setting selects 3 Pole mode where disconnect switch poles have a single common auxiliary switch or 1 Pole mode where each disconnect switch pole has its ow...

Page 217: ...put to create a logic 1 when the disconnect switch is open If a separate 89 b contact input is not available then an inverted 89 a status signal can be used SWITCH 1 B CLOSED If the mode is selected a...

Page 218: ...H 1 TROUBLE FLEXLOGIC OPERAND SWITCH 1 BAD STATUS FLEXLOGIC OPERANDS SWITCH FA BAD ST 1 SWITCH FA CLSD 1 SWITCH FA OPEN 1 SWITCH FA 1 INTERM SETTING 3 Pole 1 Pole SWITCH 1 MODE AND OR OR SETTING SWITC...

Page 219: ...iple of pickup of 1 that is 0 98 pu and 1 03 pu It is recommended to set the two times to a similar value otherwise the linear approximation may result in undesired behavior for the operating quantity...

Page 220: ...y at higher currents and where upstream and downstream pro tective devices have different operating characteristics The recloser curve configuration window shown below appears when the Initialize From...

Page 221: ...ms see below Figure 5 27 COMPOSITE RECLOSER CURVE WITH HCT DISABLED With the HCT feature enabled the operating time reduces to 30 ms for pickup multiples exceeding 8 times pickup Figure 5 28 COMPOSIT...

Page 222: ...SER CURVES GE113 GE120 GE138 AND GE142 GE104 1 1 2 1 5 2 2 5 3 4 5 6 7 8 9 10 12 15 20 0 01 0 02 0 05 0 1 0 2 0 5 1 2 CURRENT multiple of pickup TIME sec GE101 GE102 GE103 GE106 GE105 842723A1 CDR 1 1...

Page 223: ...AND GE201 Figure 5 32 RECLOSER CURVES GE131 GE141 GE152 AND GE200 1 1 2 1 5 2 2 5 3 4 5 6 7 8 9 10 12 15 20 0 5 1 2 5 10 20 50 CURRENT multiple of pickup TIME sec GE134 GE151 GE140 GE137 GE201 842730...

Page 224: ...S GE116 GE117 GE118 GE132 GE136 AND GE139 842729A1 CDR 1 1 2 1 5 2 2 5 3 4 5 6 7 8 9 10 12 15 20 0 01 0 02 0 05 0 1 0 2 0 5 1 2 5 10 20 50 CURRENT multiple of pickup TIME sec GE133 GE163 GE162 GE161 G...

Page 225: ...2 Figure 5 36 RECLOSER CURVES GE119 GE135 AND GE202 842724A1 CDR 1 1 2 1 5 2 2 5 3 4 5 6 7 8 9 10 12 15 20 0 01 0 02 0 05 0 1 0 2 0 5 1 2 5 10 20 CURRENT multiple of pickup TIME sec GE121 GE114 GE112...

Page 226: ...applies to the other features that set flags elements virtual inputs remote inputs schemes and human operators If more complex logic than presented above is required it is implemented via FlexLogic Fo...

Page 227: ...1 ON IF Contact Input On Cont Ip On Voltage is presently applied to the input external contact closed Off Cont Ip Off Voltage is presently not applied to the input external contact open Contact Outpu...

Page 228: ...messages on channel 1 exceeded the user specified level ring configurations only The rate of returned direct input output messages on channel 2 exceeded the user specified level ring configurations on...

Page 229: ...or 1 element picks up BROKEN CONDUCT 2 Same set of operands as shown for BROKEN CONDUCTOR 1 ELEMENT Digital counters Counter 1 HI Counter 1 EQL Counter 1 LO Digital counter 1 output is more than compa...

Page 230: ...urrent 1 has dropped out NEG SEQ IOC2 Same set of operands as shown for NEG SEQ IOC1 ELEMENT Negative sequence overvoltage NEG SEQ OV1 PKP NEG SEQ OV1 DPO NEG SEQ OV1 OP Negative sequence overvoltage...

Page 231: ...B PHASE OV1 OP C PHASE OV1 DPO A PHASE OV1 DPO B PHASE OV1 DPO C At least one phase of overvoltage 1 has picked up At least one phase of overvoltage 1 has operated All phases of overvoltage 1 have dro...

Page 232: ...tive Setting group 4 is active Setting group 5 is active Setting group 6 is active ELEMENT Disturbance detector SRC1 50DD OP SRC2 50DD OP Source 1 disturbance detector has operated Source 2 disturbanc...

Page 233: ...erload protection 1 operated THERMAL PROT 2 Same set of operands as shown for THERMAL PROT 1 ELEMENT Trip bus TRIP BUS 1 PKP TRIP BUS 1 OP Asserted when the trip bus 1 element picks up Asserted when t...

Page 234: ...is on LED INDICATORS LED test LED TEST IN PROGRESS An LED test has been initiated and has not finished LED INDICATORS User programmable LEDs LED USER 1 Asserted when user programmable LED 1 is on LED...

Page 235: ...d but not connected The Direct I O settings is for a connection that is not in a ring The configuration of modules does not match the stored order code A FlexLogic equation is incorrect A difference i...

Page 236: ...an equation list End END The first END encountered signifies the last entry in the list of processed FlexLogic parameters One shot POSITIVE ONE SHOT One shot that responds to a positive going edge A...

Page 237: ...16 17 through 25 to AND 9 and the outputs from these two gates to AND 2 Inspect each operator between the initial operands and final virtual outputs to determine if the output from the operator is use...

Page 238: ...er to start at the out put end of the equation and work back towards the input as shown in the following steps It is also recommended to list operator inputs from bottom to top For demonstration the f...

Page 239: ...e set of parame ters into a logic diagram The result of this process is shown below which is compared to the logic for virtual output 3 dia gram as a check Figure 5 43 FLEXLOGIC EQUATION FOR VIRTUAL O...

Page 240: ...cases where a lot of processing is required to perform logic this may be difficult to achieve but in most cases will not cause problems as all logic is calculated at least four times per power frequen...

Page 241: ...OGIC EQUATION EDITOR PATH SETTINGS FLEXLOGIC FLEXLOGIC EQUATION EDITOR There are 512 FlexLogic entries available numbered from 1 to 512 with default END entry settings If a Disabled Element is selecte...

Page 242: ...FLEXELEMENT 1 FLEXELEMENT 1 FUNCTION Disabled Range Disabled Enabled MESSAGE FLEXELEMENT 1 NAME FxE1 Range up to 6 alphanumeric characters MESSAGE FLEXELEMENT 1 IN Off Range Off any analog actual valu...

Page 243: ...le applications for the Absolute setting include monitoring the angular difference between two phasors with a symmetrical limit angle in both directions monitoring power regardless of its direction or...

Page 244: ...ction with the FLEXELEMENT 1 INPUT MODE setting the element could be programmed to provide two extra charac teristics as shown in the figure below FlexElement 1 OpSig FLEXELEMENT 1 PKP FLEXELEMENT DIR...

Page 245: ...measured by the relay The FLEXELEMENT 1 PICKUP setting is entered in per unit values using the following definitions of the base units Table 5 10 FLEXELEMENT BASE UNITS BREAKER ARCING AMPS Brk X Arc A...

Page 246: ...ting specifies duration of the time interval for the rate of change mode of operation This setting is applicable only if FLEXELEMENT 1 COMP MODE is set to Delta This FLEXELEMENT 1 PKP DELAY setting sp...

Page 247: ...rted the specified FlexLogic operand resets Latch 1 Figure 5 48 NON VOLATILE LATCH OPERATION TABLE N 1 to 16 AND LOGIC LATCH 1 LATCH 1 FUNCTION Disabled Range Disabled Enabled MESSAGE LATCH 1 TYPE Res...

Page 248: ...TTING GROUPS menu see the Control elements section later in this chapter See also the Introduction to elements section at the beginning of this chap ter 5 6 2 SETTING GROUP PATH SETTINGS GROUPED ELEME...

Page 249: ...the line is being re energized from the local ter minal pickup of an overreaching zone 2 or excessive phase current within eight power cycles after the autorecloser issues a close command results in t...

Page 250: ...en reclosing This philosophy can be programmed via the autore close scheme Figure 5 49 LINE PICKUP SCHEME LOGIC 5 DQG RQO 2 OLQH HQG RSHQ 25 1 1 1 1 1 25 25 25 1 25 F FOHV SX SX SX 1 25 1 1 1 25 PV 1...

Page 251: ...that the nominal secondary voltage of the VT is entered correctly under the SETTINGS SYSTEM SETUP AC INPUTS VOLTAGE BANK menu Set MEMORY DURATION long enough to ensure stability on close in reverse th...

Page 252: ...l philoso phy of distance memory polarization The memory polarization cannot be applied permanently but for a limited time only the self polarization may be applied permanently and therefore should ta...

Page 253: ...S SETTING GROUP 1 6 DISTANCE The common distance settings described earlier must be properly chosen for correct operation of the phase distance ele ments Additional details are in chapter 8 Theory of...

Page 254: ...nce defined by the PHS DIST Z1 REACH and PHS DIST Z1 RCA settings and the reverse reach imped ance defined by PHS DIST Z1 REV REACH and PHS DIST Z1 REV REACH RCA as illustrated below PHS DIST Z1 SHAPE...

Page 255: ...ISTIC Figure 5 54 NON DIRECTIONAL QUADRILATERAL PHASE DISTANCE CHARACTERISTIC 837721A1 CDR X R RE AC H RCA DIR RCA DIR COMP LIMIT DIR COMP LIMIT COMP LIMIT COMP LIMIT RGT BLD RCA LFT BLD RCA RGT BLD L...

Page 256: ...IT 60o X R R E A C H RCA 80o COMP LIMIT 60o DIR RCA 80o DIR COMP LIMIT 60o X R REACH RCA 90o COMP LIMIT 90o DIR RCA 45o DIR COMP LIMIT 90o 837723A1 CDR X R R E A C H RCA 80o COMP LIMIT 90o DIR RCA 80o...

Page 257: ...the Z3 setting shall be set to None See the Theory of operation chapter for more details and the Application of settings chapter for information on calcu lating distance reach settings in applications...

Page 258: ...xis of the impedance plane see the Quadrilateral distance characteristic figures The angular position of the blinder is adjustable with the use of the PHS DIST Z1 QUAD RGT BLD RCA setting This setting...

Page 259: ...her or migrates from the initial zone to zone 2 Desired zones in the trip output function should be assigned to accomplish this functionality D60 L60 and L90 only Other UR series models apply regular...

Page 260: ...D PHS DIST Z1 QUAD LFT BLD RCA PHS DIST Z1 RCA PHS DIST Z1 XFMR VOL CONNECTION PHS DIST Z1 XFMR CUR CONNECTION PHS DIST Z1 DIR PHS DIST Z1 COMP LIMIT PHS DIST Z1 SHAPE RUN RUN RUN RUN RUN RUN A B ELEM...

Page 261: ...01 MESSAGE GND DIST Z1 RCA 85 Range 30 to 90 in steps of 1 MESSAGE GND DIST Z1 REV REACH 2 00 Range 0 02 to 500 00 ohms in steps of 0 01 MESSAGE GND DIST Z1 REV REACH RCA 85 Range 30 to 90 in steps of...

Page 262: ...nd elements for all zones as entered under the SETTINGS GROUPED ELEMENTS SETTING GROUP 1 6 DISTANCE menu 2 The MEMORY DURATION setting common for both phase and ground elements for all zones as entere...

Page 263: ...D DIST Z1 ZOM Z1 MAG The ground distance elements can be programmed to apply compensation for the zero sequence mutual coupling between parallel lines If this compensation is required the ground curre...

Page 264: ...verse GND DIST Z1 REV REACH RCA This setting defines the angle of the reverse reach impedance if the zone is set to non directional GND DIST Z1 DIR setting This setting does not apply when the zone di...

Page 265: ...ound distance security against spuri ous neutral current during switch off transients three phase faults and phase to phase faults a positive sequence current restraint of 5 is applied to the neutral...

Page 266: ...ents at low signal levels Otherwise the reverse fault condition that generates concern will have high polarizing levels so that a cor rect reverse fault decision can be reliably made Figure 5 66 GROUN...

Page 267: ...A 75 Range 40 to 90 in steps of 1 MESSAGE POWER SWING REV REACH 50 00 Range 0 10 to 500 00 ohms in steps of 0 01 MESSAGE POWER SWING QUAD REV REACH MID 60 00 Range 0 10 to 500 00 ohms in steps of 0 01...

Page 268: ...to develop an under standing of the operation of the element The power swing detect element operates in three step or two step mode Three step operation The power swing blocking sequence essentially t...

Page 269: ...P operand is set immediately and sealed in for the interval set by the POWER SWING SEAL IN DELAY If the Delayed trip mode is selected the element waits until the impedance locus leaves the inner chara...

Page 270: ...SWING INNER POWER SWING TMR2 PKP POWER SWING TMR3 PKP and POWER SWING TMR4 PKP FlexLogic operands are auxiliary operands that could be used to facilitate testing and special applications The POWER SWI...

Page 271: ...ith settings of the power swing timers The two step mode uses only the outer and inner characteristics for both blocking and tripping functions This leaves more space in heavily loaded systems to plac...

Page 272: ...aracteristics Set this value high if no blinder is required for the Mho characteristic POWER SWING PICKUP DELAY 1 All the coordinating timers are related to each other and should be set to detect the...

Page 273: ...the element is enabled The blocking signal resets the output POWER SWING TRIP operand but does not stop the out of step tripping sequence Figure 5 70 POWER SWING DETECT SCHEME LOGIC 1 of 3 Figure 5 71...

Page 274: ...SETTING POWER SWING SEAL IN DELAY POWER SWING DELAY 1 RESET POWER SWING DELAY 1 PICKUP POWER SWING DELAY 2 PICKUP POWER SWING DELAY 3 PICKUP POWER SWING DELAY 4 PICKUP POWER SWING BLK Off 0 POWER SWI...

Page 275: ...quadrilateral distance element LOAD ENCROACHMENT LOAD ENCROACHMENT FUNCTION Disabled Range Disabled Enabled MESSAGE LOAD ENCROACHMENT SOURCE SRC 1 Range SRC 1 SRC 2 MESSAGE LOAD ENCROACHMENT MIN VOLT...

Page 276: ...lement as shown in the Load encroachment characteristic diagram This setting should be entered in secondary ohms and be calculated as the pos itive sequence resistance seen by the relay under maximum...

Page 277: ...that the energy capacity has reached 100 a time overcurrent element will operate If less than 100 energy capac ity is accumulated in this variable and the current falls below the dropout threshold of...

Page 278: ...845 2 439 8 0 181 454 76 174 29 174 16 014 10 374 7 419 5 674 4 555 3 794 3 252 10 0 226 817 95 217 36 467 20 017 12 967 9 274 7 092 5 693 4 742 4 065 IEEE VERY INVERSE 0 5 8 090 3 514 1 471 0 899 0...

Page 279: ...4 280 3 837 3 528 3 297 3 116 2 971 IEC CURVE B 0 05 1 350 0 675 0 338 0 225 0 169 0 135 0 113 0 096 0 084 0 075 0 10 2 700 1 350 0 675 0 450 0 338 0 270 0 225 0 193 0 169 0 150 0 20 5 400 2 700 1 35...

Page 280: ...488 1 239 1 060 0 926 IAC VERY INVERSE 0 5 1 451 0 656 0 269 0 172 0 133 0 113 0 101 0 093 0 087 0 083 1 0 2 901 1 312 0 537 0 343 0 266 0 227 0 202 0 186 0 174 0 165 2 0 5 802 2 624 1 075 0 687 0 53...

Page 281: ...m instanta neous to 600 00 seconds in steps of 10 ms EQ 5 13 EQ 5 14 where T Operate Time sec TDM Multiplier setting I Input Current Ipickup Pickup Current setting TRESET Reset Time in seconds assumin...

Page 282: ...namically reduced by a voltage restraint feature when enabled This is accom plished via the multipliers Mvr corresponding to the phase phase voltages of the voltage restraint characteristic curve see...

Page 283: ...K C PHASE TOC1 BLOCK B PHASE TOC1 VOLT RESTRAINT PHASE TOC1 A PKP PHASE TOC1 A DPO PHASE TOC1 A OP PHASE TOC1 B PKP PHASE TOC1 B DPO PHASE TOC1 B OP PHASE TOC1 C PKP PHASE TOC1 C DPO PHASE TOC1 C OP P...

Page 284: ...001 MESSAGE PHASE IOC1 PICKUP DELAY 0 00 s Range 0 00 to 600 00 s in steps of 0 01 MESSAGE PHASE IOC1 RESET DELAY 0 00 s Range 0 00 to 600 00 s in steps of 0 01 MESSAGE PHASE IOC1 BLOCK A Off Range Fl...

Page 285: ...the 90 or quadrature connection If there is a requirement to supervise overcurrent elements for flows in opposite directions such as can happen through a bus tie breaker two phase directional elements...

Page 286: ...select the source for the operating and polarizing signals The operating current for the phase directional element is the phase current for the selected current source The polar izing voltage is the...

Page 287: ...DIRECTIONAL OC2 See page 5 164 FLEXLOGIC OPERAND FLEXLOGIC OPERAND FLEXLOGIC OPERAND FLEXLOGIC OPERAND SETTING SETTING SETTING SETTING SETTING SETTING PHASE DIR 1 FUNCTION PHASE DIR 1 SOURCE PHASE DIR...

Page 288: ...tan taneous and the element is blocked the time accumulator will be cleared immediately Figure 5 81 NEUTRAL TIME OVERCURRENT 1 SCHEME LOGIC NEUTRAL TOC1 NEUTRAL TOC1 FUNCTION Disabled Range Disabled E...

Page 289: ...d three phase faults The positive sequence restraint must be considered when testing for pickup accuracy and response time multiple of pickup The operating quantity depends on how test currents are in...

Page 290: ...operating quantity EQ 5 16 The positive sequence restraint allows for more sensitive settings by counterbalancing spurious zero sequence currents resulting from System unbalances under heavy load cond...

Page 291: ...ound current When NEUTRAL DIR OC1 POL VOLT is set to Measured VX one third of this voltage is used in place of V_0 The following figure explains the usage of the voltage polarized directional unit of...

Page 292: ...e V_X accordingly must be greater than the VOLTAGE CUTOFF LEVEL setting specified in the PRODUCT SETUP DISPLAY PROPERTIES menu to be validated for use as a polariz ing signal If the polarizing signal...

Page 293: ...Set higher if large system unbalances or poor CT performance are expected NEUTRAL DIR OC1 OFFSET This setting specifies the offset impedance used by this protection The primary appli cation for the of...

Page 294: ...EUTRAL DIR OC1 FWD LIMIT ANGLE NEUTRAL DIR OC1 FWD ECA NEUTRAL DIR OC1 REV LIMIT ANGLE NEUTRAL DIR OC1 OFFSET NEUTRAL DIR OC1 FWD PICKUP NEUTRAL DIR OC1 REV PICKUP NEUTRAL DIR OC1 OP CURR NEUTRAL DIR...

Page 295: ...is from 0 02 to 46 times the CT rating This channel may be also equipped with a sensitive input The conversion range of a sensitive channel is from 0 002 to 4 6 times the CT rating Figure 5 85 GROUND...

Page 296: ...channel is from 0 002 to 4 6 times the CT rating Figure 5 86 GROUND IOC1 SCHEME LOGIC GROUND IOC1 GROUND IOC1 FUNCTION Disabled Range Disabled Enabled MESSAGE GROUND IOC1 SIGNAL SOURCE SRC 1 Range SR...

Page 297: ...gative sequence instantaneous overcurrent elements and two 2 negative sequence directional overcurrent elements For additional information on the negative sequence time overcurrent curves refer to the...

Page 298: ...r will be cleared immediately Figure 5 87 NEGATIVE SEQUENCE TOC1 SCHEME LOGIC NEG SEQ TOC1 NEG SEQ TOC1 FUNCTION Disabled Range Disabled Enabled MESSAGE NEG SEQ TOC1 SIGNAL SOURCE SRC 1 Range SRC 1 SR...

Page 299: ...phase faults The positive sequence restraint must be considered when testing for pickup accuracy and response time multiple of pickup The operating quantity depends on the way the test currents are in...

Page 300: ...ement operating quantity EQ 5 18 The positive sequence restraint allows for more sensitive settings by counterbalancing spurious negative sequence and zero sequence currents resulting from System unba...

Page 301: ...ment Table 5 21 NEGATIVE SEQUENCE DIRECTIONAL OVERCURRENT UNIT Table 5 22 NEGATIVE SEQUENCE DIRECTIONAL UNIT The negative sequence voltage must be greater than the VOLTAGE CUTOFF LEVEL setting specifi...

Page 302: ...ormation on how to calculate this setting In regular applications the offset impedance ensures proper operation even if the negative sequence voltage at the relaying point is very small If this is the...

Page 303: ...verse direc tion Upon NEG SEQ DIR OC1 TYPE selection this pickup threshold applies to zero or negative sequence current When selecting this setting it must be kept in mind that the design uses a posit...

Page 304: ...d to block the functioning of other elements through the block feature of those elements Source Transfer Schemes In the event of an undervoltage a transfer signal may be generated to transfer a load f...

Page 305: ...shown below EQ 5 19 where T operating time D undervoltage delay setting D 0 00 operates instantaneously V secondary voltage applied to the relay Vpickup pickup level Figure 5 91 INVERSE TIME UNDERVOLT...

Page 306: ...to Phase MESSAGE PHASE UV1 PICKUP 1 000 pu Range 0 000 to 3 000 pu in steps of 0 001 MESSAGE PHASE UV1 CURVE Definite Time Range Definite Time Inverse Time MESSAGE PHASE UV1 DELAY 1 00 s Range 0 00 to...

Page 307: ...SRC 1 SRC 2 MESSAGE PHASE OV1 PICKUP 1 000 pu Range 0 000 to 3 000 pu in steps of 0 001 MESSAGE PHASE OV1 PICKUP DELAY 1 00 s Range 0 00 to 600 00 s in steps of 0 01 MESSAGE PHASE OV1 RESET DELAY 1 00...

Page 308: ...rves A B or C or be used as a definite time element The NEUTRAL OV1 PICKUP DELAY setting applies only if the NEUTRAL OV1 CURVE setting is Definite time The source assigned to this element must be conf...

Page 309: ...GE NEG SEQ OV1 SIGNAL SOURCE SRC 1 Range SRC 1 SRC 2 MESSAGE NEG SEQ OV1 PICKUP 0 300 pu Range 0 000 to 1 250 pu in steps of 0 001 MESSAGE NEG SEQ OV1 PICKUP DELAY 0 50 s Range 0 00 to 600 00 s in ste...

Page 310: ...eristics The operating characteristics and equations for both definite and inverse time delay are as for the phase undervoltage element The element resets instantaneously The minimum voltage setting s...

Page 311: ...rner delta VT connection Figure 5 97 AUXILIARY OVERVOLTAGE SCHEME LOGIC AUXILIARY OV1 AUX OV1 FUNCTION Disabled Range Disabled Enabled MESSAGE AUX OV1 SIGNAL SOURCE SRC 1 Range SRC 1 SRC 2 MESSAGE AUX...

Page 312: ...specific protection or control protection element and checking the desired bus box Once the desired element is selected for a specific bus a list of element operate type operands are displayed and can...

Page 313: ...elay should be set long enough to allow the breaker or contactor to perform a required action TRIP BUS 1 INPUT 1 to TRIP BUS 1 INPUT 16 These settings select a FlexLogic operand to be assigned as an i...

Page 314: ...f Range FlexLogic operand MESSAGE GROUP 3 ACTIVATE ON Off Range FlexLogic operand MESSAGE GROUP 6 ACTIVATE ON Off Range FlexLogic operand MESSAGE GROUP 1 NAME Range up to 16 alphanumeric characters ME...

Page 315: ...ve The SETTING GROUP 1 NAME to SETTING GROUP 6 NAME settings allows to user to assign a name to each of the six settings groups Once programmed this name will appear on the second line of the GROUPED...

Page 316: ...wer cycles SELECTOR 1 FULL RANGE This setting defines the upper position of the selector When stepping up through avail able positions of the selector the upper position wraps up to the lower position...

Page 317: ...or does not accept the change and an alarm is established by setting the SELECTOR STP ALARM output FlexLogic operand for 3 seconds SELECTOR 1 ACK This setting specifies an acknowledging input for the...

Page 318: ...e the selector synchronizes to the position dictated by the three bit control input This operation does not wait for time out or the acknowledging input When the synchronization attempt is unsuccessfu...

Page 319: ...hese diagrams T represents a time out setting Figure 5 101 TIME OUT MODE 842737A1 CDR STEP UP 3BIT A0 3BIT A1 3BIT A2 POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 pre existing position...

Page 320: ...p it should synchronize the setting group to the three bit control input Make the following changes to setting group control in the SETTINGS CONTROL ELEMENTS SETTING GROUPS menu SETTING GROUPS FUNCTIO...

Page 321: ...lowing changes in the SETTINGS PRODUCT SETUP USER PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 menu PUSHBUTTON 1 FUNCTION Self reset PUSHBUTTON 1 DROP OUT TIME 0 10 s The logic for the selector switch i...

Page 322: ...y equal to the frequency difference F This time can be calculated by EQ 5 20 where phase angle difference in degrees F frequency difference in Hz SYNCHROCHECK 1 SYNCHK1 FUNCTION Disabled Range Disable...

Page 323: ...ts the combination of dead and live sources that will by pass synchronism check function and permit the breaker to be closed when one or both of the two voltages V1 or and V2 are below the maximum vol...

Page 324: ...e with both phase voltages and an auxiliary voltage ensure that only the auxiliary voltage is programmed in one of the sources to be used for synchrocheck Exception Synchronism cannot be checked betwe...

Page 325: ...ETTINGS F Maximum Max Freq Diff Freq Hysteresis SETTING Maximum Max Angle Diff SETTING V Maximum Max Volt Diff AND OR XOR AND AND AND AND AND 827076AC CDR ACTUAL VALUES Synchrocheck 1 V Synchrocheck 1...

Page 326: ...RST FRM LO Off Range FlexLogic operand MESSAGE AR1 RESET LOCKOUT IF BREAKER CLOSED Off Range Off On MESSAGE AR1 RESET LOCKOUT ON MANUAL CLOSE Off Range Off On MESSAGE AR1 BKR CLOSED Off Range FlexLogi...

Page 327: ...heme is initiated provided the circuit breaker is in the closed state before protection operation The reclose in progress RIP is set when a reclosing cycle begins following a reclose initiate signal O...

Page 328: ...heme to reset from Lockout when the breaker is manually closed regardless if the breaker remains closed or not This setting overrides the previ ous setting AR1 RESET LOCKOUT IF BREAKER CLOSED AR1 BLK...

Page 329: ...On 1 On 1 Off 0 Off 0 Off 0 Disable 0 AR1 ENABLED AR1 DISABLED AR1 BLK FROM MAN CLS Enabled Default Disabled Default AR1 RIP AR1 LO LO AND AND AND AND OR O O O O O O O O Off 0 Off 0 SETTING SETTING SE...

Page 330: ...NT 3 AR1 SHOT CNT 1 AR1 SHOT CNT 0 Increment shot counter Shot cnt 2 Shot cnt 1 Shot cnt 0 Reset shot counter Shot cnt 3 AUTORECLOSE 1 SHOT COUNT 0 1 2 3 4 AR1 CLOSE AND AND AND AND AND AND AND AND 10...

Page 331: ...SEPARATE OPENING TIME CLOSING TIME PROT TIME OPENING TIME PROT TIME ARC EXTINGUISHES ARC EXTINGUISHES CLOSE COMMAND CLOSED COMMAND BKR CLOSED AR INITIATE AR GOES TO LOCKOUT SHOT COUNT MAX RESET FROM L...

Page 332: ...for pickup and reset delays for the output operand DIGITAL ELEMENT 1 INPUT Selects a FlexLogic operand to be monitored by the digital element DIGITAL ELEMENT 1 PICKUP DELAY Sets the required time del...

Page 333: ...y applications it is desired to monitor the breaker trip circuit integrity so problems can be detected before a trip oper ation is required The circuit is considered to be healthy when the voltage mon...

Page 334: ...RCUIT INTEGRITY MONITORING If it is required to monitor the trip circuit continuously independent of the breaker position open or closed a method to maintain the monitoring current flow through the tr...

Page 335: ...perands are provided to indicate if the present value is more than HI equal to EQL or less than LO the set value COUNTER 1 UP Selects the FlexLogic operand for incrementing the counter If an enabled U...

Page 336: ...d for capturing freezing the accumulated count value into a separate register with the date and time of the operation and resetting the count to 0 COUNTER 1 FREEZE COUNT Selects the FlexLogic operand...

Page 337: ...be displayed as an actual value MONITORING ELEMENTS BREAKER 1 ARCING CURRENT See below MESSAGE BREAKER 2 ARCING CURRENT See below MESSAGE VT FUSE FAILURE 1 See page 5 214 MESSAGE VT FUSE FAILURE 2 See...

Page 338: ...fore initiation of this feature and reset of an internal low set overcurrent function Cor rection is implemented to account for a non zero reset time of the overcurrent function Breaker arcing current...

Page 339: ...C BREAKER 1 ARCING AMP LIMIT CLEAR BREAKER 1 ARCING AMPS BKR 1 ARCING AMP A BKR 1 OPERATING TIME A BKR 1 OPERATING TIME B BKR 1 OPERATING TIME C BKR 1 OPERATING TIME BKR 1 ARCING AMP B BKR 1 ARCING A...

Page 340: ...sequence voltage whereas an indication of class B failures is when positive sequence current is present and there is an insignificant amount of positive sequence voltage These noted indications of fus...

Page 341: ...75 pu Run V_1 0 80 pu Run I_1 0 05 pu SRC1 50DD OP FLEXLOGIC OPERANDS 2 cycles 20 cycles SRC1 VT FUSE FAIL OP FLEXLOGIC OPERANDS SRC1 VT FUSE FAIL DPO SRC1 VT FUSE FAIL VOL LOSS FLEXLOGIC OPERAND TIME...

Page 342: ...broken the I_2 I_1 ratio with a balanced remaining two phases is 50 So normally this setting should be set below 50 for example to 30 BROKEN CONDUCTOR 1 I1 MIN This setting specifies the minimum posi...

Page 343: ...SETTING Run 0 2 cyc FLEXLOGIC OPERAND BROKEN CONDUCT 1 OP FLEXLOGIC OPERAND BROKEN CONDUCT 1 PKP 832030A1 cdr I1 Ia Ib Ic I1 I1 MIN Ia I1 MIN Ib I1 MIN Ic I1 MIN Ic Ia Ia 0 05 pu Ib Ib 0 05 pu Ic Ic 0...

Page 344: ...protection trip time constant I measured overload RMS current Ip measured load RMS current before overload occurs k IEC 255 8 k factor applied to IB defining maximum permissible current above nominal...

Page 345: ...delayed using following formula EQ 5 23 In the above equation rst thermal protection trip time constant Tmin is a minimum reset time setting Figure 5 116 IEC 255 8 SAMPLE OPERATE AND RESET CURVES The...

Page 346: ...operand can be reset using THERM PROT 1 RESET setting All calculations are performed per phase If the accumulated energy reaches value 1 in any phase the thermal overload protection element operates...

Page 347: ...a user settable debounce time in order for the D30 to validate the new contact state In the figure below the debounce time is set at 2 5 ms thus the 6th sample in a row validates the change of state...

Page 348: ...o filter the LOW HIGH marks no 1 2 3 and 4 in the figure below and HIGH LOW marks no 5 6 7 and 8 below transitions Figure 5 118 INPUT CONTACT DEBOUNCING MECHANISM AND TIME STAMPING SAMPLE TIMING Conta...

Page 349: ...operand will be set to on for only one evaluation of the FlexLogic equations and then return to off If set to Latched the virtual input sets the state of the output operand to the same state as the mo...

Page 350: ...vent damage to the less robust initiating contact This can be done by monitoring an auxiliary contact on the breaker which opens when the breaker has tripped but this scheme is subject to incorrect op...

Page 351: ...g specifies the contact response under conflicting control inputs that is when both the OPERATE and RESET signals are applied With both control inputs applied simultaneously the contact will close if...

Page 352: ...erVista UR Setup example shown Program the Latching Outputs by making the following changes in the SETTINGS INPUTS OUTPUTS CONTACT OUT PUTS CONTACT OUTPUT H1a menu assuming an H4L module OUTPUT H1a OP...

Page 353: ...cation includes features that are used to cope with the loss of communication between transmitting and receiving devices Each transmitting device will send a GSSE GOOSE message upon a successful power...

Page 354: ...e receiving relay are extracted from GSSE GOOSE messages originat ing in remote devices Each remote input can be selected from a list consisting of DNA 1 through DNA 32 UserSt 1 through UserSt 32 and...

Page 355: ...ed with the five remote double point status input settings REM DPS IN 1 ID This setting assigns descriptive text to the remote double point status input REM DPS IN 1 DEV This setting selects a remote...

Page 356: ...ate LED event indicators and the target message on the display Once set the latching mechanism will hold all of the latched indicators or messages in the set state after the initiating condition has c...

Page 357: ...irst communication exchange the input will default to Logic 1 When communication resumes the input becomes fully operational Setting DIRECT INPUT 1 DEFAULT STATE to Latest Off freezes the input in cas...

Page 358: ...l from downstream devices say 2 3 and 4 to the upstream device that monitors a single incomer of the busbar as shown in the figure below Figure 5 121 SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME Assum...

Page 359: ...plied using the architecture shown below The scheme output operand HYB POTT TX1 is used to key the permission Figure 5 123 SINGLE CHANNEL OPEN LOOP CONFIGURATION In the above architecture Devices 1 an...

Page 360: ...by assigning FlexLogic operands to be sent via the selected communications channel This allows the user to create distributed protec tion and control schemes via dedicated communications channels Som...

Page 361: ...outputs is dependent on the number of com munication channels and terminals On two terminal two channel systems they are processed continuously on each chan nel and mapped separately per channel Ther...

Page 362: ...oint values with no units The GOOSE UNIT and PU base settings allow the user to configure GOOSE Analog so that it can be used in a FlexElement GOOSE ANALOG INPUT 1 ANALOG 1 DEFAULT 1000 000 Range 1000...

Page 363: ...he following settings are available for each GOOSE uinteger input UINTEGER 1 DEFAULT This setting specifies the value of the GOOSE uinteger input when the sending device is offline and the UINTEGER 1...

Page 364: ...are automatically generated for every channel available in the specific relay as shown above for the first channel of a type 5F transducer module installed in slot H The function of the channel may be...

Page 365: ...s are automatically generated for every channel available in the specific relay as shown above for the first channel of a type 5C transducer module installed in the first available slot The function o...

Page 366: ...22 119 39 157 74 131 45 10 97 60 140 123 24 165 90 138 25 11 35 70 158 127 07 174 25 145 20 11 74 80 176 130 89 182 84 152 37 12 12 90 194 134 70 191 64 159 70 12 51 100 212 138 50 200 64 167 20 12 90...

Page 367: ...tput are user programmable via the following settings menu an exam ple for channel M5 is shown The relay checks the driving signal x in equations below for the minimum and maximum limits and subsequen...

Page 368: ...urrent The setting is entered in per unit values The base units are defined in the same manner as the FlexElement base units The DCMA OUTPUT H1 MIN VAL and DCMA OUTPUT H1 MAX VAL settings are ignored...

Page 369: ...S DCMA OUTPUT H2 RANGE 4 to 20 mA DCMA OUTPUT H2 MIN VAL 0 000 pu DCMA OUTPUT H2 MAX VAL 1 260 pu The worst case error for this application could be calculated by superimposing the following two sourc...

Page 370: ...he VTs are connected in Delta refer to the Metering conventions section in chapter 6 while at the same time the VT nominal voltage is 1 pu for the settings Consequently the settings required in this e...

Page 371: ...ons based inputs and outputs remain fully operational in test mode If a control action is programmed using direct inputs and outputs or remote inputs and outputs then the test procedure must take this...

Page 372: ...e across the input terminals The force contact inputs feature provides a method of performing checks on the function of all contact inputs Once enabled the relay is placed into test mode allowing this...

Page 373: ...nd 3 should open and contact input 4 should close Also contact output 1 should freeze contact output 2 should open contact output 3 should close and contact output 4 should remain fully opera tional T...

Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...

Page 375: ...S See page 6 4 VIRTUAL OUTPUTS See page 6 5 AUTORECLOSE See page 6 5 REMOTE DEVICES STATUS See page 6 5 REMOTE DEVICES STATISTICS See page 6 6 DIGITAL COUNTERS See page 6 6 SELECTOR SWITCHES See page...

Page 376: ...MENTS See page 6 19 IEC 61850 GOOSE ANALOGS See page 6 19 TRANSDUCER I O DCMA INPUTS See page 6 20 TRANSDUCER I O RTD INPUTS See page 6 20 ACTUAL VALUES RECORDS FAULT REPORTS See page 6 21 EVENT RECOR...

Page 377: ...ndicates the ID of the virtual input For example Virt Ip 1 refers to the virtual input in terms of the default name The second line of the display indicates the logic state of the virtual input 6 2 3...

Page 378: ...ere The first line of a message display indicates the ID of the contact output For example Cont Op 1 refers to the contact output in terms of the default name array index The second line of the displa...

Page 379: ...output 6 2 8 AUTORECLOSE PATH ACTUAL VALUES STATUS AUTORECLOSE AUTORECLOSE 1 The automatic reclosure shot count is shown here 6 2 9 REMOTE DEVICES a STATUS PATH ACTUAL VALUES STATUS REMOTE DEVICES STA...

Page 380: ...L COUNTERS DIGITAL COUNTERS Counter 1 8 The present status of the eight digital counters is shown here The status of each counter with the user defined counter name includes the accumulated and frozen...

Page 381: ...zero The grandmasterIdentity code is specified by PTP to be globally unique so one can always know which clock is grandmaster in a system with multiple grandmaster capable clocks FLEX STATES PARAM 1 O...

Page 382: ...TH ACTUAL VALUES STATUS DIRECT INPUTS The AVERAGE MSG RETURN TIME is the time taken for direct output messages to return to the sender in a direct input output ring configuration this value is not app...

Page 383: ...is menu The GGIO5 integer data values are received via IEC 61850 GOOSE messages sent from other devices 6 2 18 TELEPROTECTION CHANNEL TESTS PATH ACTUAL VALUES STATUS TELEPROT CH TESTS The status infor...

Page 384: ...the local relay ID is set to a default value of 0 the chan nel is failed or if the teleprotection inputs outputs are not enabled 6 2 19 REMAINING CONNECTION STATUS PATH ACTUAL VALUES STATUS COMM STAT...

Page 385: ...PF Lag Current Voltage WATTS Positive VARS Negative PF Lead Current Voltage WATTS Negative VARS Negative PF Lag Current Voltage WATTS Negative VARS Positive PF Lead Current Generator Generator Inducti...

Page 386: ...not measurable the phase angles are not referenced The phase angles are assigned as positive in the leading direction and are presented as negative in the lagging direction to more closely align with...

Page 387: ...strated in the following figure Figure 6 3 MEASUREMENT CONVENTION FOR SYMMETRICAL COMPONENTS ABC phase rotation ACB phase rotation Table 6 1 SYMMETRICAL COMPONENTS CALCULATION EXAMPLE SYSTEM VOLTAGES...

Page 388: ...PATH ACTUAL VALUES METERING SOURCE SRC 1 PHASE CURRENT SOURCE SRC 1 PHASE CURRENT SRC 1 See page 6 14 MESSAGE GROUND CURRENT SRC 1 See page 6 15 MESSAGE PHASE VOLTAGE SRC 1 See page 6 15 MESSAGE AUXI...

Page 389: ...source see SETTINGS SYSTEM SETUP SIGNAL SOURCES d PHASE VOLTAGE METERING PATH ACTUAL VALUES METERING SOURCE SRC 1 PHASE VOLTAGE MESSAGE SRC 1 NEG SEQ I2 0 000 A 0 0 GROUND CURRENT SRC 1 SRC 1 RMS Ig 0...

Page 390: ...e SETTINGS SYSTEM SETUP SIGNAL SOURCES f POWER METERING PATH ACTUAL VALUES METERING SOURCE SRC 1 POWER MESSAGE SRC 1 POS SEQ V1 0 000 V 0 0 MESSAGE SRC 1 NEG SEQ V2 0 000 V 0 0 AUXILIARY VOLTAGE SRC 1...

Page 391: ...menu The SRC 1 text will be replaced by whatever name was pro grammed by the user for the associated source see SETTINGS SYSTEM SETUP SIGNAL SOURCES SOURCE FREQUENCY is measured via software implement...

Page 392: ...CKING FREQUENCY The tracking frequency is displayed here The frequency is tracked based on the selection of the reference source with the FREQUENCY AND PHASE REFERENCE setting in the SETTINGS SYSTEM S...

Page 393: ...s sent from other devices FLEXELEMENT 1 FLEXELEMENT 1 OpSig 0 000 pu Table 6 2 FLEXELEMENT BASE UNITS BREAKER ARCING AMPS Brk X Arc Amp A B and C BASE 2000 kA2 cycle DCmA BASE maximum value of the DCM...

Page 394: ...hat is enabled are displayed with the top line as the programmed channel ID and the bottom line as the value followed by the programmed units PATH ACTUAL VALUES METERING TRANSDUCER I O RTD INPUTS RTD...

Page 395: ...records have been filled the oldest record will be removed as a new record is added Each event record shows the event identifier sequence number cause and date time stamp associated with the event tr...

Page 396: ...BREAKER MAINTENANCE PATH ACTUAL VALUES RECORDS MAINTENANCE BREAKER 1 2 There is an identical menu for each of the breakers The BKR 1 ARCING AMP values are in units of kA2 cycles Refer to the COMMANDS...

Page 397: ...code format MESSAGE ORDER CODE LINE 3 Range standard GE Multilin order code format MESSAGE ORDER CODE LINE 4 Range standard GE Multilin order code format MESSAGE SERIAL NUMBER Range standard GE Multi...

Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...

Page 399: ...RTUAL INPUTS PATH COMMANDS VIRTUAL INPUTS The states of up to 64 virtual inputs are changed here The first line of the display indicates the ID of the virtual input The second line indicates the curre...

Page 400: ...setting is based on the 24 hour clock The complete date as a minimum must be entered to allow execution of this command The new time if entered and date will take effect at the moment the ENTER key i...

Page 401: ...ole can initiate the Reboot Relay command The SERVICE COMMAND is used to perform specific D30 service actions Presently there is only one service action avail able Code 101 is used to clear factory di...

Page 402: ...Engineer Logoff Selecting Yes allows the Supervisor to forcefully logoff an engineer session Operator Logoff Selecting Yes allows the Supervisor to forcefully logoff an operator session Clear Security...

Page 403: ...formation will be included if applicable If a tar get message status changes the status with the highest priority will be displayed If a self test error is detected a message appears indicating the ca...

Page 404: ...r If the problem persists contact the factory Latched target message No Description of problem A FlexLogic equation is incorrect How often the test is performed The test is event driven performed when...

Page 405: ...ta UR Setup software will list the valid items An IEC61850 client will also show which nodes are available for the D30 Latched target message Yes Description of problem The battery is not functioning...

Page 406: ...ernet cable s are properly connected At least one PTP grandmaster capable clock is functioning If strict PP is enabled that entire network is PP compliant The network is delivering PTP messages to the...

Page 407: ...en the test is performed Event driven The test is performed when a device programmed to receive GOOSE messages stops receiving This can be from 1 to 60 seconds depending on GOOSE packets What to do Ch...

Page 408: ...If a module has intentionally been added or removed use the Update Order Code command to notify the relay that the current module configuration is correct Module Failure Major Self Test Description U...

Page 409: ...order code and or core number Check that the correct core on the correct Brick is patched through to the correct Process Card port and that the field unit settings are correct An indication of communi...

Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...

Page 411: ...default This allows access to the device immediately after installation When security is disabled all users are granted administrator access To enable the security system and require password use 1 S...

Page 412: ...ION Delete Entry Deletes the user account when exiting the user management window Actual Values Allows the user to read actual values Settings Allows the user to read setting values Commands Allows th...

Page 413: ...ACCESS RIGHTS SUMMARY FIELD DESCRIPTION Delete Entry Deletes the user account when exiting the user management window Actual Values Allows the user to read actual values Settings Allows the user to re...

Page 414: ...ecified in the U S National Security Agency Suite B extension for SSH and approved by the National Institute of Standards and Technology NIST FIPS 140 2 standards for cryptographic systems Example Adm...

Page 415: ...al authentication database to authenticate the user No password or security information are displayed in plain text by the EnerVista software or UR device nor are they ever transmitted without cryptog...

Page 416: ...ed 0 0 0 0 255 255 255 255 0 0 0 0 Administrator Primary Authentication Port RADIUS authentication port 1 65535 1812 Administrator Primary Accounting Port RADIUS accounting port 1 65535 1813 Administr...

Page 417: ...inistrator is to re enable local authentication when local authentication is disabled To re enable local authentication the Supervisor unlocks the device for setting changes and then the Administrator...

Page 418: ...mpt is made the device alarm activates If No the device alarm does not activate On each firmware upgrade this setting goes back to the default No Yes Yes Administrator Settings lock A Boolean value in...

Page 419: ...tting RW RW R R R Direct Inputs RW RW R R R Direct Outputs RW RW R R R Teleprotection RW RW R R R Direct Analogs RW RW R R R Direct Integers RW RW R R R IEC61850 GOOSE Analogs RW RW R R R IEC61850 GOO...

Page 420: ...nts possible on the UR if the user ID credential does not match one of the five local accounts the UR automatically forwards the request to a RADIUS server when one is provided If a RADIUS server is p...

Page 421: ...ed operation after the memory expires Con sequently zone 1 is recommended as an underreaching element and zones 2 through 5 are recommended as overreach ing elements and for time delayed tripping The...

Page 422: ...istic impedance 1 DIR RCA ZR right blinder characteristic impedance ZR RGT BLD sin RGT BLD RCA 1 RGT BLD RCA 90 ZL left blinder characteristic impedance ZL LFT BLD sin LFT BLD RCA 1 LFT BLD RCA 90 K0...

Page 423: ...A phase element IC IA Z VC VA and IC IA Z A ground element IA Z I_0 K0 Z IG K0M Z VA and I_0 Z B ground element IB Z I_0 K0 Z IG K0M Z VB and I_0 Z C ground element IC Z I_0 K0 Z IG K0M Z VC and I_0 Z...

Page 424: ..._1M BC phase element IB IC ZD and VB VC _1M CA phase element IC IA ZD and VC VA _1M A ground element I_0 ZD and VA_1M IA_2 ZD and VA_1M B ground element I_0 ZD and VB_1M IB_2 ZD and VB_1M C ground ele...

Page 425: ...es l OVERCURRENT SUPERVISION The overcurrent supervision responds to the following currents AB phase element IA IB BC phase element IB IC CA phase element IC IA A B C ground element 3 I_0 0 05 I_1 The...

Page 426: ...d in the reverse direction for a forward fault by an amount proportional to the source impedance and in the for ward direction for a reverse fault Directional I_0 ZD V_1M DIR COMP LIMIT Directional I_...

Page 427: ...comparators Both the currents are from the protected line and are not affected by any compensation as the latter applies only to the reach defining comparators the mho reac tance and blinder characte...

Page 428: ...25 43 V 19 9 VB 80 22 V 133 5 VC 77 33 V 135 7 IA 4 47 A 107 8 IB 2 92 A 68 9 IC 2 93 A 51 1 Based on the entered setting the relay calculates K0 3 58 15 2 K0M 0 Z 14 00 88 ZD 1 88 ZR 9 99 2 ZL 4 99 1...

Page 429: ...ional difference angle 19 8 2 1 21 9 75 Negative sequence directional difference angle 19 8 2 1 21 9 75 Fault type comparator difference angle 19 8 19 8 0 0 50 All four comparators and the overcurrent...

Page 430: ...t supervision 3 I_0 4 09 A 3 A Reactance difference angle 3 9 24 8 28 7 75 Zero sequence difference angle 19 8 0 0 19 8 75 Negative sequence directional difference angle 19 8 0 0 19 8 75 Right blinder...

Page 431: ...on of the VTs and CTs with respect to the involved power transformer and the direction of any given zone In the following equations the VT and CT locations are referenced as None if the transformer is...

Page 432: ...IA IB VAB IB IC VBC IC IA VCA 3IA 1 3 VAB VCA 3IB 1 3 VBC VAB 3IC 1 3 VCA VBC IAB_21P 3IC VAB_21P 1 3 VBC VCA IBC_21P 3IA VBC_21P 1 3 VCA VAB ICA_21P 3IB VCA_21P 1 3 VAB VBC IAB_21P 3IB VAB_21P 1 3 V...

Page 433: ...IBC_21P 1 3 2IB IA IC VBC_21P 3VB ICA_21P 1 3 2IC IA IB VCA_21P 3VC IAB_21P 1 3 IA IB 2IC VAB_21P 3VC IBC_21P 1 3 IB IC 2IA VBC_21P 3VA ICA_21P 1 3 IA IC 2IB VCA_21P 3VB IAB_21P 1 3 2IB IA IC VAB_21P...

Page 434: ...e information on set tings please refer to Chapter 9 Application of Settings 9 2 2 EXAMPLE Consider the system shown below Figure 9 5 SAMPLE SYSTEM CONFIGURATION Normally in order to respond to the fa...

Page 435: ...econdary side The above example illustrates how the relay maintains correct reach for fault behind power transformers When installed at X the relay shall be set to 0 687 85 secondary in order to reach...

Page 436: ...on for both forward and reverse faults The same principle applies to the neutral directional overcurrent element 9 3 2 EXAMPLE Consider relay input signals as in the Distance Elements Analysis section...

Page 437: ...0 Line Distance Protection System 9 17 9 THEORY OF OPERATION 9 3 GROUND DIRECTIONAL OVERCURRENT 9 I_op I_2 I_1 8 1 003 A 0 25 A The overcurrent unit will pickup and the element will operate in the for...

Page 438: ...cked prior to declaring a forward fault On close in forward faults beyond the series capacitors as seen from the relaying point the current inversion phenomenon may take place for a short period of ti...

Page 439: ...s to this internal fault Traditional approach would leave this fault out of the relay reach The neutral and negative sequence directional protection functions of the relay cope with the voltage and or...

Page 440: ...V Impedance Trajectory The reach is safely reduced a Steady state apparent impedance R X FAR END BUSBAR M O V S C RF Impedance Trajectory no subsynchronous oscillations The reach is not reduced Set re...

Page 441: ...fault Z positive sequence impedance of the line The currents from the local and remote systems can be parted between their fault F and pre fault load pre components EQ 9 8 and neglecting shunt parame...

Page 442: ...PORT 1 VT SUBSTITUTION setting value is V0 and the VTs are connected in a wye configuration the fault location is performed based on the actual phase to ground voltages If the VTs are connected in a d...

Page 443: ...SRC 50DD OP X VA or VAB VC or VCA VB or VBC 827094A5 CDR Off 0 AND FAULT LOCATOR 1 RUN 0 3 SEC ACTUAL VALUES DATE TIME FAULT TYPE FAULT LOCATION FAULT RECLOSE SHOT FAULT REPORT Vn or V_0 FAULT REPORT...

Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...

Page 445: ...t low SIR values fast fault clearance times may be seen as extremely important both from system stability and from equipment damage viewpoints The high set overcurrent element when set appropriately c...

Page 446: ...ion after detecting fuse fail conditions and blocking the distance elements to using it and accepting the fact that the distance protection will not respond to subsequent internal faults until the pro...

Page 447: ...ook ing protection The fifth distance zone can be used as an alarm zone indicating that load impedance is approaching the zone characteristic 10 2 2 GROUND DISTANCE a NEUTRAL CURRENT SUPERVISION The c...

Page 448: ...compromise choice is made or different settings are applied via switchable setting groups depending on system conditions In highly non homogenous and dynamic systems where the correction for non homo...

Page 449: ...rther contribution to a remote backup philosophy the reach of this element must be set to account for any infeed at the remote bus The time delay must coordinate with other time delayed protections on...

Page 450: ...ionally the reach setting of an underreaching distance function shall be set based on the net inductive impedance between the potential source of the relay and the far end busbar or location for which...

Page 451: ...et Otherwise the offset impedance shall be at least the net capacitive reactance 2 The offset cannot be higher than the net inductive reactance between the potential source and the remote equivalent s...

Page 452: ...transformer connection and vector group as seen from the CTs toward the reach point Otherwise the CT connection setting shall be set to None 4 The voltage signals require compensation if the transfor...

Page 453: ...located between the potential source and the reach point for Z1 the reach impedance must not include the positive sequence impedance of the transformer The CTs are located on the other side of the tra...

Page 454: ...DISTANCE THROUGH POWER TRANSFORMERS 10 APPLICATION OF SETTINGS 10 The Zone 3 settings are EQ 10 10 PHS DIST Z3 REACH 2 60 PHS DIST Z3 RCA 89 PHS DIST Z3 XMFR VOL CONNECTION Yd11 PHS DIST Z3 XMFR CUR C...

Page 455: ...b screw has been removed as shown below This allows for easy accessibility of the modules for withdrawal The new wide angle hinge assembly in the enhanced front panel opens completely and allows easy...

Page 456: ...Once the clips have cleared the raised edge of the chassis engage the clips simultaneously When the clips have locked into position the module will be fully inserted CPU connections must be individual...

Page 457: ...typically in the first slot on the left side and blocked by the hinge of the front panel To remove the front panel unscrew the bracket on the front left side of the unit 5 Simultaneously pull the ejec...

Page 458: ...gen Sie diese Batterie zu Ihrem lokalen Lieferanten zur ck oder entsorgen Sie das Produkt an den gekennzeichneten Sammelstellen Weitere Informationen hierzu finden Sie auf der folgenden Website www re...

Page 459: ...ndictaies bevatten cadium Cd lood Pb of kwik Hg Voor correcte vorm van kringloop geef je de producten terug aan jou locale leverancier of geef het af aan een gespecialiseerde verzamelpunt Meer informa...

Page 460: ...d rf r avsedd deponering F r mer information se www recyclethis info TR Pil Geri D n m Bu r n Avrupa Birli i genel at k sistemlerine at lmamas gereken pil i ermektedir Daha detayl pil bilgisi i in r...

Page 461: ...vice for example to comply with data security regu lations On the computer settings files can identified by the urs extension To clear the current settings file create a default set tings file write i...

Page 462: ...pack the unit in a box with bubble wrap foam material or styrofoam inserts or packaging peanuts to cushion the item s You may also use double boxing whereby you place the box in a larger box that cont...

Page 463: ...E Store the unit indoors in a cool dry place If possible store in the original packaging Follow the storage temperature range outlined in the Specifications To avoid deterioration of electrolytic capa...

Page 464: ...an the battery there are no special requirements for disposal of the unit at the end its service life For customers located in the European Union dispose of the battery as outlined earlier To prevent...

Page 465: ...1 phase B current RMS 6148 SRC 1 Ic RMS Amps Source 1 phase C current RMS 6150 SRC 1 In RMS Amps Source 1 neutral current RMS 6152 SRC 1 Ia Mag Amps Source 1 phase A current magnitude 6154 SRC 1 Ia An...

Page 466: ...MS 6660 SRC 1 Vcg RMS Volts Source 1 phase CG voltage RMS 6662 SRC 1 Vag Mag Volts Source 1 phase AG voltage magnitude 6664 SRC 1 Vag Angle Degrees Source 1 phase AG voltage angle 6665 SRC 1 Vbg Mag V...

Page 467: ...oltage angle 6755 SRC 2 V_0 Mag Volts Source 2 zero sequence voltage magnitude 6757 SRC 2 V_0 Angle Degrees Source 2 zero sequence voltage angle 6758 SRC 2 V_1 Mag Volts Source 2 positive sequence vol...

Page 468: ...Degrees Fault 1 pre fault phase B voltage angle 9039 Prefault Vc Mag 0 Volts Fault 1 pre fault phase C voltage magnitude 9041 Prefault Vc Ang 0 Degrees Fault 1 pre fault phase C voltage angle 9042 Po...

Page 469: ...input 11 actual value 13526 DCmA Inputs 12 Value mA DCmA input 12 actual value 13528 DCmA Inputs 13 Value mA DCmA input 13 actual value 13530 DCmA Inputs 14 Value mA DCmA input 14 actual value 13532 D...

Page 470: ...D input 35 actual value 13587 RTD Inputs 36 Value RTD input 36 actual value 13588 RTD Inputs 37 Value RTD input 37 actual value 13589 RTD Inputs 38 Value RTD input 38 actual value 13590 RTD Inputs 39...

Page 471: ...nce Ibc angle 63494 Dist Ica Mag Volts Distance Ica magnitude 63496 Dist Ica Angle Degrees Distance Ica angle 63497 Dist IabZ Vab Ang 1 Degrees Distance IabZ Vab angle 1 63498 Dist IabZ Vab Ang 2 Degr...

Page 472: ...bcZR angle 1 63542 IbcZR V IbcZR 2 Degrees Distance IbcZR Vbc IbcZR angle 2 63543 IbcZR V IbcZR 3 Degrees Distance IbcZR Vbc IbcZR angle 3 63544 IbcZR V IbcZR 4 Degrees Distance IbcZR Vbc IbcZR angle...

Page 473: ...istance IcgZR Vcg IcgZR angle 4 63580 IcgZR V IcgZR Ang 5 Degrees Distance IcgZR Vcg IcgZR angle 5 63581 IagZL V IagZL Ang 1 Degrees Distance IagZL Vag IagZL angle 1 63582 IagZL V IagZL Ang 2 Degrees...

Page 474: ...9974 GOOSE UInt Input 4 IEC61850 GOOSE UInteger input 4 9976 GOOSE UInt Input 5 IEC61850 GOOSE UInteger input 5 9978 GOOSE UInt Input 6 IEC61850 GOOSE UInteger input 6 9980 GOOSE UInt Input 7 IEC61850...

Page 475: ...nal RS485 port can be set for baud rates of 300 1200 2400 4800 9600 14400 19200 28800 33600 38400 57600 or 115200 bps and even odd and no parity options are available See the Communications section of...

Page 476: ...he following describes the ADU MBAP header This Modbus Application Protocol header contains the following fields Transaction Identifier Used for transaction pairing The Modbus server copies in the res...

Page 477: ...er of data bytes Di i th data byte i 0 to N 1 G 16 bit characteristic polynomial 1010000000000001 binary with MSbit dropped and bit order reversed shr x right shift operator th LSbit of x is shifted i...

Page 478: ...read Function codes 03h and 04h are therefore identical The following table shows the format of the master and slave packets in Modbus RTU Modbus TCP IP ADUs have a MBAP instead of slave address and...

Page 479: ...0 at memory map address 4051h to slave device 11h 17 dec Table B 5 MASTER AND SLAVE DEVICE PACKET TRANSMISSION EXAMPLE MASTER TRANSMISSION SLAVE RESPONSE PACKET FORMAT EXAMPLE HEX PACKET FORMAT EXAMPL...

Page 480: ...the function code set to 1 The following table shows the format of the master and slave packets in Modbus RTU Modbus TCP IP ADUs have a MBAP instead of slave address and CRC is in another stack layer...

Page 481: ...ile transfer information so files may be read simultaneously on multiple Modbus connections b OTHER PROTOCOLS All the files available via Modbus may also be retrieved using the standard file transfer...

Page 482: ...TXT replace nnn with the desired starting record number To read from a specific record to another specific record use the following filename EVT TXT xxxxx yyyyy replace xxxxx with the starting record...

Page 483: ...Number F203 none 00C0 Ethernet Sub Module Serial Number 8 items F203 none Product Information Read Only Written by Factory 0110 FPGA Version F206 none 0113 FPGA Date 0 to 4294967295 1 F050 0 Self Test...

Page 484: ...nput 43 State 0 to 1 1 F108 0 Off 042B Virtual Input 44 State 0 to 1 1 F108 0 Off 042C Virtual Input 45 State 0 to 1 1 F108 0 Off 042D Virtual Input 46 State 0 to 1 1 F108 0 Off 042E Virtual Input 47...

Page 485: ...Input Output States Read Only 1540 Remote Device States 2 items 0 to 65535 1 F500 0 1542 Remote Input States 4 items 0 to 65535 1 F500 0 1550 Remote Devices Online 0 to 1 1 F126 0 No 1551 Remote Doubl...

Page 486: ...8 modules 16C8 Field Transducer 1 Value 32 768 to 32 767 0 001 F004 0 16CA Repeated for Field Transducer 2 16CC Repeated for Field Transducer 3 16CE Repeated for Field Transducer 4 16D0 Repeated for F...

Page 487: ...359 9 to 0 degrees 0 1 F002 0 1A1B Source 1 Phase CA or CB Voltage Magnitude 0 to 999999 999 V 0 001 F060 0 1A1D Source 1 Phase CA or CB Voltage Angle 359 9 to 0 degrees 0 1 F002 0 1A1E Source 1 Auxi...

Page 488: ...Arcing Current Actuals Read Only Non Volatile 2 modules 21F2 Repeated for module number 2 Breaker Arcing Current Commands Read Write Command 2 modules 2224 Breaker 1 Arcing Current Clear Command 0 to...

Page 489: ...to 32 1 F001 1 2621 Remote Double Point Status Input 1 Item 0 to 64 1 F606 0 None 2622 Remote Double Point Status Input 1 Name 1 to 64 1 F205 RemDPS Ip 1 2628 Remote Double Point Status Input 1 Events...

Page 490: ...tates one per register 64 items 0 to 1 1 F108 0 Off Oscillography Values Read Only 3000 Oscillography Number of Triggers 0 to 65535 1 F001 0 3001 Oscillography Available Records 0 to 65535 1 F001 0 30...

Page 491: ...ator Alphanumeric Password Status 0 to 1 1 F102 0 Disabled Security Read Write 32CA Operator Alphanumeric Password Entry F202 none Security Read Write Setting 32D4 Observer Alphanumeric Password Setti...

Page 492: ...999 0 001 F004 0 34D2 DCmA Inputs 10 Value 9999 999 to 9999 999 0 001 F004 0 34D4 DCmA Inputs 11 Value 9999 999 to 9999 999 0 001 F004 0 34D6 DCmA Inputs 12 Value 9999 999 to 9999 999 0 001 F004 0 34D...

Page 493: ...C 1 F002 0 3514 RTD Input 37 Value 32768 to 32767 C 1 F002 0 3515 RTD Input 38 Value 32768 to 32767 C 1 F002 0 3516 RTD Input 39 Value 32768 to 32767 C 1 F002 0 3517 RTD Input 40 Value 32768 to 32767...

Page 494: ...808 Field Unit 1 Serial Number 0 to1 1 F205 000000000000 380E Field Unit 1 Port 1 to 4 1 F001 1 380F Repeated for Field Unit 2 381E Repeated for Filed Unit 3 382D Repeated for Filed Unit 4 383C Repeat...

Page 495: ...ut 6 3942 Repeated for Field Contact Input 7 394D Repeated for Field Contact Input 8 3958 Repeated for Field Contact Input 9 3963 Repeated for Field Contact Input 10 396E Repeated for Field Contact In...

Page 496: ...eal In 6 items 0 to 4294967295 1 F300 0 3BCC Field Output 1 Events 6 items 0 to 1 1 F102 1 Enabled 3BD2 Repeated for Field Contact Output 2 3C14 Repeated for Field Contact Output 3 3C56 Repeated for F...

Page 497: ...5 3F28 Repeated for Field Unit RTD 6 3F30 Repeated for Field Unit RTD 7 3F38 Repeated for Field Unit RTD 8 Field Unit Transducers Read Write Setting 8 modules 3F40 Field Unit Transducer 1 Name 0 to 1...

Page 498: ...0 Disabled 4049 LED Test Control 0 to 4294967295 1 F300 0 Preferences Read Write Setting 404F Language 0 to 4 1 F531 0 English 4050 Flash Message Time 0 5 to 10 s 0 1 F001 10 4051 Default Message Time...

Page 499: ...001 240 40C2 DNP Client Address 3 0 to 4294967295 1 F003 0 40C4 DNP Client Address 4 0 to 4294967295 1 F003 0 40C6 DNP Client Address 5 0 to 4294967295 1 F003 0 40C8 DNP Number of Paired Binary Output...

Page 500: ...0 4154 Ethernet Switch Port 1 Status 0 to 2 1 F134 0 Fail 4155 Ethernet Switch Port 2 Status 0 to 2 1 F134 0 Fail 4156 Ethernet Switch Port 3 Status 0 to 2 1 F134 0 Fail 4157 Ethernet Switch Port 4 St...

Page 501: ...odules 42C0 FlexLogic Operand to Activate LED 0 to 4294967295 1 F300 0 42C2 User LED type latched or self resetting 0 to 1 1 F127 1 Self Reset 42C3 Repeated for User Programmable LED 2 42C6 Repeated f...

Page 502: ...Disabled 4445 User Programmable Secondary Ethernet Fail Function 0 to 1 1 F102 0 Disabled 4446 User Programmable Battery Fail Function 0 to 1 1 F102 1 Enabled 4447 User Programmable SNTP Fail Functio...

Page 503: ...ntrol 0 to 1 1 F102 0 Disabled 47E4 Breaker 1 Manual Close Recall Time 0 to 65 535 s 0 001 F003 0 47E6 Breaker 1 Out of Service 0 to 4294967295 1 F300 0 47E8 Breaker 1 Block Open 0 to 4294967295 1 F30...

Page 504: ...0 001 F003 0 4E17 Raw Field Data AC8 Angle 0 to 0 01 degree 0 1 F002 0 4E18 Raw Field Data DC1 0 to 0 001 V 0 001 F002 0 4E19 Raw Field Data DC2 0 to 0 001 V 0 001 F002 0 4E1A Raw Field Data DC3 0 to...

Page 505: ...ated for RTD Input 21 55A4 Repeated for RTD Input 22 55B8 Repeated for RTD Input 23 55CC Repeated for RTD Input 24 55E0 Repeated for RTD Input 25 55F4 Repeated for RTD Input 26 5608 Repeated for RTD I...

Page 506: ...or FlexLogic Timer 30 58F0 Repeated for FlexLogic Timer 31 58F8 Repeated for FlexLogic Timer 32 Phase Time Overcurrent Read Write Grouped Setting 2 modules 5900 Phase Time Overcurrent 1 Function 0 to...

Page 507: ...ay 0 to 600 s 0 01 F001 0 5C05 Neutral Instantaneous Overcurrent 1 Block 0 to 4294967295 1 F300 0 5C07 Neutral Instantaneous Overcurrent 1 Target 0 to 2 1 F109 0 Self reset 5C08 Neutral Instantaneous...

Page 508: ...oreclose 1 Breaker Open 0 to 4294967295 1 F300 0 6210 Autoreclose 1 Block Time Upon Manual Close 0 to 655 35 s 0 01 F001 1000 6211 Autoreclose 1 Dead Time Shot 1 0 to 655 35 s 0 01 F001 100 6212 Autor...

Page 509: ...set 6448 Negative Sequence Overvoltage Events 0 to 1 1 F102 0 Disabled 6449 Repeated for module number 2 6452 Repeated for module number 3 Power Swing Detect Read Write Grouped Setting 65C0 Power Swin...

Page 510: ...Delay 0 to 600 s 0 01 F001 100 7005 Phase Undervoltage 1 Minimum Voltage 0 to 3 pu 0 001 F001 100 7006 Phase Undervoltage 1 Block 0 to 4294967295 1 F300 0 7008 Phase Undervoltage 1 Target 0 to 2 1 F1...

Page 511: ...1 Reach 0 02 to 500 ohms 0 01 F001 200 7133 Ground Distance Zone 1 Direction 0 to 2 1 F154 0 Forward 7134 Ground Distance Zone 1 Comparator Limit 30 to 90 degrees 1 F001 90 7135 Ground Distance Zone...

Page 512: ...epeated for Phase Directional Overcurrent 2 Neutral Directional Overcurrent Read Write Grouped Setting 2 modules 7230 Neutral Directional Overcurrent 1 Function 0 to 1 1 F102 0 Disabled 7231 Neutral D...

Page 513: ...tting 8 modules 74A0 Disconnect Switch 1 Function 0 to 1 1 F102 0 Disabled 74A1 Disconnect Switch 1 Name F206 SW 1 74A4 Disconnect Switch 1 Mode 0 to 1 1 F157 0 3 Pole 74A5 Disconnect Switch 1 Open 0...

Page 514: ...ammable Pushbutton 1 On Text F202 none 7B75 User Programmable Pushbutton 1 Off Text F202 none 7B7F User Programmable Pushbutton 1 Drop Out Time 0 to 60 s 0 05 F001 0 7B80 User Programmable Pushbutton...

Page 515: ...rvoltage 1 Target 0 to 2 1 F109 0 Self reset 7F69 Auxiliary Undervoltage 1 Events 0 to 1 1 F102 0 Disabled 7F6A Reserved 7 items 0 to 65535 1 F001 0 7F71 Repeated for Auxiliary Undervoltage 2 7F82 Rep...

Page 516: ...08 Repeated for Digital Element 13 8B1E Repeated for Digital Element 14 8B34 Repeated for Digital Element 15 8B4A Repeated for Digital Element 16 8B60 Repeated for Digital Element 17 8B76 Repeated for...

Page 517: ...SIGNED 9008 FlexElement 1 Direction 0 to 1 1 F517 0 OVER 9009 FlexElement 1 Hysteresis 0 1 to 50 0 1 F001 30 900A FlexElement 1 Pickup 90 to 90 pu 0 001 F004 1000 900C FlexElement 1 DeltaT Units 0 to...

Page 518: ...peated for DCmA Output 20 93D8 Repeated for DCmA Output 21 93DE Repeated for DCmA Output 22 93E4 Repeated for DCmA Output 23 93EA Repeated for DCmA Output 24 Direct Input Output Names Read Write Setti...

Page 519: ...nt Actual Values Read Only 8 modules 9000 FlexElement 1 Actual 2147483 647 to 2147483 647 0 001 F004 0 9902 FlexElement 2 Actual 2147483 647 to 2147483 647 0 001 F004 0 9904 FlexElement 3 Actual 21474...

Page 520: ...7 1 F001 7 A282 Selector 1 Timeout 3 to 60 s 0 1 F001 50 A283 Selector 1 Step Up 0 to 4294967295 1 F300 0 A285 Selector 1 Step Mode 0 to 1 1 F083 0 Time out A286 Selector 1 Acknowledge 0 to 4294967295...

Page 521: ...e Latch 12 A790 Repeated for Non Volatile Latch 13 A79C Repeated for Non Volatile Latch 14 A7A8 Repeated for Non Volatile Latch 15 A7B4 Repeated for Non Volatile Latch 16 IEC 61850 Received Analog Set...

Page 522: ...D1 Name Prefix 0 to 65534 1 F206 none AB33 IEC 61850 Logical Node PIOCx Name Prefix 72 items 0 to 65534 1 F206 none AC0B IEC 61850 Logical Node PTOCx Name Prefix 24 items 0 to 65534 1 F206 none AC53 I...

Page 523: ...50 GGIO4 Analog Input 28 AFD4 Repeated for IEC 61850 GGIO4 Analog Input 29 AFDB Repeated for IEC 61850 GGIO4 Analog Input 30 AFE2 Repeated for IEC 61850 GGIO4 Analog Input 31 AFE9 Repeated for IEC 618...

Page 524: ...1 0 001 to 100 0 001 F003 10000 B0E6 IEC 61850 MMXU VAr phsB Deadband 1 0 001 to 100 0 001 F003 10000 B0E8 IEC 61850 MMXU VAr phsC Deadband 1 0 001 to 100 0 001 F003 10000 B0EA IEC 61850 MMXU VA phsA...

Page 525: ...odule number 12 B394 Repeated for module number 13 B397 Repeated for module number 14 B39A Repeated for module number 15 B39D Repeated for module number 16 B3A0 Repeated for module number 17 B3A3 Repe...

Page 526: ...Repeated for module number 13 BAA0 Repeated for module number 14 BAC0 Repeated for module number 15 BAE0 Repeated for module number 16 Contact Inputs Read Write Setting 96 modules BB00 Contact Input...

Page 527: ...ted for Contact Input 49 BC88 Repeated for Contact Input 50 BC90 Repeated for Contact Input 51 BC98 Repeated for Contact Input 52 BCA0 Repeated for Contact Input 53 BCA8 Repeated for Contact Input 54...

Page 528: ...1 Programmed Type 0 to 1 1 F127 0 Latched BE38 Virtual Input 1 Events 0 to 1 1 F102 0 Disabled BE39 Reserved 3 items F001 0 BE3C Repeated for Virtual Input 2 BE48 Repeated for Virtual Input 3 BE54 Re...

Page 529: ...Input 54 C0B8 Repeated for Virtual Input 55 C0C4 Repeated for Virtual Input 56 C0D0 Repeated for Virtual Input 57 C0DC Repeated for Virtual Input 58 C0E8 Repeated for Virtual Input 59 C0F4 Repeated f...

Page 530: ...for Virtual Output 41 C278 Repeated for Virtual Output 42 C280 Repeated for Virtual Output 43 C288 Repeated for Virtual Output 44 C290 Repeated for Virtual Output 45 C298 Repeated for Virtual Output...

Page 531: ...FD and LED 0 to 1 1 F126 0 No C432 Test Mode Initiate 0 to 4294967295 1 F300 1 Clear Commands Read Write C434 Clear All Relay Records Command 0 to 1 1 F126 0 No Mandatory Read Only C435 DSP Advanced D...

Page 532: ...ng 7 modules C760 Control Pushbutton 1 Function 0 to 1 1 F102 0 Disabled C761 Control Pushbutton 1 Events 0 to 1 1 F102 0 Disabled C762 Repeated for Control Pushbutton 2 C764 Repeated for Control Push...

Page 533: ...0 Direct Input Output Channel 1 CRC Alarm Function 0 to 1 1 F102 0 Disabled CAD1 Direct Input Output Channel 1 CRC Alarm Message Count 100 to 10000 1 F001 600 CAD2 Direct Input Output Channel 1 CRC Al...

Page 534: ...4 CD06 Repeated for Device 15 CD2B Repeated for Device 16 Remote Inputs Read Write Setting 32 modules CFA0 Remote Input 1 Device 1 to 32 1 F001 1 CFA1 Remote Input 1 Bit Pair 0 to 96 1 F156 0 None CFA...

Page 535: ...emote Output 14 D258 Repeated for Remote Output 15 D25C Repeated for Remote Output 16 D260 Repeated for Remote Output 17 D264 Repeated for Remote Output 18 D268 Repeated for Remote Output 19 D26C Repe...

Page 536: ...2 1 F001 1 D326 IEC 61850 GGIO2 CF SPCSO7 ctlModel Value 0 to 2 1 F001 1 D327 IEC 61850 GGIO2 CF SPCSO8 ctlModel Value 0 to 2 1 F001 1 D328 IEC 61850 GGIO2 CF SPCSO9 ctlModel Value 0 to 2 1 F001 1 D3...

Page 537: ...GIO2 CF SPCSO51 ctlModel Value 0 to 2 1 F001 1 D353 IEC 61850 GGIO2 CF SPCSO52 ctlModel Value 0 to 2 1 F001 1 D354 IEC 61850 GGIO2 CF SPCSO53 ctlModel Value 0 to 2 1 F001 1 D355 IEC 61850 GGIO2 CF SPC...

Page 538: ...ntact Output 16 DD80 Repeated for Contact Output 17 DD8F Repeated for Contact Output 18 DD9E Repeated for Contact Output 19 DDAD Repeated for Contact Output 20 DDBC Repeated for Contact Output 21 DDCB...

Page 539: ...9 to 9999 999 0 001 F004 4000 E061 DCmA Inputs 1 Maximum Value 9999 999 to 9999 999 0 001 F004 20000 E063 Repeated for DCmA Inputs 2 E076 Repeated for DCmA Inputs 3 E089 Repeated for DCmA Inputs 4 E09...

Page 540: ...Minimum Voltage 0 to 1 25 pu 0 01 F001 70 EC0B Synchrocheck 1 Live V2 Minimum Voltage 0 to 1 25 pu 0 01 F001 70 EC0C Synchrocheck 1 Target 0 to 2 1 F109 0 Self reset EC0D Synchrocheck 1 Events 0 to 1...

Page 541: ...s indicate leading F050 UR_UINT32 TIME and DATE UNSIGNED 32 BIT INTEGER Gives the current time in seconds elapsed since 00 00 00 January 1 1970 F051 UR_UINT32 DATE in SR format alternate format for F0...

Page 542: ...hort Inv 15 FlexCurve C 7 IAC Ext Inv 16 FlexCurve D 8 IAC Very Inv Bitmask Value Bitmask Value Bitmask Value 0 300 4 9600 8 115200 1 1200 5 19200 9 14400 2 2400 6 38400 10 28800 3 4800 7 57600 11 336...

Page 543: ...equence Overvoltage 3 140 Auxiliary Undervoltage 1 141 Auxiliary Undervoltage 2 142 Auxiliary Undervoltage 3 144 Phase Undervoltage 1 145 Phase Undervoltage 2 146 Phase Undervoltage 3 148 Auxiliary Ov...

Page 544: ...t 22 714 Digital Element 23 715 Digital Element 24 716 Digital Element 25 717 Digital Element 26 718 Digital Element 27 719 Digital Element 28 720 Digital Element 29 721 Digital Element 30 722 Digital...

Page 545: ...5 894 RTD Input 46 895 RTD Input 47 896 RTD Input 48 900 User Programmable Pushbutton 1 901 User Programmable Pushbutton 2 902 User Programmable Pushbutton 3 903 User Programmable Pushbutton 4 904 Use...

Page 546: ...odule Failure 05 79 Module Failure 06 80 Module Failure 07 81 Module Failure 08 82 Module Failure 09 83 Incompatible H W 84 Module Failure 10 85 Module Failure 11 86 Module Failure 12 87 High ENET Tra...

Page 547: ...G 9 ACG 4 AB 10 ABC 5 BC 11 ABCG Bitmask Type Bitmask Type Bitmask Type 0 None 5 Dy9 10 Yd7 1 Dy1 6 Dy11 11 Yd9 2 Dy3 7 Yd1 12 Yd11 3 Dy5 8 Yd3 4 Dy7 9 Yd5 Bitmask Value Bitmask Value 0 None 35 UserSt...

Page 548: ...ORMS F184 ENUMERATION IEC GOOSE DATASET F186 ENUMERATION MEASUREMENT MODE 0 Phase to Ground 1 Phase to Phase Bitmask Slot Bitmask Slot Bitmask Slot Bitmask Slot 0 F 4 K 8 P 12 U 1 G 5 L 9 R 13 V 2 H 6...

Page 549: ...ted V0 1 Measured VX F232 ENUMERATION CONFIGURABLE GOOSE Tx DATASET ITEMS Bitmask Keypress Bitmask Keypress 0 No key use between real keys 23 Reset 24 User 1 1 1 25 User 2 2 2 26 User 3 3 3 27 User pr...

Page 550: ...ng f 307 MMXU2 MX PhV phsB cVal mag f 308 MMXU2 MX PhV phsB cVal ang f 309 MMXU2 MX PhV phsC cVal mag f Value IEC 61850 Tx dataset item 310 MMXU2 MX PhV phsC cVal ang f 311 MMXU2 MX A phsA cVal mag f...

Page 551: ...3 MMXU5 MX PPV phsBC cVal ang f 414 MMXU5 MX PPV phsCA cVal mag f 415 MMXU5 MX PPV phsCA cVal ang f Value IEC 61850 Tx dataset item 416 MMXU5 MX PhV phsA cVal mag f 417 MMXU5 MX PhV phsA cVal ang f 41...

Page 552: ...511 GGIO5 ST UIntIn1 q 512 GGIO5 ST UIntIn1 stVal 513 GGIO5 ST UIntIn2 q 514 GGIO5 ST UIntIn2 stVal 515 GGIO5 ST UIntIn3 q 516 GGIO5 ST UIntIn3 stVal 517 GGIO5 ST UIntIn4 q 518 GGIO5 ST UIntIn4 stVal...

Page 553: ...os4 stVal 165 GGIO3 ST IndPos5 stVal 166 GGIO3 ST UIntIn1 q 167 GGIO3 ST UIntIn1 stVal 168 GGIO3 ST UIntIn2 q 169 GGIO3 ST UIntIn2 stVal 170 GGIO3 ST UIntIn3 q 171 GGIO3 ST UIntIn3 stVal 172 GGIO3 ST...

Page 554: ...e Function 0 Disabled 1 Isolated 2 Forcible Value Description 0 5 5V 1 1 1mA 2 0 1mA 3 0 1mA 4 0 5mA 5 0 10mA 6 0 20mA 7 4 20mA 8 potentiometer 9 tap position Value Description 0 None 1 U1 AC1 3 2 U1...

Page 555: ...OR 2 to 16 inputs 42 AND 2 to 16 inputs 44 NOR 2 to 16 inputs 46 NAND 2 to 16 inputs 48 TIMER 1 to 32 50 ASSIGN VIRTUAL OUTPUT 1 to 64 52 ONE SHOT 54 SELF TEST ERROR see F141 for range 56 PLATFORM DI...

Page 556: ...FAULT VARIATION F530 ENUMERATION FRONT PANEL INTERFACE KEYPRESS F531 ENUMERATION LANGUAGE 0 English 1 French 2 Chinese 3 Russian 4 Turkish F600 UR_UINT16 FLEXANALOG PARAMETER Corresponds to the Modbus...

Page 557: ...rt dataset items 0 None 1 PDIF1 ST Str general 2 PDIF1 ST Op general 3 PDIF2 ST Str general 4 PDIF2 ST Op general 5 PDIF3 ST Str general 6 PDIF3 ST Op general 7 PDIF4 ST Str general 8 PDIF4 ST Op gene...

Page 558: ...9 PIOC36 ST Str general 100 PIOC36 ST Op general 101 PIOC37 ST Str general Enumeration IEC 61850 report dataset items 102 PIOC37 ST Op general 103 PIOC38 ST Str general 104 PIOC38 ST Op general 105 PI...

Page 559: ...tr general 204 PTOC16 ST Op general 205 PTOC17 ST Str general 206 PTOC17 ST Op general 207 PTOC18 ST Str general Enumeration IEC 61850 report dataset items 208 PTOC18 ST Op general 209 PTOC19 ST Str g...

Page 560: ...eneral 310 RBRF16 ST OpIn general 311 RBRF17 ST OpEx general 312 RBRF17 ST OpIn general 313 RBRF18 ST OpEx general Enumeration IEC 61850 report dataset items 314 RBRF18 ST OpIn general 315 RBRF19 ST O...

Page 561: ...417 GGIO1 ST Ind11 stVal 418 GGIO1 ST Ind12 stVal 419 GGIO1 ST Ind13 stVal Enumeration IEC 61850 report dataset items 420 GGIO1 ST Ind14 stVal 421 GGIO1 ST Ind15 stVal 422 GGIO1 ST Ind16 stVal 423 GGI...

Page 562: ...850 report dataset items 526 GGIO1 ST Ind120 stVal 527 GGIO1 ST Ind121 stVal 528 GGIO1 ST Ind122 stVal 529 GGIO1 ST Ind123 stVal 530 GGIO1 ST Ind124 stVal 531 GGIO1 ST Ind125 stVal 532 GGIO1 ST Ind126...

Page 563: ...A phsB cVal mag f 629 MMXU3 MX A phsB cVal ang f 630 MMXU3 MX A phsC cVal mag f 631 MMXU3 MX A phsC cVal ang f Enumeration IEC 61850 report dataset items 632 MMXU3 MX A neut cVal mag f 633 MMXU3 MX A...

Page 564: ...32 MMXU6 MX PhV phsA cVal ang f 733 MMXU6 MX PhV phsB cVal mag f 734 MMXU6 MX PhV phsB cVal ang f 735 MMXU6 MX PhV phsC cVal mag f 736 MMXU6 MX PhV phsC cVal ang f 737 MMXU6 MX A phsA cVal mag f Enume...

Page 565: ...ST Pos stVal 835 XSWI24 ST Loc stVal 836 XSWI24 ST Pos stVal 837 XCBR1 ST Loc stVal 838 XCBR1 ST Pos stVal 839 XCBR2 ST Loc stVal 840 XCBR2 ST Pos stVal 841 XCBR3 ST Loc stVal 842 XCBR3 ST Pos stVal 8...

Page 566: ...GIO1 ST Ind46 stVal 93 GGIO1 ST Ind47 q 94 GGIO1 ST Ind47 stVal 95 GGIO1 ST Ind48 q Enumeration GOOSE dataset items 96 GGIO1 ST Ind48 stVal 97 GGIO1 ST Ind49 q 98 GGIO1 ST Ind49 stVal 99 GGIO1 ST Ind5...

Page 567: ...T Ind99 stVal 199 GGIO1 ST Ind100 q 200 GGIO1 ST Ind100 stVal 201 GGIO1 ST Ind101 q Enumeration GOOSE dataset items 202 GGIO1 ST Ind101 stVal 203 GGIO1 ST Ind102 q 204 GGIO1 ST Ind102 stVal 205 GGIO1...

Page 568: ...MXU2 MX PhV phsA cVal mag f 306 MMXU2 MX PhV phsA cVal ang f 307 MMXU2 MX PhV phsB cVal mag f Enumeration GOOSE dataset items 308 MMXU2 MX PhV phsB cVal ang f 309 MMXU2 MX PhV phsC cVal mag f 310 MMXU...

Page 569: ...U5 MX PPV phsAB cVal ang f 412 MMXU5 MX PPV phsBC cVal mag f 413 MMXU5 MX PPV phsBC cVal ang f Enumeration GOOSE dataset items 414 MMXU5 MX PPV phsCA cVal mag f 415 MMXU5 MX PPV phsCA cVal ang f 416 M...

Page 570: ...T UIntIn2 q 514 GGIO5 ST UIntIn2 stVal 515 GGIO5 ST UIntIn3 q 516 GGIO5 ST UIntIn3 stVal 517 GGIO5 ST UIntIn4 q 518 GGIO5 ST UIntIn4 stVal 519 GGIO5 ST UIntIn5 q Enumeration GOOSE dataset items 520 GG...

Page 571: ...622 PIOC26 ST Op general 623 PIOC27 ST Str general 624 PIOC27 ST Op general 625 PIOC28 ST Str general Enumeration GOOSE dataset items 626 PIOC28 ST Op general 627 PIOC29 ST Str general 628 PIOC29 ST...

Page 572: ...ST Str general 728 PTOC7 ST Op general 729 PTOC8 ST Str general 730 PTOC8 ST Op general 731 PTOC9 ST Str general Enumeration GOOSE dataset items 732 PTOC9 ST Op general 733 PTOC10 ST Str general 734...

Page 573: ...T OpEx general 836 RBRF8 ST OpIn general 837 RBRF9 ST OpEx general Enumeration GOOSE dataset items 838 RBRF9 ST OpIn general 839 RBRF10 ST OpEx general 840 RBRF10 ST OpIn general 841 RBRF11 ST OpEx ge...

Page 574: ...26 ST Loc stVal 940 CSWI26 ST Pos stVal 941 CSWI27 ST Loc stVal 942 CSWI27 ST Pos stVal 943 CSWI28 ST Loc stVal Enumeration GOOSE dataset items 944 CSWI28 ST Pos stVal 945 CSWI29 ST Loc stVal 946 CSWI...

Page 575: ...998 XCBR1 ST Pos stVal 999 XCBR2 ST Loc stVal 1000 XCBR2 ST Pos stVal 1001 XCBR3 ST Loc stVal 1002 XCBR3 ST Pos stVal 1003 XCBR4 ST Loc stVal 1004 XCBR4 ST Pos stVal 1005 XCBR5 ST Loc stVal 1006 XCBR5...

Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...

Page 577: ...d that all those involved with any IEC 61850 implementation obtain this document set C 1 2 COMMUNICATION PROFILES IEC 61850 specifies the use of the Manufacturing Message Specification MMS at the uppe...

Page 578: ...plorer window click the Tools menu and access the SISCO File Transfer Utility 2 Select the Remote AR Name from the drop down list Available files appear in the File Specification area on the right sid...

Page 579: ...used for SOE logs since the buffering capability reduces the chances of missing data state changes Unbuffered reporting should generally be used for local status display C 2 3 GGIO2 DIGITAL CONTROL V...

Page 580: ...tor MMXU1 MX Hz frequency MMXU1 MX PPV phsAB phase AB voltage magnitude and angle MMXU1 MX PPV phsBC phase BC voltage magnitude and angle MMXU1 MX PPV phsCA Phase CA voltage magnitude and angle MMXU1...

Page 581: ...t locator function The XCBR logical node is directly associated with the breaker control feature XCBR1 ST Loc This is the state of the XCBR1 local remote switch A setting is provided to assign a FlexL...

Page 582: ...me of the last change of either the value or quality flags of the data item To accomplish this functionality all IEC 61850 data items must be regularly scanned for data changes and the timestamp updat...

Page 583: ...nection for greater than two minutes the connection will be aborted by the D30 This frees up the con nection to be used by other clients Therefore when using IEC 61850 reporting clients should configu...

Page 584: ...n two pre defined data structures named DNA and UserSt Each DNA and UserSt item is referred to as a bit pair GSSE messages are transmit ted in response to state changes in any of the data points conta...

Page 585: ...ed for applications that require GOOSE data transfer between UR series IEDs and devices from other manufacturers Fixed GOOSE is recommended for applications that require GOOSE data transfer between UR...

Page 586: ...UNICATION IEC 61850 PROTOCOL GSSE GOOSE CONFIGURATION RECEPTION CONFIGURABLE GOOSE CONFIGURABLE GOOSE 1 CONFIG GSE 1 DATASET ITEMS settings menu Set ITEM 1 to GGIO3 ST Ind1 q to indicate quality flags...

Page 587: ...configured to use an automated multicast MAC scheme If the D30 destination MAC address setting is not a valid multicast address that is the least significant bit of the first byte is not set the addre...

Page 588: ...uration process for IEC 61850 BDA Basic Data Attribute that is not structured DAI Instantiated Data Attribute DO Data Object type or instance depending on the context 842790A2 CDR Ethernet System conf...

Page 589: ...le SCD to set communication configuration parame ters that is required addresses reception GOOSE datasets IDs of incoming GOOSE datasets etc for the IED The IED configurator functionality is implement...

Page 590: ...rators we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD and strictly within EnerVista UR Setup software or the front panel display access through the Settings P...

Page 591: ...ress node contains the address parameters of the access point The GSE node provides the address element for stat ing the control block related address parameters where IdInst is the instance identific...

Page 592: ...DataSet name Other DataSet elements FCDA fc doName daName IdInst prefix InClass InInst Other FCDA elements DOI name SDI name Val Text Other DOI elements GSEControl name datSet type confRev appID LN I...

Page 593: ...SDO The attribute DA has a func tional constraint and can either have a basic type be an enumeration or a structure of a DAType The DAType is built from BDA elements defining the structure elements w...

Page 594: ...e procedure is pretty much the same First a substation project must be created either as an empty template or with some system information by importing a system specification file SSD Then IEDs are ad...

Page 595: ...file and its version and specifies options for the mapping of names to signals The Substation node describes the substation parameters Figure C 7 SCD FILE STRUCTURE SUBSTATION NODE 842791A1 CDR SCL H...

Page 596: ...nectedAP node describes the IED access point connected to this sub network The Address node contains the address parameters of the access point The GSE node provides the address element for stat ing t...

Page 597: ...pdate the D30 with the new configuration from an SCD file with the EnerVista UR Setup software 1 Right click anywhere in the files panel and select the Import Contents From SCD File item 2 Select the...

Page 598: ...n one GE Multilin IED defined in the SCD file the software prompt the user to save a UR series set tings file for each IED 4 After the URS file is created modify any settings if required 5 To update t...

Page 599: ...SCSM IEC 61850 9 2 used B24 SCSM other GENERIC SUBSTATION EVENT MODEL GSE B31 Publisher side O Yes B32 Subscriber side Yes TRANSMISSION OF SAMPLED VALUE MODEL SVC B41 Publisher side O B42 Subscriber...

Page 600: ...set name M8 5 data reference M8 6 BufTm M8 7 IntgPd M8 8 GI Logging O M9 Log control O M9 1 IntgPd M10 Log O M11 Control M Yes IF GSE B31 32 IS SUPPORTED GOOSE O Yes M12 1 entryID M12 2 DataReflnc M13...

Page 601: ...Yes S26 SetBRCBValues TP c6 Yes UNBUFFERED REPORT CONTROL BLOCK URCB S27 Report TP c6 Yes S27 1 data change dchg Yes S27 2 qchg change qchg S27 3 data update dupd S28 GetURCBValues TP c6 Yes S29 SetUR...

Page 602: ...SendMSVMessage MC c10 S46 GetMSVCBValues TP O S47 SetMSVCBValues TP O UNICAST SVC S48 SendUSVMessage MC c10 S49 GetUSVCBValues TP O S50 SetUSVCBValues TP O CONTROL CLAUSE 20 S51 Select O Yes S52 Selec...

Page 603: ...king A LOGICAL NODES FOR AUTOMATIC CONTROL ANCR Neutral current regulator ARCO Reactive power control ATCC Automatic tap changer controller AVCO Voltage control C LOGICAL NODES FOR CONTROL CALH Alarm...

Page 604: ...es MSQI Sequence and imbalance Yes MSTA Metering statistics P LOGICAL NODES FOR PROTECTION FUNCTIONS PDIF Differential Yes PDIR Direction comparison PDIS Distance Yes PDOP Directional overpower PDUP D...

Page 605: ...ferential measurements RPSB Power swing detection blocking Yes RREC Autoreclosing Yes RSYN Synchronism check or synchronizing S LOGICAL NODES FOR SENSORS AND MONITORING SARC Monitoring and diagnostics...

Page 606: ...arth fault neutralizer Petersen coil YLTC Tap changer YPSH Power shunt YPTR Power transformer Z LOGICAL NODES FOR FURTHER POWER SYSTEM EQUIPMENT ZAXN Auxiliary network ZBAT Battery ZBSH Bushing ZCAB P...

Page 607: ...change Circuit V 24 V 28 Recommended if 1200 bits s Balanced Interchange Circuit X 24 X 27 100 bits sec 200 bits sec 300 bits sec 600 bits sec 1200 bits sec 2400 bits sec 4800 bits sec 9600 bits sec 2...

Page 608: ...indicate the following used in standard direction not used cannot be selected in IEC 60870 5 104 standard Process information in monitor direction 1 Single point information M_SP_NA_1 2 Single point i...

Page 609: ...ents of protection equipment with time tag CP56Time2a M_EP_TE_1 40 Packed output circuit information of protection equipment with time tag CP56Time2a M_EP_TF_1 45 Single command C_SC_NA_1 46 Double co...

Page 610: ...all directory select file call file call section F_SC_NA_1 123 Last section last segment F_LS_NA_1 124 Ack file ack section F_AF_NA_1 125 Segment F_SG_NA_1 126 Directory blank or X available only in m...

Page 611: ...RC_NA_1 48 C_SE_NA_1 49 C_SE_NB_1 50 C_SE_NC_1 51 C_BO_NA_1 58 C_SC_TA_1 X X X X X 59 C_DC_TA_1 60 C_RC_TA_1 TYPE IDENTIFICATION CAUSE OF TRANSMISSION NO MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 20 to 3...

Page 612: ..._1 112 P_ME_NC_1 X X X 113 P_AC_NA_1 120 F_FR_NA_1 121 F_SR_NA_1 122 F_SC_NA_1 123 F_LS_NA_1 124 F_AF_NA_1 125 F_SG_NA_1 126 F_DR_TA_1 TYPE IDENTIFICATION CAUSE OF TRANSMISSION NO MNEMONIC 1 2 3 4 5 6...

Page 613: ...ng point number M_ME_NC_1 M_ME_TC_1 and M_ME_TF_1 Station interrogation Clock synchronization Clock synchronization optional see Clause 7 6 Command transmission Direct command transmission Direct setp...

Page 614: ...equences of events Transmission of sequences of recorded analog values File transfer in control direction Transparent file Background scan Background scan Acquisition of transmission delay Acquisition...

Page 615: ...determined by the Internet Architecture Board IAB It offers a broad spectrum of actual standards used in the Inter net The suitable selection of documents from RFC 2200 defined in this standard for g...

Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...

Page 617: ...ed in addition to the Highest DNP Levels Supported the complete list is described in the attached table Binary Inputs Object 1 Binary Input Changes Object 2 Binary Outputs Object 10 Control Relay Outp...

Page 618: ...Binary Outputs Never Always Sometimes Configurable SELECT OPERATE Never Always Sometimes Configurable DIRECT OPERATE Never Always Sometimes Configurable DIRECT OPERATE NO ACK Never Always Sometimes Co...

Page 619: ...Configurable Only certain objects Sometimes attach explanation ENABLE DISABLE unsolicited Function codes supported Sends Static Data in Unsolicited Responses Never When Device Restarts When Status Fl...

Page 620: ...p 17 28 index 3 Binary Input Change with Relative Time 1 read 06 no range or all 07 08 limited quantity 10 0 Binary Output Status Variation 0 is used to request default variation 1 read 00 01 start st...

Page 621: ...ariation 0 is used to request default variation 1 read 06 no range or all 07 08 limited quantity 1 32 Bit Counter Change Event 1 read 06 no range or all 07 08 limited quantity 129 response 130 unsol r...

Page 622: ...sponse 130 unsol resp 17 28 index 3 32 Bit Analog Change Event with Time 1 read 06 no range or all 07 08 limited quantity 129 response 130 unsol resp 17 28 index 4 16 Bit Analog Change Event with Time...

Page 623: ...close 30 abort 5b free format 129 response 130 unsol resp 5b free format 5 File transfer 1 read 2 write 5b free format 129 response 130 unsol resp 5b free format 6 File transfer status 129 response 1...

Page 624: ...n is performed on a binary counter point the frozen value is available in the corresponding frozen counter point BINARY INPUT POINTS Static Steady State Object Number 1 Change Event Object Number 2 Re...

Page 625: ...rtual Input 15 15 Virtual Input 16 16 Virtual Input 17 17 Virtual Input 18 18 Virtual Input 19 19 Virtual Input 20 20 Virtual Input 21 21 Virtual Input 22 22 Virtual Input 23 23 Virtual Input 24 24 Vi...

Page 626: ...freeze and clear noack 22 assign class Static Variation reported when variation 0 requested 1 32 Bit Binary Counter with Flag Change Event Variation reported when variation 0 requested 1 32 Bit Counte...

Page 627: ...all Analog Input points are in the same units as the Analog Input quantity For example an Analog Input quantity measured in volts has a corresponding deadband in units of volts This is in conformance...

Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...

Page 629: ...ember 2004 URX 156 1601 0116 K1 4 6x 15 February 2005 URX 176 1601 0116 L1 4 8x 05 August 2005 URX 202 1601 0116 M1 4 9x 15 December 2005 URX 208 1601 0116 M2 4 9x 27 February 2006 URX 214 1601 0116 N...

Page 630: ...nger being sold Units with blank LED panels no longer being sold 5 18 5 18 Add Added Syslog Format section 5 26 5 26 Add Added Far End Fault Indication FEFI section 5 102 5 102 Update Updated FlexLogi...

Page 631: ...ed Communication to Real Time Clock in SNTP protocol settings path Moved SNTP Protocol menu and settings descriptions to Real Time Clock subsection 5 37 5 Delete Deleted section k SNTP Protocol and th...

Page 632: ...lin F 1 CHANGE NOTES APPENDIX F F C 23 C 23 Update Updated tables in sections C 6 3 ACSI Services Conformance Statement and C 7 1 Logical Nodes Table Table F 5 MAJOR UPDATES FOR D30 MANUAL REVISION Y1...

Page 633: ...eld FAIL Failure FD Fault Detector FDH Fault Detector high set FDL Fault Detector low set FLA Full Load Current FO Fiber Optic FREQ Frequency FSK Frequency Shift Keying FTP File Transfer Protocol FxE...

Page 634: ...Resistance Temperature Detector RTU Remote Terminal Unit RX Rx Receive Receiver s second S Sensitive SAT CT Saturation SBO Select Before Operate SCADA Supervisory Control and Data Acquisition SEC Seco...

Page 635: ...of 1 October 2013 GE Digital Energy warrants most of its GE manufactured products for 10 years For warranty details including any limitations and disclaimers see the GE Digital Energy Terms and Condit...

Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...

Page 637: ...B 41 settings 5 184 specifications 2 13 AUXILIARY VOLTAGE CHANNEL 3 11 AUXILIARY VOLTAGE METERING 6 16 AWG WIRE SIZE 3 10 3 30 3 33 3 35 B BANKS 5 6 5 81 5 82 BATTERY replace 11 3 BATTERY FAILURE 7 7...

Page 638: ...3 9 CSA APPROVAL 2 21 CT BANKS settings 5 81 CT INPUTS 3 11 5 6 5 81 CT WIRING 3 11 CURRENT BANK 5 81 CURRENT DIFFERENTIAL Modbus registers B 15 CURRENT METERING actual values 6 14 specifications 2 1...

Page 639: ...N 2 21 ELECTROSTATIC DISCHARGE 2 20 ELEMENTS 5 4 END OF LIFE 11 10 ENERVISTA UR SETUP creating a site list 4 1 event recorder 4 2 firmware upgrades 4 2 installation 1 6 introduction 4 1 oscillography...

Page 640: ...s registers B 12 FREQUENCY TRACKING 5 83 6 18 FREQUENCY NOMINAL 5 82 FUNCTION SETTING 5 4 FUSE 2 17 FUSE FAILURE see VT FUSE FAILURE G G 703 3 30 3 31 3 32 3 35 G 703 WIRE SIZE 3 30 GE TYPE IAC CURVES...

Page 641: ...MENT FlexLogic operands 5 104 Modbus registers B 36 settings 5 149 5 150 specifications 2 14 LOCAL SETTING AUTHORIZATION 4 3 LOGIC GATES 5 110 LOGS SYSTEM 5 18 LOST PASSWORD 5 9 M MAINTENANCE battery...

Page 642: ...7 settings 5 121 specifications 2 14 O ONE SHOTS 5 110 OPERATING TEMPERATURE 2 19 OPERATING TIMES 2 10 ORDER CODES 2 3 2 5 2 6 6 23 7 3 ORDER CODES UPDATING 7 3 ORDERING 2 3 2 5 2 6 OSCILLATORY TRANSI...

Page 643: ...registers B 24 PROCESS BUS overview 3 11 PRODUCT INFORMATION 6 23 B 9 PRODUCT SETUP 5 8 5 14 PRODUCTION TESTS 2 20 PROTECTION ELEMENTS 5 4 PU QUANTITY 5 4 PUSHBUTTONS USER PROGRAMMABLE see USER PROGRA...

Page 644: ...racy 2 18 error messages 7 8 Modbus registers B 26 settings 5 50 SOFTWARE installation 1 6 see entry for ENERVISTA UR SETUP SOFTWARE ARCHITECTURE 1 5 SOFTWARE PC see entry for EnerVista UR Setup SOURC...

Page 645: ...68 Modbus registers B 24 B 29 settings 5 68 5 70 specifications 2 14 USER PROGRAMMABLE LEDs defaults 4 18 description 4 16 4 17 Modbus registers B 27 settings 5 58 specifications 2 14 USER PROGRAMMABL...

Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...