5-189
5 SETTINGS
5.7 CONTROL ELEMENTS
5
The
SETTING GROUPS BLK
setting prevents the active setting group from changing when the FlexLogic parameter is set to
"On". This can be useful in applications where it is undesirable to change the settings under certain conditions, such as the
breaker being open.
The
GROUP 2 ACTIVATE ON
to
GROUP 6 ACTIVATE ON
settings select a FlexLogic operand which, when set, will make the par-
ticular setting group active for use by any grouped element. A priority scheme ensures that only one group is active at a
given time – the highest-numbered group which is activated by its
ACTIVATE ON
parameter takes priority over the lower-
numbered groups. There is no activate on setting for group 1 (the default active group), because group 1 automatically
becomes active if no other group is active.
The
SETTING GROUP 1 NAME
to
SETTING GROUP 6 NAME
settings allows to user to assign a name to each of the six settings
groups. Once programmed, this name will appear on the second line of the
GROUPED ELEMENTS
SETTING GROUP 1(6)
menu display.
The relay can be set up via a FlexLogic equation to receive requests to activate or de-activate a particular non-default set-
tings group. The following FlexLogic equation (see the figure below) illustrates requests via remote communications (for
example,
VIRTUAL INPUT 1 ON
) or from a local contact input (for example,
CONTACT IP 1 ON
) to initiate the use of a particu-
lar settings group, and requests from several overcurrent pickup measuring elements to inhibit the use of the particular set-
tings group. The assigned
VIRTUAL OUTPUT 1
operand is used to control the “On” state of a particular settings group.
Figure 5–100: EXAMPLE FLEXLOGIC CONTROL OF A SETTINGS GROUP
10
1
VIRT IP 1 ON (VI1)
2
CONT IP 1 ON (H5A)
3
OR (2)
OR (2)
4
PHASE TOC1 PKP
5
NOT
6
PHASE TOC2 PKP
7
NOT
8
AND (3)
AND (3)
9
= VIRT OP 1 (VO1)
= VIRT OP 1 (VO1)
END
842789A1.CDR
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...