5-200
D30 Line Distance Protection System
GE Multilin
5.7 CONTROL ELEMENTS
5 SETTINGS
5
5.7.6 AUTORECLOSE
PATH: SETTINGS
CONTROL ELEMENTS
AUTORECLOSE
AUTORECLOSE 1
AUTORECLOSE 1
AR1 FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
AR1 INITIATE:
Off
Range: FlexLogic operand
MESSAGE
AR1 BLOCK:
Off
Range: FlexLogic operand
MESSAGE
AR1 MAX NUMBER OF
SHOTS: 1
Range: 1, 2, 3, 4
MESSAGE
AR1 REDUCE MAX TO 1:
Off
Range: FlexLogic operand
MESSAGE
AR1 REDUCE MAX TO 2:
Off
Range: FlexLogic operand
MESSAGE
AR1 REDUCE MAX TO 3:
Off
Range: FlexLogic operand
MESSAGE
AR1 MANUAL CLOSE:
Off
Range: FlexLogic operand
MESSAGE
AR1 MNL RST FRM LO:
Off
Range: FlexLogic operand
MESSAGE
AR1 RESET LOCKOUT IF
BREAKER CLOSED: Off
Range: Off, On
MESSAGE
AR1 RESET LOCKOUT ON
MANUAL CLOSE: Off
Range: Off, On
MESSAGE
AR1 BKR CLOSED:
Off
Range: FlexLogic operand
MESSAGE
AR1 BKR OPEN:
Off
Range: FlexLogic operand
MESSAGE
AR1 BLK TIME UPON
MNL CLS: 10.000 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR1 DEAD TIME 1:
1.000 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR1 DEAD TIME 2:
2.000 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR1 DEAD TIME 3:
3.000 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR1 DEAD TIME 4:
4.000 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR1 ADD DELAY 1:
Off
Range: FlexLogic operand
MESSAGE
AR1 DELAY 1:
0.000 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR1 ADD DELAY 2:
Off
Range: FlexLogic operand
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...