CHAPTER 6: COMMUNICATIONS
NETWORK SETTINGS
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
97
Figure 77: HTTP configuration settings
The following settings are available.
HTTP TCP Port Number
Range: 1 to 65535 in steps of 1
Default: 80
This setting specifies the TCP port number for the embedded web server. This setting will
take affect once the D90
Plus
is rebooted.
Web Server Function
Range: Disabled, Enabled
Default: Disabled
This setting enables and disabled the web server feature.
Network filtering
Select the
Settings > Communications > Network > Filtering
menu item to open the
network filtering configuration window.
Figure 78: Network filtering configuration settings
The following settings are available.
Port 1 Bandwidth Limitation
Range: Disabled, Enabled
Default: Disabled
This setting is used to enable IP protocol bandwidth limiting on Ethernet port 1. The
COMM HIGH TRAFFIC self-test message is issued when the D90
Plus
is actively limiting IP
bandwidth usage. This is a minor self-test error that does not interfere with protection
functionality.
Port 2 and 3 Bandwidth Limitation
Range: Disabled, Enabled
Default: Disabled
This setting is used to enable IP protocol bandwidth limiting on Ethernet ports 2 and 3.
The COMM HIGH TRAFFIC self-test message is issued when the D90
Plus
is actively limiting
IP bandwidth usage. This is a minor self-test error that does not interfere with protection
functionality. IP bandwidth limiting of Ethernet ports 2 and 3 does not affect GOOSE
messaging.