104
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
DNP COMMUNICATIONS
CHAPTER 6: COMMUNICATIONS
DNP Client Address 1, DNP Client Address 2,..., DNP Client Address 5
Range: any standard IP address
Default: 0.0.0.0
These settings force the D90
Plus
to respond to a maximum of five specific DNP masters.
DNP TCP/UDP Port Number
Range: 1 to 65535 in steps of 1
Default: 20000
This setting specifies the TCP/UDP port used for DNP communications.
DNP Unsolicited Response Function
Range: Enabled, Disabled
Default: Disabled
Program this setting to “Disabled” for RS485 applications, since there is no collision
avoidance mechanism.
DNP Unsolicited Response Timeout
Range: 0 to 60 seconds in steps of 1
Default: 5 seconds
This setting specifies how long the D90
Plus
waits for a DNP master to confirm an
unsolicited response.
DNP Unsolicited Response Maximum Re-Tries
Range: 1 to 255 in steps of 1
Default: 10
This setting specifies the number of times the D90
Plus
retransmits an unsolicited
response without receiving confirmation from the master. A value of “255” allows infinite
re-tries.
DNP Unsolicited Response Destination Address
Range: 0 to 65519 in steps of 1
Default: 1
This setting specifies the DNP address to which all unsolicited responses are sent. The IP
address to which unsolicited responses are sent is determined by the D90
Plus
from the
current TCP connection or the most recent UDP message.
DNP Current Scale Factor, DNP Voltage Scale Factor, DNP Power Scale Factor, DNP
Power Factor Scale Factor, DNP Other Scale Factor
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000, 100000
Default: 1
These settings scale the analog input current values. For example, if the
DNP Current
Scale Factor
is “10”, all DNP analog input points that represent currents will be returned
with values 10 times smaller (for example, a value of 700 amps on the D90
Plus
will be
returned as 70). Likewise, if the
DNP Voltage Scale Factor
is “0.01”, all DNP analog input
points that represent voltages will be returned with values 100 times larger (for example,
a value of 17 volts on the D90
Plus
will be returned as 1700).
These settings are useful when analog input values must be adjusted to fit within certain
ranges in DNP masters.
DNP Current Default Deadband, DNP Voltage Default Deadband, DNP Power Default
Deadband, DNP Power Factor Default Deadband, DNP Other Default Deadband
Range: 0 to 100000000 in steps of 1
Default: 30000
These settings determine when to trigger unsolicited responses containing analog Input
data. These settings group the D90
Plus
analog input data into types: current, voltage,
power, energy, and other. Each setting represents the default deadband value for all