112
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
IEC 61850 COMMUNICATIONS
CHAPTER 6: COMMUNICATIONS
Destination MAC
Range: standard MAC address format
Default: 00 00 00 00 00 00
This setting specifies the destination Ethernet MAC address for the fixed GOOSE
transmission. This address must be a multicast address and the least significant bit of
the first byte must be set.
If this setting is specified as “00 00 00 00 00 00” (the default value), then a multicast MAC
address is formed based on the MAC address of Ethernet ports 2 and 3. The MAC address
of Ethernet port 2 is the MAC address of Ethernet port 1 incremented by 1. Likewise, the
MAC address of Ethernet port 3 is the MAC address of Ethernet port 1 incremented by 2.
GOOSE VLAN Priority
Range: 0 to 7 in steps of 1
Default: 4
This setting indicates the Ethernet priority of GOOSE messages. This allows GOOSE
messages to have higher priority than other Ethernet data. This setting is required by IEC
61850.
GOOSE VLAN ID
Range: 0 to 4096 in steps of 1
Default: 0
This setting allows the selection of a specific VLAN ID for each GOOSE sending device.
This value can be left at its default if the feature is not required.
GOOSE ETYPE APPID
Range: 0 to 16383 in steps of 1
Default: 0
This setting allows the selection of a specific application ID for each GOOSE sending
device. This value can be left at its default if the feature is not required. This setting is
required by IEC 61850.
GOOSE Minimum Time to Live
Range: 50 to 4000 ms in steps of 1
Default: 400 ms
This setting specifies the minimum time to live for the GOOSE transmission data set.
Configurable GOOSE transmission
The configurable GOOSE settings allow the D90
Plus
to be configured to transmit a number
of different datasets within IEC 61850 GOOSE messages. Up to eight different configurable
datasets can be configured and transmitted, allowing for the optimization of data transfer
between devices. This is useful for intercommunication between D90
Plus
IEDs and devices
from other manufacturers that support IEC 61850.
Items programmed for datasets 1 through 8 will have changes in their status transmitted
once per protection pass for digital data and every 250 ms for analog data.
The integrity GOOSE message is sent at the pre-configured rate for all datasets, even if no
changes in the data items are detected.
The configurable GOOSE feature is recommended for applications that require GOOSE
data transfer between UR
Plus
-series IEDs and devices from other manufacturers. Fixed
GOOSE is recommended for applications that require GSSE data transfer between UR
Plus
-
series IEDs. IEC 61850 GOOSE messaging contains a number of configurable parameters,
all of which must be correct for successful data transfer. It is critical that the configured
datasets at the transmission and reception devices are an exact match in terms of data
structure, and that the GOOSE addresses and name strings match exactly. Manual