122
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
IEC 61850 COMMUNICATIONS
CHAPTER 6: COMMUNICATIONS
IEC 61850 GOOSE analog inputs
The IEC 61850 GOOSE analog inputs feature allows the transmission of analog values
between any two UR
Plus
-series devices.
Select the
Settings > Communications > IEC 61850 > GSSE/GOOSE Configuration >
Inputs/Outputs > IEC 61850 GOOSE Analog Inputs
menu item to open the IEC 61850
GOOSE analog inputs configuration window.
Figure 99: IEC 61850 GOOSE analog inputs configuration settings
The following settings are available for each of the 128 IEC 61850 GOOSE analog inputs.
Default Value
Range: –1000000.000 to 1000000.000 in steps of 0.001
Default: 1000.000
This setting specifies the value of the GOOSE analog input when the sending device is
offline and the
Default Mode
setting is set to “Default Value”. This setting is stored as an
IEEE 754 / IEC 60559 floating point number. Because of the large range of this setting,
not all possible values can be stored. Some values may be rounded to the closest
possible floating point number.
Mode
Range: Default Value, Last Known
Default: Default Value
When the sending device is offline and this setting is “Last Known”, the value of the
GOOSE analog input remains at the last received value. When the sending device is
offline and this setting value is “Default Value”, then the value of the GOOSE analog input
is defined by the
Default Value
setting.
Units
Range: up to 4 alphanumeric characters
Default: ---
This setting specifies a four-character alphanumeric string that is used in the actual
values display of the corresponding GOOSE analog input value.
PU Base
Range: 0 to 1000000000 in steps of 1
Default: 1
This setting specifies the per-unit base factor when using the GOOSE analog input
FlexAnalog™ values in other D90
Plus
features, such as protection FlexElements™. The
base factor is applied to the GOOSE analog input FlexAnalog quantity to normalize it to a
per-unit quantity. The base units are described in the following table.