LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
FLEXSTATES
CHAPTER 6: COMMUNICATIONS
Name
Range: up to 65 alphanumeric characters
This value displays the name programmed for the corresponding remote device.
StNum
Range: 0 to 4294967295 in steps of 1
This value is obtained from the indicated remote device and is incremented whenever a
change of state of at least one DNA or UserSt bit occurs.
SqNum
Range: 0 to 4294967295 in steps of 1
This value is obtained from the indicated remote device and is incremented whenever a
GSSE message is sent. This number will rollover to zero when a count of 4294967295 is
incremented.
IEC 61850 GOOSE analog input actual values
Select the
Actual Values > Communications > Inputs/Outputs > IEC61850 GOOSE
Analog Inputs
menu item to open the IEC 61850 GOOSE analog input actual values
window.
Figure 113: IEC 61850 GOOSE analog input actual values
The following actual value is available for each of the IEC 61850 GOOSE analog inputs.
IEC 61850 GOOSE Analog Input 1 Actual
Range: Yes, No
This value displays the IEC 61850 GGIO3 analog input data point 1. The GGIO3 analog
data values are received via IEC 61850 GOOSE messages sent from other devices.
FlexStates
The FlexStates feature provides a mechanism where any of 256 selected FlexLogic™
operand states can be used for efficient monitoring. The feature allows user-customized
access to the FlexLogic™ operand states in the D90
Plus
. The state bits are packed so that