CHAPTER 9: EQUIPMENT MANAGER
BREAKER MANAGEMENT
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
495
Figure 426: Breaker arcing current measurement
Select the
Settings > Equipment Manager > Breaker > Breaker Arcing
menu item to open
the breaker arcing current configuration window.
Figure 427: Breaker arcing current configuration settings
The following settings are available for each breaker arcing current element.
Function
Range: Enabled, Disabled
Default: Disabled
This settings enables or disables the breaker arcing current function.
Source
Range: LINE (SRC 1), BKR 1 (SRC 2), BKR 2 (SRC 3)
Default: LINE (SRC 1)
This setting selects the signal source for the breaker arcing current element.
Limit
Range: 0 to 50000 kA
2
-cycle in steps of 1
Default: 1000 kA
2
-cycle
This setting specifies the limit of the accumulated current arcing time for maintenance.