CHAPTER 12: LOCAL INTERFACE
ANNUNCIATOR PANEL
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
587
Figure 510: Metering value properties
This dialog box allows the user to configure metering values. The following parameters are
available.
Parameter
Range: any FlexAnalog™ parameter
Default: Digital Counter 1 Value
This setting selects a FlexAnalog™ parameter that specifies the metered value to display
in the annunciator alarm.
Units
Range: up to 4 alphanumeric characters
Default: ---
This setting specifies a four-character alphanumeric string that is used in the
annunciator display of the corresponding metered value.
Scale Factor
Range: None, k (kilo), M (Mega), G (Giga)
Default: None
This setting allows the user to specify the scaling factor for the metering units value.
Multiplier
Range: dependent on selected analog value
Default: 1.0
This setting allows the user to specify a multiplier for the metering parameter value. The
range is restricted to correspond to the selected actual value parameter.
Number of Integers
Range: 1 to 12 in steps of 1
Default: 1
This setting specifies the number of integers in the displayed analog value. It can be
used to provide for leading character spacing of the resultant display value.
Number of Decimals
Range: 1 to 10 in steps of 1
Default: 3
This setting specifies the number of decimal places in the displayed analog value.