CHAPTER 6: COMMUNICATIONS
IEC 61850 COMMUNICATIONS
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
133
SPCSO 1 ctlModel
Range: 0, 1, 2
Default: 1
The GGIO5 control configuration settings are used to set the control model for each
input. The available choices are “0” (status only), “1” (direct control), and “2” (SBO with
normal security).
Unbuffered report control configuration
IEC 61850 unbuffered reporting is provided in the GGIO1 logical nodes (for binary status
values), GGIO4 logical nodes (for analog value points) and MMXU1 to MMXU4 (for analog
measured values). Report settings can be configured using the EnerVista UR
Plus
Setup software, substation configurator software, or via an IEC 61850 client.
Select the
Settings > Communications > IEC 61850 > Unbuffered Report Control
Configuration
menu item to open the IEC 61850 unbuffered report configuration window.
Figure 107: IEC 61850 unbuffered report control configuration
The following settings are available for each unbuffered report. Up to 18 unbuffered
reports can be configured. Changes to the report configuration will not take effect until the
D90
Plus
is restarted.
Unbuffered Reports RptID
Range: up to 65 alphanumeric characters
Default: empty
This setting specifies the name for the IEC 61850 unbuffered report.
Unbuffered Reports OptFlds
Range: 0 to 65535 in steps of 1
Default: 0
This setting specifies a bitmask that selects the option fields. The following bits are
supported by the D90
Plus
.
–
Bit 1: sequence-number.
–
Bit 2: report-time-stamp.
–
Bit 3: reason-for-inclusion.
–
Bit 4: data-set-name.
–
Bit 5: data-reference.
–
Bit 6: not supported for unbuffered reports.
–
Bit 7: not supported for unbuffered reports.
–
Bit 8: conf-revision.