28
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS
CHAPTER 2: PRODUCT DESCRIPTION
GROUND DISTANCE
Characteristic:......................................................mho (memory polarized or offset) or quad (memory polarized
or non-directional), selectable individually per zone
Reactance polarization:...................................negative-sequence or zero-sequence current
Non-homogeneity angle:................................–40 to 40° in steps of 1
Zones:.......................................................................5
Directionality:........................................................forward, reverse, or non-directional per zone
Reach (secondary ohms):................................0.02 to 250.00 ohms in steps of 0.01
Reach accuracy: .................................................±5%, including the effect of CVT transients up to an SIR of 30
for V < 1.1 × V
nominal
Distance characteristic angle:......................30 to 90° in steps of 1
Comparator limit angle: ..................................30 to 90° in steps of 1
Characteristic angle:.........................................30 to 90° in steps of 1
Limit angle: ............................................................30 to 90° in steps of 1
Z0/Z1 magnitude:...............................................0.00 to 10.00 in steps of 0.01
Z0M/Z1 angle: ......................................................–90 to 90° in steps of 1
Z0M/Z1 magnitude:...........................................0.00 to 7.00 in steps of 0.01
Z0/Z1 angle: ..........................................................–90 to 90° in steps of 1
Right and left blinder reach:..........................0.02 to 500.00 ohms in steps of 0.01
Right and left blinder characteristic
angle: ..................................................................60 to 90° in steps of 1
Time delay: ............................................................0.000 to 65.535 seconds in steps of 0.001
Timing accuracy: ................................................±3% or 4 ms (whichever is greater)
Current supervision level: ...............................neutral current (3I_0)
Current supervision pickup:...........................0.050 to 30.000 pu in steps of 0.001
Memory duration:...............................................5 to 25 cycles in steps of 1
Voltage supervision pickup:...........................0 to 5.000 pu in steps of 0.001 (series compensation
applications)
Operation time:....................................................1 to 1.5 cycles (typical)
Reset time: .............................................................1 power cycle (typical)