30
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS
CHAPTER 2: PRODUCT DESCRIPTION
GROUND INSTANTANEOUS OVERCURRENT
Pickup level:...........................................................0.000 to 30.000 pu in steps of 0.001
Dropout level: .......................................................<98% of pickup
Level accuracy at 0.1 to 2.0 × CT: ...............±0.5% of reading or ±1% of rated (whichever is greater)
Level accuracy at >2.0 × CT:..........................±1.5% of reading
Overreach: .............................................................<2%
Pickup delay:.........................................................0.00 to 600.00 seconds in steps of 0.01
Reset delay: ...........................................................0.00 to 600.00 seconds in steps of 0.01
Operate time:........................................................<16 ms at 3 × pickup at 60 Hz
Timing accuracy for operation at 1.5 ×
pickup: ................................................................±3% or ±4 ms (whichever is greater)
GROUND TIME OVERCURRENT
Current:....................................................................phasor or RMS
Pickup level:...........................................................0.000 to 30.000 pu in steps of 0.001
Dropout level: .......................................................<98% of pickup
Level accuracy at 0.1 to 2.0 × CT: ...............±0.5% of reading or ±1% of rated (whichever is greater)
Level accuracy at >2.0 × CT:..........................±1.5% of reading
Curve shapes:.......................................................IEEE Moderately Inverse, IEEE Very Inverse, IEEE Extremely
Inverse, IEC (BS) A, IEC (BS) B, IEC (BS) C, IEC Short Inverse, IAC
Inverse, IAC Short Inverse, IAC Very Inverse, IAC Extremely
Inverse, I
2
t, FlexCurves™ (programmable), definite time (0.01
second base curve)
Curve multiplier:..................................................0.01 to 600.00 in steps of 0.01
Reset type: .............................................................instantaneous/timed (per IEEE)
Timing accuracy for 1.03 to 20 × pickup: ±3.5% of operating time or ±1 cycle (whichever is greater)
LINE PICKUP
Phase instantaneous overcurrent:.............0.000 to 30.000 pu in steps of 0.001
Undervoltage pickup: .......................................0.000 to 3.000 pu in steps of 0.001
Overvoltage delay:.............................................0.000 to 65.535 seconds in steps of 0.001
LOAD ENCROACHMENT
Responds to: .........................................................positive-sequence quantities
Minimum voltage:...............................................0.000 to 3.000 pu in steps of 0.001
Reach: ......................................................................0.02 to 250.00 ohms in steps of 0.01 (secondary ohms)
Impedance accuracy:.......................................±5%
Angle:........................................................................5 to 50° in steps of 1
Angle accuracy:...................................................±2°
Pickup delay:.........................................................0.000 to 65.535 seconds in steps of 0.001
Reset delay: ...........................................................0.000 to 65.535 seconds in steps of 0.001
Timing accuracy: ................................................±3% or ±4 ms (whichever is greater)
Operate time:........................................................<30 ms at 60 Hz