PROTECTION INPUTS AND OUTPUTS
CHAPTER 7: PROTECTION
Figure 330: Protection contact input actual values
The following actual values are available for all protection contact inputs.
Name
Range: up to 12 alphanumeric characters
This value displays the programmed
ID
for the corresponding protection contact input.
Status
Range: On, Off
This value indicates the logic state of the protection contact input.
Contact outputs
Upon startup of the relay, the main processor will determine from an assessment of the
modules installed in the chassis which contact outputs are available and present the
settings for only these outputs.
Select the
Settings > Protection > Protection Inputs/Outputs > Contact Outputs
menu
item to access the contact output configuration settings.
Figure 331: Protection contact output configuration settings
The settings listed below are available for all contact outputs.
ID
Range: up to 12 alphanumeric characters
Default: Cont Op 1
This setting specifies an alphanumeric identifier for the contact output.
Operate
Range: any FlexLogic™ operand or shared operand
Default: as shown above
This setting selects an operand (virtual output, element state, contact input, or virtual
input) that will operate the contact output when asserted.