CHAPTER 7: PROTECTION
PROTECTION FLEXLOGIC™
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
405
Table 26: Viewpoint Engineer compiler errors
Additional tools are included with EnerVista Viewpoint Engineer Tools that facilitate
debugging of the application. These include the following.
•
Forcing of input variables.
•
Simulation of analog values.
•
Live logic showing intermediate logic states and outputs of timers, counters, and
other operators.
•
Live analog function blocks with output values.
Run-time errors are detectable during execution and are summarized in the following
table. A message is written to the automation event record on detection of an error. There
is also a FlexLogic™ operand associated with each message type. Any virtual analog
outputs associated with a math error will not be updated. Execution of the logic is not
suspended otherwise.
Table 27: Run-time errors
Protection FlexLogic™ equation editor
A protection FlexLogic™ equation can contain up to 512 entries, including the
END
operator. If a disabled element is selected as a FlexLogic™ entry, the associated state flag
will never be asserted (set to logic 1).
Select the
Settings > Protection > Protection FlexLogic > FlexLogic Equation Editor
menu item to open the protection FlexLogic™ equation editor window.
Message
Description
Affected operator
Connection In not connected A connection-input symbol is not referencing an
existing logic or math operator.
Connection input
Input not connected
One or more of the inputs to an operator has no
connection.
All
Number of lines exceeds
maximum limit
The compiled result exceeds the limit for the
number of lines.
All
Operator is over limit
The number of operators of a particular type has
exceeded the maximum allowed.
All
Type Mismatch
An analog variable (physical, shared, or virtual) or
constant has been assigned to an operator input
that expects a digital variable (physical, shared,
or virtual) or vice-versa.
Input
Unrecognized Symbol
An input symbol is not recognized by the current
order code or firmware version.
Input
VAO not connected
A virtual analog output has no connection to its
input.
Virtual analog
output
VDO not connected
A virtual digital output has no connection to its
input.
Virtual digital
output
Message
Description
Affected
operators
Slow execution
The automation scan time exceeded the
expected time.
---