CHAPTER 10: DIGITAL FAULT RECORDER
DISTURBANCE RECORDER
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
523
Figure 452: Disturbance recorder screen
Disturbance recorder settings
Select the
Settings > DFR > Disturbance Record
menu item to open the disturbance
recorder function configuration window.
Figure 453: Disturbance recorder function settings
The following settings are available.
Function
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the disturbance recorder function.
Number of Records
Range: 1 to 64 in steps of 1
Default: 48
This setting specifies the total number of disturbance records that can be stored in the
D90
Plus
. A larger setting results in a shorter record length, and
vice-versa
.
Trigger Mode
Range: Automatic Overwrite, Protected
Default: Automatic Overwrite
If this setting value is “Automatic Overwrite”, then the oldest disturbance record will be
overwritten once the number of stored records reaches the setting value. If this value is
“Protected”, then no new disturbance record are stored once the number of records
reaches the setting value.