530
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
DIGITAL FAULT RECORDER FLEXANALOG™ PARAMETERS
CHAPTER 10: DIGITAL FAULT RECORDER
Figure 460: Shared operands configuration window
The left side of this screen displays all D90
Plus
operands that are available to the digital
fault recorder function as shared operands. Select any operands from the other five
primary features by clicking on the
>>
button. Operands may be de-assigned as shared
operands by pressing the
<<
button.
Digital fault recorder FlexAnalog™ parameters
The following digital fault recorder FlexAnalog™ parameters (analog operands) are
available for the D90
Plus
. They are listed alphabetically by operand syntax The definitions
listed below reflect the programmed source and element names, where applicable.
Fault report analog operands
Fault Ia Mag [1]...........................................Metered phase A fault current magnitude from fault report
Fault Ia Ang [1]............................................Metered phase A fault current angle from fault report
Fault Ib Mag [1]...........................................Metered phase B fault current magnitude from fault report
Fault Ib Ang [1]............................................Metered phase B fault current angle from fault report
Fault Ic Mag [1]...........................................Metered phase C fault current magnitude from fault report
Fault Ic Ang [1]............................................Metered phase C fault current angle from fault report
Fault Va Mag [1].........................................Metered phase A fault voltage magnitude from fault report
Fault Va Ang [1]..........................................Metered phase A fault voltage angle from fault report
Fault Vb Mag [1].........................................Metered phase B fault voltage magnitude from fault report
Fault Vb Ang [1]..........................................Metered phase B fault voltage angle from fault report
Fault Vc Mag [1]..........................................Metered phase C fault voltage magnitude from fault report
Fault Vc Ang [1]...........................................Metered phase C fault voltage angle from fault report