CHAPTER 11: METERING
METERING FLEXANALOG™ PARAMETERS
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
577
PMU 1 FREQ TRIGGER ..............................Asserted when the abnormal frequency trigger of phasor
measurement unit 1 operates.
PMU 1 POWER TRIGGER..........................Asserted when the overpower trigger of phasor measurement
unit 1 operates.
PMU 1 ROCOF TRIGGER...........................Asserted when the rate of change of frequency trigger of
phasor measurement unit 1 operates.
PMU 1 TRIGGERED.....................................Asserted when the phasor measurement unit 1 triggers. No
events or targets are generated by this operand.
PMU 1 VOLT TRIGGER...............................Asserted when the abnormal voltage trigger of phasor
measurement unit 1 operates.
Phasor measurement unit one-shot operands
PMU ONE-SHOT EXPIRED.......................Asserted after the one-shot operation executes.
PMU ONE-SHOT OP...................................Asserted upon one-shot operation.
PMU ONE-SHOT PENDING......................Asserted while the one-shot operation is pending. That is, while
the present time is before the scheduled one-shot time.
Metering FlexAnalog™ parameters
The following metering FlexAnalog™ parameters (analog operands) are available for the
D90
Plus
. They are listed alphabetically by operand syntax The definitions listed below
reflect the programmed source and element names, where applicable.
Phasor measurement unit analog operands
PMU 1 Conf Ch............................................Metered configuration change counter value for phasor
measurement unit 1
PMU 1 df dt...................................................Metered frequency rate of change value for phasor
measurement unit 1
PMU 1 Freq....................................................Metered frequency value for phasor measurement unit 1
PMU 1 Num Triggers ................................Metered number of triggers for phasor measurement unit 1
PMU 1 Ia Mag...............................................Metered phase A current magnitude for phasor measurement
unit 1
PMU 1 Ia Ang................................................Metered phase A current angle for phasor measurement unit 1
PMU 1 Ib Mag...............................................Metered phase B current magnitude for phasor measurement
unit 1
PMU 1 Ib Ang................................................Metered phase B current angle for phasor measurement unit 1
PMU 1 Ic Mag...............................................Metered phase C current magnitude for phasor measurement
unit 1
PMU 1 Ic Ang................................................Metered phase C current angle for phasor measurement unit 1
PMU 1 Ig Mag...............................................Metered ground current magnitude for phasor measurement
unit 1
PMU 1 Ig Ang................................................Metered ground current angle for phasor measurement unit 1
PMU 1 I0 Mag...............................................Metered zero-sequence current magnitude for phasor
measurement unit 1
PMU 1 I0 Ang................................................Metered zero-sequence current angle for phasor measurement
unit 1
PMU 1 I1 Mag...............................................Metered positive-sequence current magnitude for phasor
measurement unit 1
PMU 1 I1 Ang................................................Metered positive-sequence current angle for phasor
measurement unit 1