The main DC-capacitor needs replacement due to aging or failure
CAPACITOR C1
CAPACITY LOW
Due to a failure the output converter's output is not available. As a result the
load may have been transferred to bypass.
LOADnotPROTECTED
INVERTER OFF
OPM_LPE_11X_3K0_10K_1GB_V041
21
GE DE LP 11 UPS: User manual 4.1 (GB)
The remaining runtime is zero. As a result the load may have been transferred
to bypass.
LOADnotPROTECTED
BATTERY DEPLETED
The remaining runtime is less than the set time (standard 2 minutes). This text
alternates with the following screen:
LOADnotPROTECTED
BATTERY LOW
The output voltage can be lost after the indicated time due to discharged
battery. Controlled shutdown of any computer equipment is absolutely
necessary at this point. (Using the RS232 or SNMP communications interface,
this procedure can be initiated automatically on unattended systems). If the
UPS operates at 100% load, the shutdown procedure should be completed
within 2 minutes after the 'battery low' alarm started. When the batteries are
fully discharged, the UPS is no longer able to power the connected equipment.
UPS SHUTDOWN
LEFT 2 MINUTES
The static bypass MCB (rear panel, 9) is in 'off' (down position): no bypass
voltage available. Mains voltage is available. If not manually operated, this may
have been caused by an overload situation.
BYPASS ERROR
FUSE FAILURE
The mains MCB (rear panel, 8) is in the 'off' (down position): no line voltage
available, bypass voltage is available. If not manually operated, this may have
been caused by an internal system failure.
INPUT ERROR
FUSE FAILURE
The internal battery fuse is defective; this may have been caused by an
internal system failure. This alarm also appears if no batteries are installed.
INTERNAL BATTERY
FUSE FAILURE
The (custom-built) battery extension set has been disconnected from the
system: its energy reserve is not available. See 4.5.2 or 4.5.4 step 9 for details.
EXTERNAL BATTERY
FUSE FAILURE
The batteries are (almost) chemically worn out. If the batteries are aged, they
must be replaced as soon as possible to ensure full protection for your
equipment (see section 8.3).
REPLACE BATTERY
The mains voltage or mains frequency are outside UPS input tolerance (see
chapter 10, specifications)
INPUT out LIMITS
137V 50.0Hz
The mains voltage or mains frequency are outside bypass input tolerance but
inside UPS (rectifier) input tolerance (see chapter 10, specifications). Bypass
operation is inhibited: if for whatever reason the output converter is unable to
deliver the required output, output power is lost.
BYPASSoutLIMITS
197V 50.0Hz
The output converter frequency is not synchronized to the mains (input)
frequency. In this situation the automatic bypass switch is not able to transfer
the load from output converter to bypass and reverse: automatic bypass
operation is inhibited: if for whatever reason the output converter is unable to
deliver the required output, output power is lost. (see section 3.4).
INPUT AND OUTPUT
NOT SYNCHRONIZED
Synchronization is only possible if the mains frequency remains within
certain limits (see chapter 10).
The remaining runtime. This figure is counted down during battery operation
until either the mains returns or the batteries are depleted.
AUTONOMY TIME
LEFT 0:09:41