4 - Installation
4.1 Transport
NOTE:
Transport the UPS only in upright position. Check for sufficient floor and elevation loading
capacity. Move the UPS in its original package to the final destination room. Do not stack other
package on top.
4.2 Unpacking
Cut the two wrapping bands, and remove the shipping box. Loosen the four bolts with which the UPS is fixed to
the pallet. Remove the UPS from the pallet.
BE CAREFUL! Pay attention to the HEAVY WEIGHT of the UPS when downloading the UPS
from the pallet!
Never try to lift the unit by yourself!
The UPS is equipped with castors, which allow easy displacement of the unit. Please take appropriate
measures to avoid damage on vulnerable floors.
4.3 Package
Contents
The shipping box contains a LP 11 UPS, a CD-ROM, an RS232 cable, cable clamps, a safety guide and this
manual. If the UPS is equipped with an RPA plug-in card (Redundant Parallel Architecture, right option slot at
the rear of the unit) the shipping box also contains a yellow network cable and one bus terminator. Inspect the
UPS for damage after unpacking. If any damage is present please notify the carrier and place of purchase
immediately.
4.4 Location
Please refer to sections 1.2 and 1.3 of ‘IMPORTANT SAFETY INSTRUCTIONS’.
4.5 Installation
IMPORTANT
:
Before making any connection and switching on the LP UPS, please check the following conditions:
-
the voltage and frequency of your utility supply is 220/230/240 Vac and 50/(60) Hz; off-factory the output
of the UPS is set to 230 Vac / 50 Hz,
-
the branch circuit supply is protected as follows:
UPS model
branch protection
LP 3kVA
16A slow
LP 5/6kVA
25A slow
LP 8kVA
50A slow
LP 10kVA
50A slow
Table 1. external input fuse value
CAUTION:
To reduce risk of fire, connect the UPS only to a circuit provided with the fuse
values according to Table 1 above.
-
Ensure that the total power requirement of the equipment to be protected does not exceed the rated
output power of the UPS (output power for your unit is indicated on the rating label on the rear panel).
-
The UPS must be grounded when in use: Connect the UPS to a single phase, three wire AC source
equipped with an earth connection.
The following sections describe the installation of the LP 11 UPS.
LP 3/5/6-11 UPS:
4.5.1 and 4.5.2
LP 8/10-11 UPS:
4.5.3 and 4.5.4
LP 11 UPS, general:
4.5.5
OPM_LPE_11X_3K0_10K_1GB_V041
8
GE DE LP 11 UPS: User manual 4.1 (GB)