g
GE
OPM_LPS_31E_8K0_20K_1GB_V010.doc
22/40
Operating
Manual
LP 31
/ 8-10-15-20
kVA
LOADnotPROTECTED
BATTERY LOW
The remaining autonomy is less than the set time (standard 2
minutes).
This text alternates with the following screen:
UPS SHUTDOWN
LEFT 2 MINUTES
The output voltage can be lost after the indicated time due to
discharged battery. Controlled shutdown of any computer
equipment is absolutely necessary at this point.
(Using the ComConnect communications interface, this
procedure can be initiated automatically on unattended
systems).
If the UPS operates at 100% load, the shut-down procedure
should be completed within 2 minutes after the
“battery low”
alarm started.
When the batteries are fully discharged, the UPS is no longer
able to power the connected equipment.
INTERNAL BATTERY
FUSE FAILURE
One of the internal battery fuses is defective; this may have
been caused by an internal system failure.
This alarm also appears if no batteries are installed.
EXTERNAL BATTERY
FUSE FAILURE
The battery extension MCB is in “OFF” position (down):
energy reserve of the battery extension pack is not available.
If not manually operated, this may have been caused by faulty
wiring or battery failure.
REPLACE BATTERY
The batteries are (almost) chemically worn out.
If the batteries are aged, they must be replaced as soon as
possible to ensure full protection for your equipment (see
chapter 7.3).
INPUT out LIMITS
137V 138V 140V
The mains voltage or mains frequency are outside UPS input
tolerance (see section 9 - Specifications).
BYPASS out LIMITS
170V 52.7Hz
The mains voltage or mains frequency are outside bypass
input tolerance but inside UPS (rectifier) input tolerance (see
section 9 - Specifications).
Bypass operation is inhibited: if for whatever reason the output
converter is not able to deliver the required output, output
power is lost