INPUT AND OUTPUT
NOT SYNCRONIZED
The output frequency is not synchronised to the mains (input)
frequency.
The automatic bypass switch is not able to transfer the load
from output converter to bypass and reverse (see chapter
2.5).
This requires synchronisation of the output frequency with
the mains supply frequency.
Synchronisation is only possible if the mains frequency
remains within certain limits (see section 9 - Specifications).
If output converter and mains are not synchronised bypass
operation is inhibited.
If for whatever reason the output converter is not able to
deliver the required output, output power is lost.
RUNTIME
LEFT 0:09:41
The remaining autonomy time.
This figure is counted down during battery operation until
either the mains returns or the batteries are empty.
OUTPUT OFF
NO INPUT POWER
The output is switched OFF due to a faulty situation, indicated
by the second line, e.g. no input power and depleted batteries.
PROG. SHUTDOWN
WITHIN 0:09:17
The output will be switched OFF via ComConnect.
The second line indicates the time until shutdown.
PROG. SHUTDOWN
LEFT 0:14:03
The output is switched OFF via ComConnect.
The second line indicates the time until wake-up.
IMMEDIATE
SHUTDOWN
The wire on connector 18 (rear panel, see figure 6) is
interrupted.
The output is no longer available.
To restart the unit, restore the connection and turn ON/OFF
switch (7) OFF and ON again.