OUTPUT VOLTAGE
230V
The system output voltage.
Range: 220/230/240 VAC.
BATTERY CAPACITY
7Ah
Battery
capacity.
Range: 7 through 590 Ah, in 1 Ah steps.
WARNING !
If you proceed, the information about the
actual battery condition (as a result of a deep
battery test) is lost.
For more info see chapter 4.4.2 – “Quick
Battery Test”.
FAN CURVE
SMALL
The
fan
speed.
Range: SMALL/LARGE.
Proper setting optimizes the cooling capacity of the fans
installed.
DO NOT READJUST!
Incorrect setting may lead to reduced lifetime of the power
semiconductors.
NO-LOAD SHUTDOWN
YES
Setting “YES” means that the function is activated: the UPS
switch OFF during a mains failure when the load is less than
2% of the maximum load.
Range:
YES/NO.
AUTOMATIC BYPASS
ENABLED
Controls functioning of the automatic bypass switch.
Range: ENABLED/DISABLED.
If the UPS is used as a frequency converter you may change
the setting to “DISABLED”.
Bypass operation will then inhibited and all alarms related to
“bypass out of limits” are suppressed.