Modifications reserved
Page 7/10
PRD_LPS_31E_8K0_20K_1GB_V021.doc
Product Description
LP 31 Series
The ‘
default screen’
shows UPS model and actual load (values are examples):
LP 15-31
LOAD 37%
The
'information screens'
show the UPSs system data:
- Mains voltage, mains frequency and the power delivered by the mains.
- Output voltage and output frequency, and the power delivered by the UPS.
- Power factor, crest factor and peak currents of the connected equipment.
- Temperature near the batteries, battery voltage and battery (dis)charging current.
- Remaining autonomy time (during mains failure).
- The total operating time of the UPS
The
'setup screens'
show a programmable UPS function and its actual setting:
- System operating frequency.
- System operating voltage.
- Battery
capacity.
- No-load
shutdown
(<2%).
- Bypass
enable/disable.
- Frequency tracking range.
The
'service screens'
show service information targeted on trained service personnel:
- Serial number of the UPS, release number of the installed software.
- Service information on internal components, fan speed, internal DC voltage, internal temperature
levels, peak input voltage, mean (bypass) input voltage, mean output voltage.
- Start of a quick battery test.
- Forced (manual) transfer to bypass.
The
'test screens'
show the proceeding of the following tests:
- General system test.
- Quick
battery
test.
- Battery calibration test.
- Bypass
test.
3.3 Alarm Conditions
The LCD screen on the front panel displays status messages and alarm messages.
Three kinds of messages can be recognized.
- Status indications
indicate the UPS operating mode.
- Low
priority
alarms
indicate
abnormal operating situations; the screen message is accompanied by
a 1x per sec. blinking red LED and a 1x per 8 seconds. sounding buzzer, resettable.
- High priority alarms
indicate situations in which the connected load is at risk as a
proper
output voltage of the UPS is no longer guaranteed
; immediate action
should be taken.
The screen message is accompanied by a 1x per sec. blinking red
LED
'alarm'
and a 1x per second sounding buzzer, resettable.
Note: By using ComConnect, additional conditions can be monitored and signals include written screen
messages (see section 5, Interfacing).