Digital Energy™
g
OPM_LPS_3UI_10K_20K_0US_V010.doc
15/38
Installation Guide
LP 33
/ 10 - 20 kVA
3.4
PLACE OF INSTALLATION
The UPS should be installed in a
restricted area
where only qualified personnel should be
admitted.
The place of installation
should be clean
,
dust-free
, and provided with proper
ventilation or air-
conditioning
.
Verify for
sufficient floor load capacity
(see
Section 3.1.1
).
We strongly advice that the ambient temperature should not exceed
68°
÷
77°F
/ 20°
÷
25°C
(max.
95°F / 35°C).
See
Section 3.5
.
NOTE !
Insufficient space on both sides of the UPS in respect to the wall can cause a
dangerous increase of the internal operating temperature.
Fig. 3.4-1
LP 33
positioning
Fig. 3.4-2
LP 33
RPA parallel system positioning
LP 33
positioning
For easier access in case of maintenance
operation and for a free circulation around the
cabinet, we recommend to maintain the
following minimum distances:
Right & left side:
50 mm
(2”)
Rear side:
50 mm
(2”)
Top of the UPS:
300
mm
(12”)
Right & left side:
50 mm
(2”)
Rear side:
50 mm
(2”)
Top of the UPS:
300
mm
(12”)
NOTE !
Operating temperature is very important for
valve regulated battery
(maintenance free).
Operation at temperatures higher than 20°C (68°F) will reduce life expectancy.
Respect the prescription VDE 0510, those of the battery supplier and other
local standards.
The installation and cabling of the battery must be done by qualified people.