Modifications reserved
Page 31/86
OPM_SGS_USM_M40_M50_1US_V020.doc
Operating Manual
SG Series 400 & 500 kVA
6.5 USER PARAMETERS
Pressing the
Parameters
button displays a series of screens containing the user parameters on the
LCD
panel
.
This first parameter level in not protected by password, therefore the user can freely adapt these
parameters to their needs.
The meaning of the user parameters and their use is described below (buttons performance is described
to
Section 7.3
).
1.
Date and Time set-up
DATE AND TIME
D M Y
Date: 01.01.2006
Time: 12:45:07
metering
alarms
parameters
+
–
ok
Date
You can adjust the date of the real time clock existing in the UPS by the means of this
parameter.
The value you enter is thoroughly checked to be a correct date in the format “dd.mm.yy”.
Time
You can adjust the time of the real time clock existing in the UPS by means of this
parameter.
The value you enter is thoroughly checked to be a correct time in the format “hh.mm.ss”.
The time is specified in 24-hour format.
2. Protocol
Set-up
PROTOCOL SETUP
Modem enabled= N
Init= BEQV1X3&D0S0=2
Alarm =N Delay=22sec
m e te ring
alarm s
pa ra m e te rs
+
–
ok
Modem enabled
You can enable/disable with
Y/N
the remote control through modem calls by
using this parameter.
Init
This parameter presents the modem initialisation string.
It can be 39 characters long.
When editing this parameter the UPS considers that a blank character terminates
the string.
If no blank character is found then all 39 characters are used.
Alarm
This
Y/N
parameter controls the automatic events signalling through modem.
If this parameter is set to Yes the UPS itself will call the remote location when a
new event occurs.
Delay
This parameter controls the delay between the occurrence of a new event and the
modem dialing.
It is useful because since the events typically do not occur isolated but in certain
sequences, you can eliminate the need for multiple dial-outs for such a sequence
of events.