Operating Manual
SG Series 400 & 500 kVA
7.3.4 Separate a Unit from the parallel system (System Redundancy)
Initial status:
Load supplied from all Inverters
.
First operated unit
All other units of the system
1. Press and hold
“
inverter off
”
( O ) key on the Unit to separate, until the LED turns OFF
.
Load
supplied from
Inverter(s)
of the other Unit(s) of the parallel system
.
First operated unit
All other units of the system
2. Open Q1 (Pos. O) and, only when the LED service check is ON, press
“
total off
”
button
on the Unit to separate
.
•
Press
mute
, to reset
alarm and buzzer.
First operated unit
All other units of the system