SitePro 60 kVA
UPS room conditions and temperature
The UPS room and the battery room have to be maintained clean and free from dust.
A high temperature of the UPS room and of the battery room affect the lifetime of several components
inside the equipment.
The battery is very sensitive to room temperatures above 25°C (77°F).
Preventive maintenance program:
a) Cleaning, a visual inspection and a mechanical inspection of the UPS modules;
b) Replacement of defective parts or the preventive replacement of parts with a defined life time
c) “Updating” of the equipment (technical improvements subsequent to the delivery).
d) Check the calibration of DC voltage and Inverter output voltage and frequency.
e) Check of the settings of the electronic regulation, the control and the alarm circuits of the rectifier(s)
and inverter(s).
f) Functional checks on thyristors, diodes, transformers, filter components, e.g. to ensure that they
are operating within the specified design parameters.
g) Overall performance test including a mains failure simulation with and without the load.
h) Monitoring battery operation in discharge and recharge mode including any boost charge duties.