5.1 Technical
data
Input line parameters (supply)
Rated input voltage
3 x 400 V RMS phase to phase
TN-C, TN-S
Acceptable changes of input
voltages
-25%
÷
+20%
Frequency 50
Hz
Acceptable changes of
frequency
-9%
÷
+6%
<1,5kV
Iimp 15kA 8/20us
Voltage surge withstand
<1,0kV
Iimp 5kA 8/20us
Voltage insulation
AC 2kV 60s
Efficiency >99%
cos(
φ
) > 0,8
Output line parameters
STS-400-63-4
3 x 63 A RMS
+ 125 A RMS (neutral)
STS-400-40-4
3 x 40 A RMS
+ 80 A RMS (neutral)
STS-400-25-4
3 x 25 A RMS
+ 50 A RMS (neutral)
STS-400-100-3
3 x 100 A RMS
+ 200 A RMS (neutral)
STS-400-63-3
3 x 63 A RMS
+ 125 A RMS (neutral)
STS-400-40-3
3 x 40 A RMS
+ 80 A RMS (neutral)
Rated output current
STS-400-25-3
3 x 25 A RMS
+ 50 A RMS (neutral)
Maximum crest factor
3,5
Power factor cos(
φ
)
0,5-1 lag,
lead
<1,5kV
Iimp 15kA 8/20us
Voltage surge withstand
<1,0kV
Iimp 5kA 8/20us
Acceptable overload
125%
400%
800%
1000%
1500%
t=1h
t=5s
t=0,4s
t=0,2s
t=20ms
Short circuit withstand for
thyristors (130°C)
3200 A/20ms
8000 A/20ms for STS-400-100-3
I
2
t value for thyristors (130°C)
51200A
2
s
320000 A
2
s for STS-400-100-3
Breaking ability for fuses
50kA
5 - Specifications