DMC490 Microgrid Controller Software Configuration Guide
18
View and Switch Modes
»
To view the state of Optimizer Operation Mode:
1.
Navigate to the MGC application Point details page on the HMI:
Point Summary
>
Applications
>
Microgrid Controller
>
Analog Input
2.
Use the Analog Input pseudo point
MGC Current state
from the MGC point summary page.
»
To switch between different Optimizer Operation modes:
1.
Navigate to the MGC application Point details page on the HMI:
Point Summary
>
Applications
>
Microgrid Controller
>
Analog Output
2.
From the Analog Output tab, access pseudo point
MGC Change Current state
.
3.
Choose a desired mode based on the Analog codes given for each mode.
»
To view the time remaining until the next cycle of Optimization is executed:
1.
Navigate to the MGC application Point details page on the HMI:
Point Summary
>
Applications
>
Microgrid Controller
>
Analog Input
2.
From the Analog Output, access pseudo point
MGC Change Current state
.
3.
See the status for the
Time to Next Advice
point.
Configuration Overview
Microgrid Assets
»
To configure and map microgrid assets:
1.
Click the
Configuration
Power Bar button and select the
MGC
tab.
Result: The Electrics pane appears.
2.
Select:
Electrics
(Electrical Assets) tab or the
Thermal
(Thermal Assets) tab.
3.
If Electrics or Thermal is selected, click
+
to add an asset.
Result: The Create Asset window appears.
4.
Select the Asset type:
•
Electrical Assets
o
Renewable Asset
o
Dispatchable Asset
o
Storage Asset
o
Load Asset
o
Grid Asset
•
Thermal Assets
o
Thermal CHP Asset
o
Boiler Asset
o
Heat Load Asset
Summary of Contents for DMC490