DMC490 Microgrid Controller Software Configuration Guide
32
•
Operation mode:
This is an Analog output which refers to the current microgrid operation mode of the
asset (as explained in section System Settings on page 19, see the Active Mode setting).
•
Input Watchdog:
This is a Digital Output command used to inform the charge controller in the Storage
asset that the MGC controller is active. A Digital Output command is sent on this point with a value
toggling between 0 and 1 every 10 seconds.
•
Output watchdog:
This is a Digital Output command used to inform the discharge controller in the
Storage asset that the MGC controller is active. A Digital Output command is sent on this point with a
value toggling between 0 and 1 every 10 seconds.
Figure 14 Upper Boundary Store – State of Charge
Load Asset
Configure each load for the use of the electricity, such as which forecast to use.
Point Settings
Setting
Description
Range
Default
Asset ID
Unique asset ID assigned by the DMC490 MGC.
Name
Specify the name of the asset.
4 to 20 characters
Load Asset_
Enabled
Specify if the asset is to be included in the microgrid
optimization calculations.
Disabled
Enabled
Enabled
Status Points
The following field mappings apply to the status/control and read only inputs that are to be mapped to the
Microgrid controller >
Load Asset
configuration page:
•
Online:
This field indicates if the load is online or offline, meaning consuming electricity or not.
•
Net Meter Power:
This field indicates the values of demanding powers in kW read from different loads
in the system.
•
Operation mode:
This is an Analog output which refers to the current microgrid operation mode of the
asset (as described in section System Settings on page 19, see the Active Mode setting).
•
Watchdog:
This is a Digital Output command used to inform the asset that the MGC controller is
active. A Digital Output command is sent on this point with the value toggling between 0 and 1 every
10 seconds.