Health Status and Monitoring
45
Health Status and
Chapter 3 -
Monitoring
The MGC application provides health status information in the form of Pseudo points in the Point Summary of
MGC table. Navigate to this table in the D400 HMI at:
Point Summary
>
Applications
>
Microgrid Controller
.
The following table lists the Point Summary of MGC status points and their descriptions.
Health and Monitoring points Status
Status point name
Action
MGC - Solver timed out
Solver related error: unable to find a solution within a reasonable amount of time
MGC - Solution Status
Solver related error: the solver fails to find a solution, for example due to insufficient
memory
Optimal Control Feasibility
Solver related error: the problem has no feasible solution, meaning that there is no
solution that satisfies all the constraints
Optimal Control Optimality
Solver related error: no converge to an optimal solution
MGC Solver data valid
Solver related error: data file parsing fails; error with the generated data file
MGC solver – solution is feasible
Solver related error: solution is out of range
MGC Solver solution is defined
Solver related error: undefined solution
MGC Solver solution bound
Solver related error: solution is not finite (feasibility condition is not violated but the
value of one or more decision variables and the objective function approach infinity)
Unexpected Disp [1...16] Offline
One of the dispatchable resources went offline unexpectedly
Unexpected Disp [1...16] Online
One of the dispatchable resources came online unexpectedly
Unexpected Disp [1...16] in Droop
Discrepancy between the "Isoch" command and actual reading from the device
Unexpected Disp [1...16] in Isoch
Discrepancy between the "Droop" command and actual reading from the
device
Unexpected Renew [1...16] in
Droop
Discrepancy between the "Isoch" command and actual reading from the device
Unexpected Renew [1...16] in
Isoch
Discrepancy between the "Droop" command and actual reading from the device
Unexpected StoreChg [1...16] Offline
One of the charging storage devices went offline unexpectedly
Unexpected StoreChg [1...16] Online
One of the charging storage devices came online unexpectedly
Unexpected StoreDischg [1...16] Offline
One of the storage devices supplying electricity to the microgrid went offline
unexpectedly
Unexpected StoreDischg [1...16] Online
One of the storage devices that supplies electricity to the microgrid came online
unexpectedly
Unexpected CHP Offline (1…8)
One of the CHP devices went offline unexpectedly
Unexpected CHP Droop(1…8)
Discrepancy between the "Isoch" command and actual reading from the device
Unexpected CHP Isoch(1…8)
Discrepancy between the "Droop" command and actual reading from the device
Unexpected Grid Offline
Grid connection went offline unexpectedly
Unexpected Boiler Offline (1…8)
One of the Boiler devices supplying Heat to the microgrid went offline unexpectedly
Unexpected Boiler Online(1…8)
One of the Boiler devices supplying Heat to the microgrid went Online unexpectedly