22
DR60-TM-EN-
2A
Before decommissioning, completely isolate the
equipment power supplies (both poles of any dc supply).
The auxiliary supply input may have capacitors in
parallel, which may still be charged. To avoid electric
shock, discharge the capacitors using the external
terminals before decommissioning.
Avoid incineration or disposal to water courses. Dispose
of the equipment in a safe, responsible and
environmentally friendly manner, and if applicable, in
accordance with country-specific regulations.
5
Standards Compliance
Compliance with the European Commission Directive on EMC and LVD is demonstrated
using a Technical File.
5.1
EMC Compliance:
Compliance with IEC 60255-26:2013 was used to establish conformity.
5.2
Product Safety
Compliance with IEC 60255-27:2014 was used to establish conformity.
Protective Class
IEC 60255-27:2014 Protective Class 1. This equipment requires a protective conductor
(earth) to ensure user safety.
Installation category
▪
When using the 100-250 Vdc / 110-240 Vac power supply: IEC 60255-27:2013
Installation category III (Overvoltage Category III). Equipment in this category is
qualification tested at 5kV peak, 1.2/50 μS, 500 Ohms, 0.5 J, betw
een all supply
circuits and earth and also between independent circuits.
▪
When using the 24-48 Vdc power supply: IEC 60255-27:2013 Installation category II
(Overvoltage Category II)
Environment
IEC 60068-2-1, IEC 60068-2-2, IEC 60068-2-30, IEC 60068-2-14, IEC 60255-21-1, IEC
60255-21-2. The equipment shall always be installed in a specific cabinet or housing
which will enable it to meet the requirements of IEC 60529 with the classification of
degree of protection IP54 or above.