EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH41549 R05
Install Door Interlock System
•
It must be ensured that the supply power
to the compartment is turned off/
compartment is de-energized for all the
incoming and outgoing circuits of the LVS
prior to any work being conducted on it.
•
During the installation and related work
on the equipment, it must be ensured
that the operator is using the prescribed
PPE for the specified tasks.
•
Ensure only qualified personnel install, operate, service, and maintain all electrical
equipment.
Details regarding installation of the door interlock system are shown below in
Figure 44
, 45 and
46
.
Figure 44. AKD-8—Door Interlocking Components (Model 1)
•
Racking stroke of legacy = 4.25”. Racking stroke of Retrofills = 2.75”.
•
Racking stroke of the Retrofills is equal to that of AKR30S.
•
Same mounting bracket used for all AKR breakers in AKD8, depending on SKU the mounting holes are
decided on.
•
Provisions for fixing the door interlock are already present on the mounting bracket.
•
Door interlock system of AKR30S can be used for Retrofills.
•
Remove existing activator and replace with new activator shown.
•
For AKR30S, existing door interlock suffices. No changes needed.