7
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH41549 R05
Document Conventions
Topics and text are divided into primary, secondary, and tertiary paragraph headings.
Related Publications
Publication
Publication Number
Brochure
DEA-532
Snapshot
DEE-543
Installation Manual AKD-10
DEH-41550
Installation Manual AKD8
DEH-41549
Installation Manual AKD6 (800A-2000A)
DEH-41548
Installation Manual AKD5 (600A-2000A)
DEH-41547
Installation Manual AKD-5/6 (3000A/3200A/4000A)
DEH0005240
Accessory: Door Interlock (Door Interlock Kit)
DEH-41529
Accessory Retrofill Doors Assembly
DEH-41563
Accessory: Position Switch Plate & Position Switch Assembly & Wiring (Position Switch Kit)
DEH-41530
Accessory: Neutral Rogowski CT Disconnect (Neutral Assemblies)
DEH-41531
Accessory: Programmer Disconnects
DEH-41532
Accessory: Finger Clusters (Cluster Assemblies)
DEH-41533
Accessory: Secondary Disconnects
DEH-41534
FAQ
DEQ-171
Application Guide
DET-753
Guideform Spec
DET-754
Spare/Renewal Parts Guide
DET-755
Neutral CT Adapters
DEH0002400
Service and Support:
Service and support always available from GE Energy.
Estimated Time to Complete Tasks
Wiring the secondary disconnects and verifying they match the switchgear cublicle may take 1 to 8 hrs
depending on the complexity of the original breaker. Once the retrofill breaker is fully prepared, it should
take about 20 minutes to swap out the old breaker and rack in the new EntelliGuard R retrofill circuit breaker
if the proper lifting bar and hoist are available.
The EntelliGuard R retrofill, when ordered with 4 wire ground fault, will be equipped with a Neutral CT
adapter. The adapter will modify the GE MicroVersaTrip type Neutral CT output to a Rogowski sensor output
compatible with the EntelliGuard R’s Trip Unit. With this device, it will
not
be necessary to change the neutral
CT in the switchgear to a Rogowski sensor. Note: Neutral CT Adapters are designed to modify the signal
from any Neutral CT which is compatible with a MicroVersaTrip or any newer GE Trip Unit type originally
supplied by GE in AKD-8 switchgear from 1979 to 2015. GE type TSVG… neutral CT’s are compatible. The old
GE SST Neutral CT’s are not. Neutral sensors working with any Non-GE trip units installed as the result of a
Trip unit conversion kit should be assumed to be incompatible with the NCT Adapter.
Product Specs
Weight (lbs.)
Retrofill Breaker
Weight
Cover Box Wt.
Pallet Wt.
~ Accessories
Wt.
~ Shipping
Weight
AKR30S-800A
184
11
24
2
221
AKR-30/30H-800A
230
11
24
2
267
AKR-30L-800A AKR-50/50H-1600A
270
11
24
2
307
AKRT-50H-2000A
270
11
24
2
307
AKR75/AKR75H-3200A
600
15
30
2
647
AKR100-4000A
625
15
30
2
672
AKR125-5000A
700
19
38
2
759