background image

 

 

 

 

                     Figure 7B.            Tighten to 6

 

Nm (4.42ft-lbs) 

 

 

 

Figure 7C.

 

                  

Tighten to 6

 

Nm (4.42ft-lbs) 

 
12. To reinstall the cover, rotate the charging 
handle down and slide the front cover over the 
handle to assemble the front cover to housing as 
shown in Fig. 8. 
14. Ensure the fascia is aligned properly with the 
trip unit and the pad lock features of the breaker. 
 

 

Figure 8.

 

                                         
15

.

 

Fasten the 6 mounting screws of fascia with 

the housing using a pozidrive screwdriver.  Apply 
torque of 6 Nm (4.42ft-lbs).

   

 

Breaker key lock Operation: 

Use the following procedure to operate the 
padlock: 
 
1. Depress the OFF pushbutton on the breaker 
front Fascia and extend/pull the breaker padlock 
lever to its' outer position. 
2. With the padlock lever extended, rotate one or 
more of the keys anticlockwise. The key can then 
be removed thus locking the breaker in its open 
position. 
3. With padlock lever extended, insert the key and 
rotate in clockwise to unlock.

                              

 

 

 
 

 
 
 
 
 

 
 

 

GE Consumer & Industrial 

Electrical Distribution

 

These instructions do not purport to cover all details or variations in equipment nor, to provide contingency to be met in connection 
with installation, operation, or maintenance.  Should further information be desired, or should particular problems arise which are not 
covered sufficiently for the purchaser’s purposes, the matter should be referred to GE. 

GE 

41 Woodford Ave, Plainville, CT 06062 
www.geelectrical.com 
 
© 2009         General Electric Company

 

 

DEH-41407 R02 (11/14) 

Summary of Contents for EntelliGuard GBKRKR

Page 1: ...log Number Installation of kit Use the following procedure to install the Key Interlock Key accessory into the circuit breaker 1 Turn the breaker off and discharge the closing springs by depressing the OFF and ON buttons in the sequence OFF ON OFF Verify that the breaker OFF ON indicator shows OFF and that the charge indicator shows DISCHARGE If installing in a draw out type breaker remove breaker...

Page 2: ...upplied as a field mountable kit please proceed to step 4 4 Take the Lock cover and carefully break out the openings needed to place the required number of locks 5 Fix each lock to the lock bracket using the fixation nuts as indicated in Fig 2 Figure 2 6 Using the nut supplied with each lock fix the activating CAM Ensure that the CAM is positioned as indicated in fig 3 For Kirk Lock insert the spa...

Page 3: ...erator installation Support bracket Nylock nut Adaptor nut Figure 5 10 If the locking mechanism device has been supplied factory fitted Remount the mechanism with its cover into the breaker making sure that the operating lever moves freely and interacts correctly with the breaker mechanism Fig 6 Figure 6 11 If supplied as a field mountable kit carefully remove the dummy lock cover from the Breaker...

Page 4: ...e breaker front Fascia and extend pull the breaker padlock lever to its outer position 2 With the padlock lever extended rotate one or more of the keys anticlockwise The key can then be removed thus locking the breaker in its open position 3 With padlock lever extended insert the key and rotate in clockwise to unlock These instructions do not purport to cover all details or variations in equipment...

Reviews: