4
.1
C
OILS
ACCESSORIES
EntelliGuard L
4.1-06
UV ratings
Data
Control Voltages
Operational voltage range
Dropout Volts
Control Voltages
Operational voltage range
Dropout Volts
(85-110%)
(35-60%)
(85-110%)
(35-60%)
24 VDC
21-26 VDC
8-14
48 VDC / VAC
41-53 VDC / VAC
17-29
110-130 VDC / VAC 94-143 VDC / VAC
45-66
220-240 VDC / VAC
187-264 VDC / VAC
84-132
250 VDC / 250-277 VAC 213-275 VAC
96-150
380-415 VAC
323-456 VAC
145-228
Bobina de Mínima Tensão, Operação
- Tempo de ciclo:
2 per min
- Energia de Inrush: 350VA(CA) 350W (CC)
- Energia de Funcionamento: 60VA (CA) 50W (CC)
Undervoltage release operating
- Duty cycle:
2 per min
- Inrush Power:
350VA(AC) 350W (DC)
- Steady state:
60VA (AC) 50W (DC)
Wyzwalacz podnapięciowy
- Cykl pracy:
2
/
min
-
Moc początkowa:
350VA(AC) 350W (DC)
- Stan ustalony:
60VA (AC) 50W (DC)
Tensões de Controle Intervalo Operacional de Tensão Dropout Volts
Napięcia sterujące
Zakres napięciowy
Napięcia odpadania
Fig. A: Insert top plate
Fig. B: Snap on
Fig. C: wire assembly
Fig. D: Coil positions
Fig. A: Insira na placa de topo
Fig. B: Encaixe
Fig. C: Ligação
Fig. D: Posições das Bobinas
Fot. A: Zamocowanie wyzwalacza
Fot. B: Po zamocowaniu
Fot. C: Podłączenie przewodów
Fot. D: Położenia cewek
A
B
2
C
D
1
3
Undervoltage
Release
2
STANDARD CONNECTION SCHEME FOR TERMINAL BLOCK B
ESQUEMA DE LIGAÇÃO PADRÃO PARA O BLOCO DE TERMINAIS B
Schemat połączeń standardowych dla listy zaciskowej
B
Undervoltage
Release
2
SHUNT Release
1
Closing Coil
3
B10
B9
M
ML
M1
M2
LP1
B2
B1
SPR
58
57
User‘s designated circuits | Circuitos atribuídos ao utilizador | Obwody uzytkownika
B12
B11
C1
C2
ST
1
B14
B13
C4
C3
UVR
2
B16
B15
CC
D1
D2
3
LP4
B8
B7
95
98
T
BAT
B4
B3
N-RC
+
N-RC
-
-
+
N
B6
B5
24V
+
24V
-
+24-
VDC
1:
Wyzwalacz napięciowy (wzrostowy)
2:
Wyzwalacz podnapięciowy (zanikowy)
3: C
ewka zamykająca
Portuguese VDC=Vcc VCA=Vca