18
EntelliGuard R Circuit Breaker Retrofill AKD-10 Installation Manual DEH41550 R06
Clean and Grease Breaker
1.
Before installing or operating a breaker, refer to the breaker instruction manual for pre-operation
inspection and test.
2.
Check thoroughly for any damaged or loose parts and for any dirt or foreign matter which may be in
the breaker.
3.
Clean those areas if necessary with a clean, lint-free rag and isopropyl alcohol or acetone.
4.
Be sure to apply a thin film of electrical grease DH0HD38 (Mobilgrease 28) to the primary disconnect
fingers (
Figure 7 and 7A
). GE part #193A1751P1 is a 1 oz. tube of Mobilgrease 28.
Figure 7. AKD-10—Primary Contacts or “Fingers” (Apply
Grease)
Figure 7A. AKD-10—Primary Contacts or “Fingers” (Apply