CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP
50
EPM 5000 series Advanced Power Meters
GE Multilin
9.7: Relay Mode
NOTE
: Relays are not available for the EPM 5200P.
SWITCH DESCRIPTION
Segment
Position
A
Reversal Imbalance Control
UP
!
Enable
DOWN
!
Disable
B
AND/OR Logic
UP
!
AND
DOWN
!
OR
C & D
Relay Control
see Table 8-4
Table 9-3
: SWITCH PACKS for 04P & 05P
The Switch PACKS in FUNCTIONS 4 and 5 of programming GROUP 0 control the relay position. Setting
the switches in different combinations allows the user to specify the conditions in which the relay will be
“SET” or “RESET.” The following table indicates possible configurations.
SWITCH C
SWITCH
D
DESCRIPTION
UP UP
FAIL-SAFE MODE
—The normal or non-event condition is set. RESET relay
on either out of limit condition. Relay acts as a protective switch if power is
interrupted. This alerts the user if the meter or the meter power is out.
UP
DOWN
N/A (Reserved for future features).
DOWN
UP
N/A (Reserved for future features).
DOWN DOWN
RESET MODE
—The normal or non-event condition is reset. SET relay on
either out of limit condition.
Table 9-4
DEFINITIONS:
RESET:
There is a short between “COM” and “N.C.” (Normally closed)
SET:
There is a short between “COM” and “N.O.” (Normally open)
(See Part I: Installation and Operation.)
Example 1
: Fail-safe mode normally set—non-event condition is set relay
Relay 1 will be “SET” if the instantaneous reading for frequency is between 58 Hz and 62 Hz. When all
other conditions exist, the relay will “RESET.”
NOTE:
Under this setup the relay acts as a protective switch
.
5 8 H z
6 2 H z
0 H z
R E S E T
R E S E T
L 1
L 2
S E T
N O P O W E R T O T H E U N I T
R E S E T
Summary of Contents for EPM 5300
Page 2: ......
Page 30: ...CHAPTER 4 COMMUNICATION INSTALLATION 26 EPM 5000 series Advanced Power Meters GE Multilin...
Page 70: ...CHAPTER 10 PROGRAMMING GROUP 1 66 EPM 5000 series Advanced Power Meters GE Multilin...
Page 88: ...CHAPTER 14 EXITING PROGRAMMING MODE 84 EPM 5000 series Advanced Power Meters GE Multilin...
Page 94: ...CHAPTER 15 PROGRAMMING QUICK REFERENCE 90 EPM 5000 series Advanced Power Meters GE Multilin...