CHAPTER 12: GROUPS 4, 5, AND 6 – SET LIMITS AND RELAYS
GE Multilin
EPM 5000 series Advanced Power Meters
77
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
Step 3:
a.
Press
AMPS
once.
!
Lower display is replaced with three dashes.
!
Follow this step for
DISABLING LIMITS
:
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
Step 4:
a.
Press
AMPS
once to Disable the Limit.
!
The display blanks momentarily, then the disabled
settings appears in middle and lower displays.
!
The
Set Above/Below
will be set to below.
!
Trip Relay 1
will be disabled.
!
Trip Relay 2
will be disabled.
!
The
Setup Level
will be set to 0000.
Step 5:
a.
Press
VOLTS
to change current Set Above/Below,
Trip Relay 1, and Trip Relay 2 settings.
!
This toggles the segments UP (above limit) or DOWN
(below limit).
b.
Press
AMPS
to store.
c.
Press
VOLTS
to toggle the second segment UP
(enable Relay 1) or DOWN (disable Relay 1).
d.
Press
AMPS
to store.
e
.
Press
MAX/MIN/LIMITS
to proceed to entering the
limit value.
f.
Press
AMPS
to store.
Summary of Contents for EPM 5300
Page 2: ......
Page 30: ...CHAPTER 4 COMMUNICATION INSTALLATION 26 EPM 5000 series Advanced Power Meters GE Multilin...
Page 70: ...CHAPTER 10 PROGRAMMING GROUP 1 66 EPM 5000 series Advanced Power Meters GE Multilin...
Page 88: ...CHAPTER 14 EXITING PROGRAMMING MODE 84 EPM 5000 series Advanced Power Meters GE Multilin...
Page 94: ...CHAPTER 15 PROGRAMMING QUICK REFERENCE 90 EPM 5000 series Advanced Power Meters GE Multilin...