background image

2

ESL 700 Series

Testing the Wiring for Continuity

After all universal mounting bases are installed, including the end-of-line

device, check the system wiring for continuity. Verify that the manually

operated continuity switch in each base is in the shorting position —

making contact with terminals 1 and 2 (for use at initial installation

only).  Use a screwdriver to reset any unshorted continuity switches (reset

by prying the jumper wire out of the plastic stopper). This establishes

continuity across the alarm initiating circuit at initial installation. The

wiring can now be tested for continuity using an ohmmeter or “megger.”

Installing the Detector Head

Base models 702RE and 702RU have a special plastic protrusion built in to

prevent insertion of the wrong heads. They are designed specifically for use

with only 731U  heads, which include auxiliary relay contacts, and are only

required when high voltage (i.e. 120 VAC) is connected to the auxiliary

relay. This prevents the installer from inserting a low voltage detector head

into a base containing damaging high voltages. Standard base models 702E

and 702U can be used with the 731U heads when 120 VAC is not present.

Every 700 Series base includes a continuity switch which shorts terminals

1 and 2 together for easy continuity testing. When a 700 Series head is

inserted, the continuity switch will be snapped back, out of the way, and

will no longer short terminals 1 and 2. The continuity switch can be

snapped back into its original position with a screwdriver, if necessary.

To install a detector head, insert the head and rotate it clockwise until it is

properly aligned and “sets” into the base (see Figure 6). Then rotate it an

additional 15 degrees to lock it in place. This action will automatically

“open” the continuity switch in the base and allow continuity in the

system to be established by the detector heads.

Removing the Detector Head

To remove the detector head turn it counterclockwise. However, if the

locking tab slot has been removed, insert a small screwdriver into the

locking tab slot on the side of the base and press in while simultaneously

turning the detector head counterclockwise (see Figure 7). When a

detector head is removed for cleaning or repair, continuity in the system is

broken. Continuity can be re-established by manually resetting the

continuity switch on the empty base with a screwdriver.

Consider the Locking Mechanism BEFORE Installation

Each detector head is equipped with a breakaway locking tab slot to prevent

unauthorized removal of the detector head (see Figure 3). For installations

where unauthorized removal of the detector head is not a concern, the head

can be removed by simply turning counterclockwise.

However, when the head must lock to the base, break away the locking tab

slot with a pair of pliers. Then, to remove the detector head, insert a small

screwdriver into the slot on the side of the base and press in while

simultaneously turning the detector head counterclockwise (see Figure 7).

Installing the Universal Base

The 701U and 702U 6-inch diameter universal mounting bases mount

directly to standard single-gang electrical boxes, 4-inch square, round, or

octagonal boxes, 3.5-inch octagonal boxes, and to WIREMOLD Nos.

5738A or 5739 fixture boxes. The 702E 4-inch diameter universal

mounting bases mount only to 3-inch round electrical boxes. Bases may

also be mounted without electrical boxes if approved by the AHJ or if

codes allow.

The 6-inch diameter bases have two parts; the base itself that mounts to

the electrical box or ceiling, and the base cover that conceals the

mounting screws (see Figure 4). The 6-inch diameter bases are shipped

loosely coupled to the base cover.

1. Mount the base. Align the molded line on the base with the base cover,

and twist clockwise to snap in place. To remove the base cover, simply

twist counter-clockwise to unsnap (see Figure 4).

2. Pull wire through the electrical box, then through the center opening

of the 700 Series universal base. Connect the wire to the appropriate

terminals according to the wiring diagrams (see Figure 1). Each base is

equipped with either three or six clamping type wire terminals and

bifurcated contact springs for contact with detector head circuit pins.

Each wire clamping terminal will accommodate two conductors up to

2.0 mm in diameter (#12 AWG).

3. Dress the wiring neatly and verify that the continuity switch (jumper

wire) is touching both terminal 1 and terminal 2. Securely fasten base

with appropriate hardware (see Figure 5).

CHECK ALL WIRING AND MOUNTING CONNECTIONS.

End-of-Line Supervision for Four-Wire Systems

NFPA 72 requires power wiring in four-wire systems to be supervised. This is

accomplished by installing a power supervision unit for the appropriate

control unit voltage at the end of the detector power circuit. ESL model

204–12/24 V power supervision relay—is recommended for both 12 VDC or

24 VDC operation. See 204–12/24 V installation instructions for more

information.

Figure 2. Fire sensor placement

4 in. (100mm)

minimum

4 in. (100mm)

minimum

12 in.

(300mm)

maximum

ceiling

acceptable here

never here

top of detector

acceptable here

side

wall

Figure 4.  The 6" diameter mounting base

Screwdriver slot to

unlock head

Base

Base cover

Align the molded lines on

the base and cover, then

twist to snap into place

.

Figure 3. Removing the locking tab slot

To lock, break out tab with pliars

firealarmresources.com

Summary of Contents for ESL 700 Series

Page 1: ...ery 9 seconds during normal condition Blinks once every second during trouble condition Latches on in alarm No indication during loss of power Normally Open Common Normally Closed End of Line Device 1 3 2 6 4 5 1 3 2 6 4 5 NOTE Alarm contacts shown in non alarm mode 700 Series 4 Wire Wiring Diagram 741UT Head Figure 1 Wiring diagrams RemoteLED Blinks every 9 seconds during normal condition Blinks ...

Page 2: ...orized removal of the detector head is not a concern the head can be removed by simply turning counterclockwise However when the head must lock to the base break away the locking tab slot with a pair of pliers Then to remove the detector head insert a small screwdriver into the slot on the side of the base and press in while simultaneously turning the detector head counterclockwise see Figure 7 In...

Page 3: ...tivity test If the error persists replace unit 2 3 Indication Unit is becoming insensitive Action Clean and reset the unit Rerun sensitivity test If the error persists replace the unit 4 7 Indication Unit is within normal sensitivity range Action N A 8 9 Indication Unit is becoming too sensitive Action Verify the optical chamber is snapped down securely Clean the unit and replace the optical chamb...

Page 4: ...ctor 711UT 2 wire photoelectric type smoke detector with rate of rise heat detector and fast response algorithms 721UT 2 wire photoelectric type with rate of rise heat detector with fast response algorithms remote test alarm trouble LED output 731U 2 wire photoelectric type smoke detector with auxiliary relay N C N O outputs UL Listed for releasing service 741UT 4 wire photoelectric type smoke det...

Reviews: