5-24
F60 Feeder Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
3.
Configure the data by making the following changes in the
PRODUCT SETUP
ÖØ
COMMUNICATION
ÖØ
IEC 61850 PROTO-
COL
Ö
GGIO1 STATUS CONFIGURATION
settings menu:
–
Set
GGIO1 INDICATION 1
to a FlexLogic™ operand used to provide the status of GGIO1.ST.Ind1.stVal (for example,
a contact input, virtual input, a protection element status, etc.).
The F60 must be rebooted (control power removed and re-applied) before these settings take effect.
The following procedure illustrates the reception configuration.
1.
Configure the reception dataset by making the following changes in the
PRODUCT SETUP
ÖØ
COMMUNICATION
ÖØ
IEC
61850 PROTOCOL
Ö
GSSE/GOOSE CONFIGURATION
ÖØ
RECEPTION
ÖØ
CONFIGURABLE GOOSE
Ö
CONFIGURABLE GOOSE
1
ÖØ
CONFIG GSE 1 DATASET ITEMS
settings menu:
–
Set
ITEM 1
to “GGIO3.ST.Ind1.q” to indicate quality flags for GGIO3 status indication 1.
–
Set
ITEM 2
to “GGIO3.ST.Ind1.stVal” to indicate the status value for GGIO3 status indication 1.
The reception dataset now contains a set of quality flags, a single point status Boolean value, and a floating point ana-
log value. This matches the transmission dataset configuration above.
2.
Configure the GOOSE service settings by making the following changes in the
INPUTS/OUTPUTS
ÖØ
REMOTE DEVICES
ÖØ
REMOTE DEVICE 1
settings menu:
–
Set
REMOTE DEVICE 1 ID
to match the GOOSE ID string for the transmitting device. Enter “GOOSEOut_1”.
–
Set
REMOTE DEVICE 1 ETYPE APPID
to match the ETHERTYPE application ID from the transmitting device. This is
“0” in the example above.
–
Set the
REMOTE DEVICE 1 DATASET
value. This value represents the dataset number in use. Since we are using
configurable GOOSE 1 in this example, program this value as “GOOSEIn 1”.
3.
Configure the data by making the following changes in the
INPUTS/OUTPUTS
ÖØ
REMOTE INPUTS
ÖØ
REMOTE INPUT 1
settings menu:
–
Set
REMOTE IN 1 DEVICE
to “GOOSEOut_1”.
–
Set
REMOTE IN 1 ITEM
to “Dataset Item 2”. This assigns the value of the GGIO3.ST.Ind1.stVal single point status
item to remote input 1.
Remote input 1 can now be used in FlexLogic™ equations or other settings. The F60 must be rebooted (control power
removed and re-applied) before these settings take effect.
The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value
in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a com-
plete SCD file is created by third party substation configurator software.
For intercommunication between F60 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset contains
the same DNA and UserSt bit pairs that are included in GSSE messages. All GOOSE messages transmitted by the F60
(DNA/UserSt dataset and configurable datasets) use the IEC 61850 GOOSE messaging services (for example, VLAN sup-
port).
Set the
CONFIG GSE 1 FUNCTION
function to “Disabled” when configuration changes are required. Once changes are
entered, return the
CONFIG GSE 1 FUNCTION
to “Enabled” and restart the unit for changes to take effect.
PATH:...TRANSMISSION
ÖØ
CONFIGURABLE GOOSE 1(8)
ÖØ
CONIFIG GSE 1(64) DATA TIMES
Ö
ITEM 1(64)
To create a configurable GOOSE dataset that contains an IEC 61850 Single Point Status indication and its associated qual-
ity flags, the following dataset items can be selected: “GGIO1.ST.Ind1.stVal” and “GGIO1.ST.Ind1.q”. The F60 will then cre-
ate a dataset containing these two data items. The status value for GGIO1.ST.Ind1.stVal is determined by the FlexLogic™
operand assigned to GGIO1 indication 1. Changes to this operand will result in the transmission of GOOSE messages con-
taining the defined dataset.
CONFIG GSE 1
DATASET ITEMS
ITEM 1:
GGIO1.ST.Ind1.stVal
Range: all valid MMS data item references for
transmitted data
NOTE
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...