F60 Feeder Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
The optional user-programmable pushbuttons (specified in the order code) provide an easy and error-free method of enter-
ing digital state (on, off) information. The number of available pushbuttons is dependent on the faceplate module ordered
with the relay.
•
Type P faceplate: standard horizontal faceplate with 12 user-programmable pushbuttons.
•
Type Q faceplate: enhanced horizontal faceplate with 16 user-programmable pushbuttons.
The digital state can be entered locally (by directly pressing the front panel pushbutton) or remotely (via FlexLogic™ oper-
ands) into FlexLogic™ equations, protection elements, and control elements. Typical applications include breaker control,
autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control level of
password protection.
The user-configurable pushbuttons for the enhanced faceplate are shown below.
Figure 5–8: USER-PROGRAMMABLE PUSHBUTTONS (ENHANCED FACEPLATE)
The user-configurable pushbuttons for the standard faceplate are shown below.
Figure 5–9: USER-PROGRAMMABLE PUSHBUTTONS (STANDARD FACEPLATE)
Both the standard and enhanced faceplate pushbuttons can be custom labeled with a factory-provided template, available
online at
. The EnerVista UR Setup software can also be used to create labels for the enhanced
faceplate.
Each pushbutton asserts its own “On” and “Off” FlexLogic™ operands (for example,
PUSHBUTTON 1 ON
and
PUSHBUTTON
1 OFF
). These operands are available for each pushbutton and are used to program specific actions. If any pushbutton is
active, the
ANY PB ON
operand will be asserted.
Each pushbutton has an associated LED indicator. By default, this indicator displays the present status of the correspond-
ing pushbutton (on or off). However, each LED indicator can be assigned to any FlexLogic™ operand through the
PUSHBTN
1 LED CTL
setting.
The pushbuttons can be automatically controlled by activating the operands assigned to the
PUSHBTN 1 SET
(for latched and
self-reset mode) and
PUSHBTN 1 RESET
(for latched mode only) settings. The pushbutton reset status is declared when the
PUSHBUTTON 1 OFF
operand is asserted. The activation and deactivation of user-programmable pushbuttons is dependent
on whether latched or self-reset mode is programmed.
•
Latched mode
: In latched mode, a pushbutton can be set (activated) by asserting the operand assigned to the
PUSH-
BTN 1 SET
setting or by directly pressing the associated front panel pushbutton. The pushbutton maintains the set state
until deactivated by the reset command or after a user-specified time delay. The state of each pushbutton is stored in
non-volatile memory and maintained through a loss of control power.
The pushbutton is reset (deactivated) in latched mode by asserting the operand assigned to the
PUSHBTN 1 RESET
set-
ting or by directly pressing the associated active front panel pushbutton.
842814A1.CDR
USER
LABEL 1
USER
LABEL 2
USER
LABEL 3
USER
LABEL 4
USER
LABEL 5
USER
LABEL 6
USER
LABEL 7
USER
LABEL 8
USER
LABEL 9
USER
LABEL 10
USER
LABEL 11
USER
LABEL 12
USER
LABEL 13
USER
LABEL 14
USER
LABEL 15
USER
LABEL 16
USER LABEL
USER LABEL
USER LABEL
USER LABEL
USER LABEL
USER LABEL
7
9
11
8
10
12
USER LABEL
1
3
5
2
4
6
USER LABEL
USER LABEL
USER LABEL
USER LABEL
USER LABEL
842779A1.CDR
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...