6-8
F60 Feeder Protection System
GE Multilin
6.2 STATUS
6 ACTUAL VALUES
6
6.2.13 HI-Z STATUS
PATH: ACTUAL VALUES
Ö
STATUS
ÖØ
HIZ STATUS
The current status of high-impedance fault detection element is displayed here. Refer to
Theory of operation
for information
on element status determination. The arc fault detection confidence is also displayed.
6.2.14 DIRECT INPUTS
PATH: ACTUAL VALUES
Ö
STATUS
ÖØ
DIRECT INPUTS
The
AVERAGE MSG RETURN TIME
is the time taken for direct output messages to return to the sender in a direct input/output
ring configuration (this value is not applicable for non-ring configurations). This is a rolling average calculated for the last
ten messages. There are two return times for dual-channel communications modules.
The
UNRETURNED MSG COUNT
values (one per communications channel) count the direct output messages that do not
make the trip around the communications ring. The
CRC FAIL COUNT
values (one per communications channel) count the
direct output messages that have been received but fail the CRC check. High values for either of these counts may indicate
on a problem with wiring, the communication channel, or one or more relays. The
UNRETURNED MSG COUNT
and
CRC FAIL
COUNT
values can be cleared using the
CLEAR DIRECT I/O COUNTERS
command.
The
DIRECT INPUT 1
to
DIRECT INPUT (32)
values represent the state of each direct input.
HIZ STATUS
HIZ STATUS:
NORMAL
Range: Normal, Coordination Timeout, Armed, Arcing,
Down Conductor
MESSAGE
ARC CONFIDENCE A:100
B:100 C:100 N:100 %
DIRECT INPUTS
AVG MSG RETURN
TIME CH1: 0 ms
MESSAGE
UNRETURNED MSG
COUNT CH1: 0
MESSAGE
CRC FAIL COUNT
CH1: 0
MESSAGE
AVG MSG RETURN
TIME CH2: 0 ms
MESSAGE
UNRETURNED MSG
COUNT CH2: 0
MESSAGE
CRC FAIL COUNT
CH2: 0
MESSAGE
DIRECT INPUT 1:
On
MESSAGE
DIRECT INPUT 2:
On
↓
MESSAGE
DIRECT INPUT 32:
On
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...